Loading...
2015-0545 Clark (Balas Homes).pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: May 12, 2015 TO: Balas Homes jonathan@balashomes.com FROM: Andrew Gahan, Plans Examiner RE: Plan Check: BLD2015-0545 Project: Clark Remodel Project Address: 801 Caspers Street During a review of the plans by the Building Division for the above noted project, it was found that the following information, clarifications, or changes are needed. A complete review cannot be performed until the revised plans/documents, including a written response indicating where the ‘clouded’ or otherwise highlighted changes can be found on the revised plans, have been submitted to a Permit Coordinator. Reviews by other divisions, such as Planning, Engineering, or Fire, may result in additional comments. 1.It can be assumed that new beam will be supported at one end by the existing post. However the other end of the new beam will produce a new point load in a new location. Please clarify how the aforementioned new point load will be supported, and verify that there is a footing/foundation below for bearing. 2.Please note that all smoke detectors must be interconnected and hard wired during the course of this remodel per IRC R314. Additionally, carbon monoxide detectors must be installed per IRC R315. 3.Please note that any insulated element which is disturbed during construction must have the insulation upgraded to the current specifications set forth in the Washington State Energy Code Table 402.1.1.