2015-0569 Spuds type I hood - Burgess Design.pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: May 19, 2015 TO: Polar Bear Mechanical polarbearrefrigeration.com FROM: Chuck Miller, Plans Examiner RE: Plan Check: BLD2015-0569 Project: Spuds Type I Hood Project Address: 174 Sunset Avenue S During a review of the plans by the Building Division for the above noted project, it was found that the following information, clarifications, or changes are needed. A complete review cannot be performed until the revised plans/documents, including a written response indicating where the ‘clouded’ or otherwise highlighted changes can be found on the revised plans, have been submitted to a Permit Coordinator. Reviews by other divisions, such as Planning, Engineering, or Fire, may result in additional comments. General Review Notes: 1.Work related to the required fire suppression system to be installed for the Type I hood is to be done under a separate permit. 2.Complete and return the attached City of Edmonds ‘Commercial Kitchen Hood Worksheet’ or provide on the plans the following information: Details regarding the exhaust system to be installed. · Details regarding the make-up air system to be installed. · On sheet A.9.1 – Details: 3.Detail G – Noncombustible Furring @ Kitchen Hood – Coordinate the construction of the noncombustible wall surface with that proposed under the tenant improvement permit – BLD2015-0392. Changes appear to have been made during the separate review process that does not consistently represent the work to be completed meeting the requirements of International Mechanical Code (IMC) 507.9. On sheet A.9.2 – Details: 4.Detail J – Section @ Kitchen and Dining – Provide on the plans a detail, and a reference to it, for the required construction of the one-hour fire-resistance rated construction of the grease duct enclosure per IMC 506.3.11/International Building Code (IBC) 713.