2015-0579 Schell addition-remodel - Wise.pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: June 15, 2015 TO: Sara Wise sjw@sarawise.com FROM: Chuck Miller, Plans Examiner RE: Plan Check: BLD2015-0579 Project: Schell addition-remodel rd Project Address: 10624 243 Place SW During a review of the plans by the Building Division for the above noted project, it was found that the following information, clarifications, or changes are needed. A complete review cannot be performed until the revised plans/documents, including a written response indicating where the ‘clouded’ or otherwise highlighted changes can be found on the revised plans, have been submitted to a Permit Coordinator. Reviews by other divisions, such as Planning, Engineering, or Fire, may result in additional comments. On sheet S2.1 – Main Floor Framing/Foundation Plan: 1.Indicate on the plans the required widened/isolated footing to support the loads below the south-most bearing of the east 3-1/2x11-7/8 LSL - Continuous B2 Rim – along gridline ‘2’. The point load at the end of the east ‘Cont. B2 Rim’ from the south ‘Cont. B2 Rim’ appears to be a bit low, and the footing represented in detail ‘3/S3.2’ undersized, for the loads anticipated by the represented construction.. On sheet S3.2 – Concrete Details: 2.Detail 3 – Interior Cripple Wall at Crawl Space – Clarify the difference in the depth of the proposed footing and of the required embedment depth of the anchorage for the ‘HDU4’ holdowns along gridline ‘2’ on sheet ‘S2.1’ – Main Floor Framing/Foundation Plan.