City of Edmonds
PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
DATE: May 27, 2015
TO: Ghorghe Vasile
gigiv90@yahoo.com
FROM: Chuck Miller, Plans Examiner
RE: Plan Check: BLD2015-0581
Project: Vasile addition-AFU
th
Project Address: 20222 76 Avenue W
During a review of the plans by the Building Division for the above noted project, it was found that
the following information, clarifications, or changes are needed. A complete review cannot be
performed until the revised plans/documents, including a written response indicating where the
clouded or otherwise highlighted changes can be found on the revised plans, have been submitted
to a Permit Coordinator. Reviews by other divisions, such as Planning, Engineering, or Fire, may
result in additional comments.
General Review Notes:
1.The purpose of this building permit is an addition to and remodel of an existing single
family dwelling, and to verify the required construction for the use of the structure for an
intended use as an Adult Family Home (AFH). The allowance for the use of the structure
as an AFH is determined by the approval of the Washington State Department of Social and
Health Services (DSHS). An important part of the DSHS AFH approval process is the
Adult Family Home (AFH) Local Building Inspection Checklist see attachment City of
Edmonds Adult Family Home Permit Submittal Requirements. This form contains very
specific information regarding the requirements for an AFH that may not be represented on
the building plans but will be verified by field inspection. The following plan review
comments reflect the requirements found on the AFH checklist in addition to those
regarding the submitted construction documents.
On the City of Edmonds Development Services Residential Building Permit Application:
2.Project Valuation Provide a document establishing the building valuation using the criteria
listed in the Edmonds Community Development Code (ECDC) 19.70.015 see attached.
The amount stated on the Building Application appears to be lower than that anticipated by
the represented work to be done and standard methodology of determining valuation.
On the DSHS Adult Family Home (AFH) Local Building Inspection Checklist:
3.Complete sections 1, 2, 3, and 4 and return to the Permit Center prior to the issuance of the
permit.
On sheet A-1 Floor Plan:
4.Provide a Fire Exit Plan, developed for the emergency evacuation of residents, to be
reviewed and, upon approval, posted in a conspicuous place in the building per the City of
Edmonds Adult Family Home Permit Submittal Requirements.
5.Indicate on the plans the location of the fire extinguishers per the City of Edmonds Adult
Family Home Permit Submittal Requirements.
6.Change on the plans the identifier for each of the bedrooms from 1, 2, 3, 4, 5 to A, B, C,
D, E per the DSHS checklist section 3.
7.Label on the plans all components for exiting (step, ramps, etc.) per the DSHS checklist
section 3 and International Residential Code (IRC) R325.2.
8.Indicate on the plans the size, species, grade, and spacing of the framing members used for
the roof and ceiling joists to guide proper review, construction, and inspection of the work
associated with the removal of the non-bearing wall in the Kitchen.
On sheet A-3 Elevations/Sections:
9.Section 2 Section @ New Porch Change on the plans the sheet number from A-5 to A-
4 for the callout of the new footing.
10.Section 3 Section @ New Porch Clarify the note Truss per plan for the roof framing
over the New Porch. No details for the construction of the trusses could be found among
the submitted construction documents.
On sheet A-4 Foundation Plan:
11.Detail 2 Typical Footing with Slab
a.Clarify the reference per S.W. table on S-3. for the required attachment of the
exterior sheathing to the bottom plate. Sheet S-3 could not be found among the
submitted construction documents.
b.Note 4 - Clarify the note Refer to shear wall table on S-3. for the required
attachment of the bottom plate to the foundation. Sheet S-3 could not be found
among the submitted construction documents.
c.Note 5.3 - Clarify the note refer to shear wall table on S-3. for the required
anchor bolts to be used to attach the bottom plate to the foundation. Sheet S-3
could not be found among the submitted construction documents.