2015-0581 Vasile addition-AFH - Custom Design.pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: May 27, 2015 TO: Ghorghe Vasile gigiv90@yahoo.com FROM: Chuck Miller, Plans Examiner RE: Plan Check: BLD2015-0581 Project: Vasile addition-AFU th Project Address: 20222 76 Avenue W During a review of the plans by the Building Division for the above noted project, it was found that the following information, clarifications, or changes are needed. A complete review cannot be performed until the revised plans/documents, including a written response indicating where the ‘clouded’ or otherwise highlighted changes can be found on the revised plans, have been submitted to a Permit Coordinator. Reviews by other divisions, such as Planning, Engineering, or Fire, may result in additional comments. General Review Notes: 1.The purpose of this building permit is an addition to and remodel of an existing single family dwelling, and to verify the required construction for the use of the structure for an intended use as an ‘Adult Family Home’ (AFH). The allowance for the use of the structure as an AFH is determined by the approval of the Washington State Department of Social and Health Services (DSHS). An important part of the DSHS AFH approval process is the ‘Adult Family Home (AFH) Local Building Inspection Checklist’ – see attachment ‘City of Edmonds Adult Family Home Permit Submittal Requirements’. This form contains very specific information regarding the requirements for an AFH that may not be represented on the building plans but will be verified by field inspection. The following plan review comments reflect the requirements found on the AFH checklist in addition to those regarding the submitted construction documents. On the City of Edmonds ‘Development Services Residential Building Permit Application’: 2.Project Valuation – Provide a document establishing the building valuation using the criteria listed in the Edmonds Community Development Code (ECDC) 19.70.015 – see attached. The amount stated on the ‘Building Application’ appears to be lower than that anticipated by the represented work to be done and standard methodology of determining valuation. On the DSHS ‘Adult Family Home (AFH) Local Building Inspection Checklist’: 3.Complete sections 1, 2, 3, and 4 and return to the Permit Center prior to the issuance of the permit. On sheet A-1 – Floor Plan: 4.Provide a ‘Fire Exit Plan’, developed for the emergency evacuation of residents, to be reviewed and, upon approval, posted in a conspicuous place in the building per the City of Edmonds ‘Adult Family Home Permit Submittal Requirements’. 5.Indicate on the plans the location of the fire extinguishers per the City of Edmonds ‘Adult Family Home Permit Submittal Requirements’. 6.Change on the plans the identifier for each of the bedrooms from ‘1, 2, 3, 4, 5’ to ‘A, B, C, D, E’ per the DSHS checklist section 3. 7.Label on the plans all components for exiting (step, ramps, etc.) per the DSHS checklist section 3 and International Residential Code (IRC) R325.2. 8.Indicate on the plans the size, species, grade, and spacing of the framing members used for the roof and ceiling joists to guide proper review, construction, and inspection of the work associated with the removal of the ‘non-bearing wall’ in the ‘Kitchen’. On sheet A-3 – Elevations/Sections: 9.Section 2 – Section @ New Porch – Change on the plans the sheet number from ‘A-5’ to ‘A- 4’ for the callout of the new footing. 10.Section 3 – Section @ New Porch – Clarify the note ‘Truss per plan’ for the roof framing over the ‘New Porch’. No details for the construction of the trusses could be found among the submitted construction documents. On sheet A-4 – Foundation Plan: 11.Detail 2 – Typical Footing with Slab a.Clarify the reference ‘…per S.W. table on S-3.’ for the required attachment of the exterior sheathing to the bottom plate. Sheet ‘S-3’ could not be found among the submitted construction documents. b.Note 4 - Clarify the note ‘Refer to shear wall table on S-3.’ for the required attachment of the bottom plate to the foundation. Sheet ‘S-3’ could not be found among the submitted construction documents. c.Note 5.3 - Clarify the note ‘…refer to shear wall table on S-3.’ for the required anchor bolts to be used to attach the bottom plate to the foundation. Sheet ‘S-3’ could not be found among the submitted construction documents. Page 2 of 2