City of Edmonds
PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
DATE: June 12, 2015
TO: Bell/Reed
ralphrbell@gmail.com
FROM: Chuck Miller, Plans Examiner
RE: Plan Check: BLD2015-0634
Project: Bell/Reed carport-deck
Project Address: 615 Main Street #C
During a review of the plans by the Building Division for the above noted project, it was found that
the following information, clarifications, or changes are needed. A complete review cannot be
performed until the revised plans/documents, including a written response indicating where the
clouded or otherwise highlighted changes can be found on the revised plans, have been submitted
to a Permit Coordinator. Reviews by other divisions, such as Planning, Engineering, or Fire, may
result in additional comments.
On sheets 1 and 2:
1.Clarify the callout for the 6x8 beams to be used to support the loads from the carport/deck
joists. They appear to be over spanned and fail in bending.
On sheet 2:
2.Indicate on the plans the proposed diameter, length, and spacing of the lags to be used to
attach the ledger to the building.
On sheets 2 and 3:
3.Indicate on the plans the span, or distance between the supporting beams, and the amount of
cantilever, or overhang at the north end, of the proposed 2x8 joists.
4.Indicate on the plans the span, or distance between the supporting posts, of the proposed 6x8
beams.
On sheet 4:
5.Clarify the note all others anchor to slab. used to describe the support below the
majority of the posts bearing the loads of the carport/deck. Using the general dimensions
given on other sheets, footings ranging from 12x12 to 16x16 would be required below the
posts. Re-use of existing footings is permissible if the loads are distributed similar to that of
the prior construction. Use of the slab alone is inadequate.