2015-0639 Pruett addition-proposed ADU - Shapiro Arch.pdf
City of Edmonds
PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
DATE: August 3, 2015
TO: AD Shapiro Architects
Tony Shapiro
tonys@adshipiro.com
FROM: Chuck Miller, Plans Examiner
RE: Plan Check: BLD2015-0639
Project: Pruett addition-proposed ADU
nd
Project Address: 9011 192 Street SW
During a review of the plans by the Building Division for the above noted project, it was found that
the following information, clarifications, or changes are needed. A complete review cannot be
performed until the revised plans/documents, including a written response indicating where the
clouded or otherwise highlighted changes can be found on the revised plans, have been submitted
to a Permit Coordinator. Reviews by other divisions, such as Planning, Engineering, or Fire, may
result in additional comments.
General Review Note:
1.The purpose of this building permit is for the work associated with a remodel and two-story
addition to an existing structure, and to verify the required construction for the use of a
portion of the structure for an intended use as an Accessory Dwelling Unit (ADU). The
allowance for the use of a portion of the lower level as an ADU is determined by the
approval of a Planning Division Type 2 Conditional Use Permit.
2.Provide an Existing Floor Plan including the present location of all mechanical appliances
(and their fuel gas demands) and plumbing fixtures.
3.Indicate on the plans the location of all of the relocated and added mechanical appliances
and their fuel gas demands. The proposed work and systems to support the separate
dwelling units have not been clearly represented on the permit application or the submitted
construction documents. Of particular concern is the gas piping sizing to meet the demands
of the installed appliances.
On sheet A 101 Cover Sheet, Site Plan, Code Notes, Vicinity Map, Project Team:
4.Bldg Code Data
a.Basic Allowable Floor Area Clarify the building area limit noted. It does not
appear to correspond to that indicated for R-3 or U occupancy classifications in
International Building Code (IBC) Table 503.
b.Areas Doubled for Multistory B Occupancy Clarify the building area noted. The
proposed use does not appear to be as a B occupancy, and IBC section 506.4 only
regards single occupancy buildings.
c.Total Area Allowed - Clarify the building area limit noted. It does not appear to
correspond to that indicated for R-3 or U occupancy classifications in
International Building Code (IBC) Table 503.
d.Occupant Load Clarify the noted occupant load factor. It does not appear to
correspond to that noted for Residential or Parking Garages per IBC Table
1004.1.2.
e.Occupancy Separation Clarify the required separation of occupancies. It does not
appear to correspond to that indicated for R and U occupancy classifications in
IBC Table 503.
5.Energy Code Data
a.Note #2 Indicate on the plans the requirement that in a building where the energy
use will increase, existing ceiling, wall, or floor cavities required to be insulated and
exposed during construction will comply with 2012 Washington State Energy Code
(WSEC) Table R402.1.1. Existing 2x4 walls exposed during construction shall be
insulated to a minimum of R-15.
b.Note #4 Change the U-factor for skylights from 0.80 to 0.50 per WSEC Table
R402.1.1.
c.Note #5 Clarify the note No insulation required since all slab is in unheated
area.. The existing structure is noted by the Snohomish County Assessors office
and in the Scope of Work Note #5 as being heated hydronically. Additional
slab-on-grade work appears to be proposed on sheet A102 Demolition Floor
Plan.
d.Note #8 Clarify the selected WSEC Table 406.2 option 3a. The existing structure
is noted by the Snohomish County Assessors office and in the Scope of Work
Note #5 as being heated hydronically. Option 3a regards furnace installations.
e.Note #8 Indicate on the plans the required maximum water use for showerheads
and kitchen sink faucets of 1.75 GPM, and for all other lavatories of 1.0 GPM, per
selected WSEC Table 406.2 option 5a.
f.Note #10 Add the wording and on each level per International Residential Code
(IRC) R314.3.
g.Note #11 (listed required insulation and fenestration factors) Change the following
information per the selected WSEC Table 406.2 option 1a:
Floor slab R-10 perimeter and under entire slab
·
Windows U=0.28
·
On sheet A 102 Code Sheet:
6.Demolition Floor Plan Clarify the difference in the square footage of the existing slab to
be removed for the new ADU slab noted above gridline 1.7 and that of the existing slab
where the new ADU is to be located indicated between gridlines F and G.
7.Building Notes
a.Egress Notes Edit the following information:
Change the minimum net clear opening of the emergency escape and rescue
·
openings from 224 inches to 24 inches.
Add the wording when measured from the bottom of the clear opening.
·
after the word levels per IRC 310.1.
Page 2 of 6
b.Shower Notes Clarify the wording regarding the use of gypsum board as a backer
for adhesive application of ceramic tile or other required nonabsorbent finish and in
areas subject to continuous high humidity or direct exposure to water. It does not
appear to coincide with that of IRC 702.3.8.
c.Garage Note Change the wording regarding the required dwelling/garage
separation from have a double to habitable per IRC Table R302.6.
d.Water Heater Notes Change the seismic zone for the required anchorage to resist
displacement from D2 to C, D, E, and F per Uniform Plumbing Code 507.2.
On sheets A 111 Main Floor Plan and A 112 Upper Floor Plan:
8.Indicate on the plans the location and extent of the masonry fireplace noted on sheet A202
North Elevation.
On sheet A 111 Main Floor Plan:
9.General notes regarding the proposed ADU - The creation of two separate dwelling units
within a structure originally designed as a single dwelling unit has very specific
requirements to meet the welfare and life safety requirements of the Building Division and
the community development concerns of the Planning Division. Refer to the attached
Accessory Dwelling Unit handout (see attachment) for guidance with the following plan
review comments:
a.Indicate on the plans the location of the water service shut off valve. It must be
equally accessible at all times to occupants of both dwelling units per Uniform
Plumbing Code (UPC) 606.3 or a separate valve can be installed for the portion of
the structure to be used as an ADU. The plumbing code requires a shut off valve
inside each dwelling unit, separate from the meter shut off.
b.Indicate on the plans the location of the water heater for the proposed ADU per IRC
R306.4.
c.Indicate on the plans the location of the natural gas service shut off valve. It must be
equally accessible at all times to occupants of both dwelling units per IRC G2420.1.3
or a separate valve can be installed for the portion of the structure to be used as an
ADU.
Unlike the water shut off, the valve at the meter is sufficient as long as equal access
is available.
d.Indicate on the plans the means to be used to provide comfort heat for the portion of
the structure to be used as an ADU per IRC R303.9. There must be at least one
thermostat in each dwelling unit to regulate the temperature per WSEC 403.1.1. The
manifold/controls of a hydronic heat system must be equally accessible at all times,
or a separate manifold/control must be available to independently regulate the
system.
e.Per the International Residential Code (IRC) definition of dwelling, and the
meeting of the provisions allowed in it for one accessory dwelling unit, the
construction of fire-resistance rated assemblies between the dwelling units is
optional. Two of the provisions will be met with the compliance of the conditional
use permit for the use of the portion of the structure as an ADU. The remaining
requirement All required smoke alarms in the accessory dwelling unit and the
primary dwelling unit are interconnected in such a manner that the actuation of one
Page 3 of 6
alarm will activate all alarms in both the primary dwelling unit and the accessory
dwelling unit. must be noted on the plans and verified in the field to allow for the
option to not construct fire-resistance rated assemblies between the dwelling units.
Otherwise, the proposed fire-resistance rated construction, and any related City of
Edmonds plan review comments, must achieve the requirements of IRC R302.3.
10.Main Floor Plan
a.Provide on the plans a door and window schedule, and a reference to it, for the
various door and window installations associated with this project. Of particular
interest are window required to be safety glazed per IRC R308, or serve as
emergency escape and rescue openings per IRC R310, and doors required to be fire-
resistance rated per IRC R302.4.
b.Indicate on the plans the required smoke alarm outside of, and in the immediate
vicinity of, Bedroom 1 per IRC R314.
c.Indicate on the plans the required carbon monoxide alarm outside of, and in the
immediate vicinity of, Bedroom 1 per IRC R314.
d.Clarify the callout for wall type WW31 along the east wall of space A106 Bath.
It does not appear to meet the requirements of IRC R302.3 see also plan review
note # 9.e above.
e.Clarify the callout for wall type WW25 along the south wall of space 101
Entry. No such wall type could be found on sheet A 113 or elsewhere among the
submitted construction documents.
f.Clarify the placement of a boiler in space 107 Boiler. It does not appear to meet
the combustion air requirements of IRC G2407.
g.Clarify the difference in the representation of windows marked A06 in the north
wall of space A104 Bedroom 1 and of that noted at that location on sheet S-2
Main Floor.
h.Clarify the difference in the representation of the window marked 01 and door
marked 101 in the east wall of space 101 Entry and of that noted at that
location on sheet S-2 Main Floor.
On sheet A 112 Upper Floor Plan:
11.Option A Upper Floor Plan
a.Provide on the plans a detail, and a reference to it, for the required construction of
the 1 hr rated hood exhaust chase from ADU kitchen below in compliance with
ASTM E 119 or UL 263 see also plan review note # 9.e above.
b.Clarify the represented structure along the east wall of space 104 - Kitchen. A
corresponding element could not be found on sheet A 201 East Elevation.
c.Clarify the difference in the representation of the windows in the west wall of space
201 Hall on sheet S-2 Upper Floor and on sheet S-3 Roof Level and
of that noted at that location on this sheet.
d.Clarify the difference in the representation of the windows marked A06 in the north
wall of space 203 Master Bedroom and of that noted at that location on sheet
S-2 Upper Floor and on sheet S-3 Roof Level.
Page 4 of 6
On sheet A 113 Roof Plan, Exterior Details, Partition Types:
12.Wall Legend WW 22 Clarify the indicated required thickness of the gypsum wallboard
to be installed. It does not appear to be that noted for GA File No. WP 3510 in the
Gypsum Association Fire Resistance Design Manual. The required fasteners (type, length,
shank, head diameter), and their spacing, must also be specified on the plans to guide proper
installation and inspection see also plan review note # 9.e above.
On sheet A 202 North & South Elevations:
13.North Elevation
a.Clarify the difference in the representation of the window marked A08 in the north
wall of space A106 Bath and of that shown on sheet A 111 Main Floor Plan
and sheet S-2 Detail #1 Main Floor.
b.Clarify the difference in the representation of the windows on each side of the
French doors in the south wall of space 103 Dining and of that shown on
sheet A 111 Main Floor Plan and sheet S-2 Detail #1 Main Floor.
On sheet A301 Building Sections:
14.Detail #1 301 ADU Master Bedroom Looking North - and Detail #3 Entry Stair Looking
West Indicate on the plans the required minimum 1-hour fire-resistance rated floor/ceiling
construction between the separate dwelling units per IRC 302.3 see also plan review note
#9.e above.
On sheet S-2 Structural Plans:
15.Detail #1 Main Floor
a.Indicate on the plans the minimum required post to support the loads below the
trimmer(s) between the two windows marked 43 in space 208 Studio/Office.
b.Clarify the callout for the 24x24 isolated footing to be used to support the north end
of beam B2-3 existing beam/3.5x11.875 PSL. It appears to be undersized for the
loads anticipated by the represented construction. The loads noted in the provided
structural calculations do not appear to account for the tributary load from the
existing roof on the cantilevered end of the beam. The south end of the existing
roof beam to remain appears to also be bearing at the same location.
16.Detail #2 Upper Floor
a.Provide on the plans a legend, or other description, indicating the meaning of the
letter-P-in-circle with arrow(s).
b.Clarify the represented structure along the east wall of space 104 - Kitchen. A
corresponding element could not be found on sheet A 201 East Elevation.
On sheet S-2 and/or sheet S-3 Structural Plans:
17.S-2 Upper Floor or S-3
a.Indicate on the plans the minimum required posts to support the loads below the west
ends of the girder trusses supporting the truss girder or 5.25x14 PSL (RB-2) over
space 203 Master Bedroom.
Page 5 of 6
b.Indicate on the plans the minimum required post to support the loads below the south
end of the beam used to support the south girder truss over the south-most window
marked A10 in the east wall of space 201 Hall.
On sheet S-3 Structural Plans:
18.Roof Level
a.Clarify the note 6,600 LBS OF TOTAL REACTIONS at each end of the truss
girder or 5.25x14 PSL (RB-2) over space 203 Master Bedroom. The load at the
north end appears to be lower than that anticipated by the represented construction.
b.Clarify the callout for the 2x10s to be installed at 24 inches on-center and be used as
roof rafters. They appear to be over spanned and fail in bending.
c.Clarify the represented structure along the east wall of space 104 - Kitchen. A
corresponding element could not be found on sheet A 201 East Elevation.
d.Indicate on the plans the required minimum existing beam to be verified used to
support the loads over the east and west walls of the Kitchen to guide proper
construction and inspection.
e.Clarify the placement of the notes Existing beam to be verified on the Roof
Level framing detail. The construction represented on detail 10/S-4 and 15/S4
suggest that the note might be more appropriate on Detail #2 Upper Floor on
sheet S-2.
On sheet S-4 Structural Details:
19.Detail #1 - Indicate on the plans the minimum required width of the foundation wall to guide
proper construction and inspection.
20.Details #10, #15, and #16 Indicate on the plans the required minimum attachment of the
bottom plate of the extended and spliced wall framing to the top plate of the existing
wall framing to resist lateral loads.
21.Detail #14 Clarify the callout for (3)2x6 under post below the midspan of the SIP roof.
It does not appear to correspond to the construction represented on sheet S-3 Roof Level.
22.Detail #18 Indicate on the plans the required installation of blocking between the wall
studs to be used for the attachment of the 2x ledger.
23.Detail #19 Indicate on the plans the required installation of blocking between the wall
studs to be used for the attachment of the 2x ledger.
Page 6 of 6