Loading...
2015-0641 O'Malley SFR2 - O'Neill.pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: August 14, 2015 TO: Bruce O’Neill mick@designworksconstruction.net FROM: Chuck Miller, Plans Examiner RE: Plan Check: BLD2015-0641 Project: O’Malley SFR Project Address: 754 Bell Street During a review of the plans by the Building Division for the above noted project, it was found that the following information, clarifications, or changes are needed. A complete review cannot be performed until the revised plans/documents, including a written response indicating where the ‘clouded’ or otherwise highlighted changes can be found on the revised plans, have been submitted to a Permit Coordinator. Reviews by other divisions, such as Planning, Engineering, or Fire, may result in additional comments. Items that recur on this list appear in italics. On sheet A-4: 1.Upper Floor Plan and Roof Framing Plan - Clarify the difference in the placement of the window marked ‘20’ and of that represented on the ‘East Elevation’ on sheet ‘A-7’, and noted in the provided structural calculations. The reduced size sheet ‘A-4’ in the provided structural calculations does not show a window (although there is a mark ‘20’). The shear wall calculations on page 4.7 of the provided structural calculation indicate shear wall segment widths of 9.5 feet and 5.5 feet, neither of which can be located adjacent the stairs without additional lateral design. On sheet A-5: 2.First Floor Framing Plan a.Indicate on the plans the required posts to support the compression loads below each end of the of the shearwalls marked ‘SSW24’ along wall line ‘B’ on sheet ‘A-3’ – Upper Floor Framing Plan. The response to the plan review comment states: Lower floor SSW24 has been added to the west shear wall along line “B” to utilize ‘Simpson SSW” details. (see plan for call outs). SSW24 on the east shear wall along line “B” is only on the main floor because wall below is concrete to top of lower main floor. (see plan for call outs). A full-height concrete wall below the first floor framing appears to have been added below the east-most main floor ‘SSW24’, so no posts are required below it. However, no changes appear to have made (by adding either posts or ‘SSW24s’) below the remaining two shearwalls marked ‘SSW24’ along wall line ‘B’ on sheet ‘A-3’ – Upper Floor Framing Plan. b.Indicate on the plans the required hanger or construction to support the loads at the The response to the plan north end of beam ‘FB-3’ – 3.5x11.875 2.05E PSL. review comment states: HSUL410 Added to plans to support end of FB 3. Per the manufacturer, the allowable load capacity of the ‘HSUL410’ is well below the loads noted in the provided structural calculations. c.Indicate on the plans the minimum required post to support the loads below the east end of beam ‘FB-4’ – 7x14 2.05E PSL. The hanger callout in response to the review comment above appears to have replaced/obscured the post noted on the construction documents submitted earlier. On sheet A-6: 3.Foundation Plan a.Clarify the location of the 24x24x12 isolated footing intended to support the loads below the converging ends of beams ‘FB-7’ – 3.5x11.875 2.05E PSL - and ‘FB-8’ – 3.5x9.5 2.05E PSL. It appears to be mis-located 2 feet to the east. b.Clarify the location of the 24x24x12 isolated footing intended to support the loads below the east end of beam ‘FB-8’ – 3.5x9.5 2.05E PSL. It appears to be mis- located 2 feet to the north. 4.Holdown Schedule a.Clarify the callout for the holdown marked ‘T-2’ – HDQU11-SDS2.5. Per the manufacturer, it appears that it is no longer available and there is quite a difference in the allowable tension loads when attached to a 6x6 for those similarly identified. HDQU11-SDS2.5 changed on The response to the plan review comment states: shear wall schedule to HHQU11-SDS2.5 (typo.) and 6x6 DF #1 noted on plan 1/A5. No change appears to have been made in the resubmitted construction documents. b.Indicate on the plans the required framing members to be used for the attachment of the holdown marked ‘T-3’ – HDQ8-SDS3. Per the manufacturer, it appears that a very specific wood member thickness and species of wood be used to develop the The response to the tension loads noted in the provided structural calculations. plan review comment states: Detail of the wall-to-wall connection is shown on 1- A5 and revise to show member called out on shear wall schedule in the comments column (6x6 DF #1). Also holdown is corrected to HHQU11-SDS2.5. No change appears to have been made in the resubmitted construction documents. Page 2 of 2