2015-0669 Spuds mechanical - Williams Mech.pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: June 11, 2015 TO: Williams Mechanical bill@williamsmechanical.com FROM: Chuck Miller, Plans Examiner RE: Plan Check: BLD2015-0669 Project: Spuds mechanical Project Address: 174 Sunset Avenue S During a review of the plans by the Building Division for the above noted project, it was found that the following information, clarifications, or changes are needed. A complete review cannot be performed until the revised plans/documents, including a written response indicating where the ‘clouded’ or otherwise highlighted changes can be found on the revised plans, have been submitted to a Permit Coordinator. Reviews by other divisions, such as Planning, Engineering, or Fire, may result in additional comments. General Review Note: 1.Provide on the plans a detail, designed and ‘stamped’ by an engineer, for the required support and attachment of rooftop unit ‘RTU-1’ per IMC 301.15/18, IBC 1609/1613, and ASCE 7-10 chapter 13. Notes on sheet ‘M-1’ of the plans and on page 9 of the ‘Submittal Data’ reference the ‘General Contractor/Design Professional of Record’ as being responsible for providing the engineering for the anchorage and restraint of the unit, however no information regard such a design could be found among the submittal documents for the tenant improvement project proceeding under permit BLD2015-0392.