2015-0685 Stevens Health Center TI - Freiheit.pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: June 29, 2015 TO: Freiheit & Ho Architects Craig Carney ccarney@fhoarch.com FROM: Chuck Miller, Plans Examiner RE: Plan Check: BLD2015-0685 Project: Stevens Health Center TI th Project Address: 21701 76 Avenue W During a review of the plans by the Building Division for the above noted project, it was found that the following information, clarifications, or changes are needed. A complete review cannot be performed until the revised plans/documents, including a written response indicating where the ‘clouded’ or otherwise highlighted changes can be found on the revised plans, have been submitted to a Permit Coordinator. Reviews by other divisions, such as Planning, Engineering, or Fire, may result in additional comments. On sheet A0.0 – Cover Sheet: 1.Project Data – Type of Construction – Clarify the proposed type of construction of ‘V-A’. Originally required to be constructed as a ‘Type IV 1-hour’ structure with a ‘F-2’ occupancy under the 1973 Uniform Building Code (UBC), it would now be considered type ‘II-A’ construction. To date, no record of a complete ‘Building Analysis’, or work completed under another permit that might affect the type of construction and allowable materials, can be found to support the construction classification as type ‘V-A’. 2.Description of Work – Change on the plans the project scope of work from “…(2) suites, suites 300A and 300B.” to “…(3) suites, suites 300A, 300B, and 301.”. The addition of the two walls appears to divide the existing suite – Suite 300 – into 3 separately accessed spaces. On sheet A1.0 – Third Floor Code Plan: 3.Detail 2/A3.0 – Third Floor Code Plan a.Clarify the difference in the configuration of the following areas and of that represented in the most recent permitted work completed under permit BLD2011- 0444: The door into the ‘new’ suite ‘301’ · The hall closet/storage adjacent the entry · The restroom · The closet/storage in the west-most space labeled ‘Lab’ · Neither the proposed scope of work nor the construction documents appear to include work in those areas. b.Clarify the use of ‘USF’ (usable square feet?) to determine the occupant loads of the areas shown. It does not appear to meet the occupant load factor criteria (gross/net floor area) of International Building Code (IBC) Table 1004.1.2. Adjust the occupant loads for each suite accordingly. Page 2 of 2