20150714151907216.pdfx.12
Building Envelope Engineering
DATE: July 2, 2015
TO: Chuck Miller, Plans Examiner
Building Division, City of Edmonds
FROM: BEE Consulting, LLC
RE: Plan Check: BLD2015-0689 -0690
Project: Edmonds Townhomes exterior envelope review response
Project Address: 624 & 628 Daley Sheet
Project No. 1501-1008
General Review Notes:
The proposed work appears to fall under the regulatory oversight of the Revised Code
of Washington (RCW) chapter 64.55.005. As such, the following requirements must be
met:
1. The building enclosure design documents must be `stamped' by a
licensed engineer or architect.
RESPONSE: Design documents are stamped by a licensed engineer.
2. The building enclosure design documents must contain a `stamped' statement
by the person `stamping' the building enclosure documents in substantially
the following form: "The undersigned has provided building enclosure
documents that in my professional judgement are appropriate to satisfy the
requirements of RCW 64.55.005 through 64.55.090.".
RESPONSE: "The undersigned has provided building enclosure documents
that in my professional judgement are appropriate to satisfy the requirements
of RCW 64.55.005 through 64.55.090." statement is added to the design
document. BEE also has included an input letter for submittal.
170 W. Dayton St. #1206 e Edmonds, WA 98020 @ T 425 672 3900 o F 425 712 8608 o www.bee-engineers.com
In addition to the above requirements prior to permit issuance, the following will be
required before a final inspection by the City of Edmonds can be performed on, and a
`certificate of occupancy' can be issued by the Building Division for, the permit when
issued:
® The `qualified inspector' shall prepare and submit to the City of Edmonds
Building Division a signed letter certifying that the building enclosure has
been inspected during the course of rehabilitative construction and that it has
been reconstructed in substantial compliance with the building enclosure
design documents.
RESPONSE: BEE will provide a final signed letter certifying that the building
enclosure has been inspected during the course of rehabilitative construction
and that it has been reconstructed in substantial compliance with the building
enclosure design documents.