Loading...
2015-0753 Pizza Hut remodel - CDA Pirscher Arch.pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: July 17, 2015 TO: CDA + Pirscher Architects carlp@cdaarch.com FROM: Chuck Miller, Plans Examiner RE: Plan Check: BLD2015-0753 Project: Pizza Hut remodel Project Address: 23830 Highway 99, #118 During a review of the plans by the Building Division for the above noted project, it was found that the following information, clarifications, or changes are needed. A complete review cannot be performed until the revised plans/documents, including a written response indicating where the ‘clouded’ or otherwise highlighted changes can be found on the revised plans, have been submitted to a Permit Coordinator. Reviews by other divisions, such as Planning, Engineering, or Fire, may result in additional comments. On sheet A2.0 – Equipment Plan & Schedule: 1.New Equipment Plan – Clarify the equipment callouts ‘marked’ as follows: ‘E-917’ · ‘S-914’ · ‘U-245’ · ‘U-910’ · No information for the equipment could be found in the ‘Equipment Legend’. On sheet A9.0 – Interior Construction Details: 2.Detail 2 – Stainless Steel @ Existing Wall – Provide on the plans a detail, and a reference to it, for the required construction enclosing the Type I hood where it penetrates the ceiling per International Mechanical Code (IMC) 507.10. 3.Detail 14 – Framed Fur Down – Indicate of the plans the required construction/attachment to structure at the top of the ‘furred-down’ wall to guide proper review, installation and inspection. On sheet 1 – Pizza Hut Wingstreet 3’ BD: 4.Clarify the difference in the provided information/specifications for the Type I hood to be installed and of that noted in the submittal documents for permit BLD2015-0821. The separate submittals should consistently represent the proposed and required work to be done to meet the provisions of the applicable codes.