2015-0753 Pizza Hut remodel - CDA Pirscher Arch.pdf
City of Edmonds
PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
DATE: July 17, 2015
TO: CDA + Pirscher Architects
carlp@cdaarch.com
FROM: Chuck Miller, Plans Examiner
RE: Plan Check: BLD2015-0753
Project: Pizza Hut remodel
Project Address: 23830 Highway 99, #118
During a review of the plans by the Building Division for the above noted project, it was found that
the following information, clarifications, or changes are needed. A complete review cannot be
performed until the revised plans/documents, including a written response indicating where the
clouded or otherwise highlighted changes can be found on the revised plans, have been submitted
to a Permit Coordinator. Reviews by other divisions, such as Planning, Engineering, or Fire, may
result in additional comments.
On sheet A2.0 Equipment Plan & Schedule:
1.New Equipment Plan Clarify the equipment callouts marked as follows:
E-917
·
S-914
·
U-245
·
U-910
·
No information for the equipment could be found in the Equipment Legend.
On sheet A9.0 Interior Construction Details:
2.Detail 2 Stainless Steel @ Existing Wall Provide on the plans a detail, and a reference to
it, for the required construction enclosing the Type I hood where it penetrates the ceiling per
International Mechanical Code (IMC) 507.10.
3.Detail 14 Framed Fur Down Indicate of the plans the required construction/attachment to
structure at the top of the furred-down wall to guide proper review, installation and
inspection.
On sheet 1 Pizza Hut Wingstreet 3 BD:
4.Clarify the difference in the provided information/specifications for the Type I hood to be
installed and of that noted in the submittal documents for permit BLD2015-0821. The
separate submittals should consistently represent the proposed and required work to be done
to meet the provisions of the applicable codes.