2015-0755 Red Twig mechanical - Ambient Control.pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: June 24, 2015 TO: Azose Commercial Properties pmiller@azose.com FROM: Chuck Miller, Plans Examiner RE: Plan Check: BLD2015-0755 Project: Red Twig mechanical th Project Address: 117 5 Avenue S During a review of the plans by the Building Division for the above noted project, it was found that the following information, clarifications, or changes are needed. A complete review cannot be performed until the revised plans/documents, including a written response indicating where the ‘clouded’ or otherwise highlighted changes can be found on the revised plans, have been submitted to a Permit Coordinator. Reviews by other divisions, such as Planning, Engineering, or Fire, may result in additional comments. City of Edmonds ‘Commercial Mechanical/HVAC Permit Submittal Requirements’: 1.Provide on the plans a detail, designed and ‘stamped’ by an engineer, for the required support and seismic attachment of rooftop unit per IMC 301.15/18, IBC 1609/1613, and ASCE 7-10 chapter 13.