City of Edmonds
PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
DATE: June 24, 2015
TO: Azose Commercial Properties
pmiller@azose.com
FROM: Chuck Miller, Plans Examiner
RE: Plan Check: BLD2015-0755
Project: Red Twig mechanical
th
Project Address: 117 5 Avenue S
During a review of the plans by the Building Division for the above noted project, it was found that
the following information, clarifications, or changes are needed. A complete review cannot be
performed until the revised plans/documents, including a written response indicating where the
clouded or otherwise highlighted changes can be found on the revised plans, have been submitted
to a Permit Coordinator. Reviews by other divisions, such as Planning, Engineering, or Fire, may
result in additional comments.
City of Edmonds Commercial Mechanical/HVAC Permit Submittal Requirements:
1.Provide on the plans a detail, designed and stamped by an engineer, for the required
support and seismic attachment of rooftop unit per IMC 301.15/18, IBC 1609/1613, and
ASCE 7-10 chapter 13.