City of Edmonds
Building Division
�J ATTN: Chuck Miller
PROJECT: Pizza Hut - Edmonds
CDA# 14012
SUBJECT. Response to City Comments
Pizza Hut Remodel
23830 Highway 99, #118
Edmonds, WA
PLAN CHECK NUMBER: BLD2015-0753
PARCEL NUMBER: 00451900200700
Dear Chuck Miller:
Below are our responses to your comments. Please refer to the included response letter from the structural
engineer for the structural portion.
COMMENTS:
On sheet A2.0 — Equipment Plan & Schedule:
1. New Equipment Plan — Clarify the equipment callouts `marked' as follows:
• `B-917'
• `S-914'
• `U-245'
• `U-910'
No information for the equipment could be found in the `Equipment Legend'.
Response: See A2.0 Reference to E -917,5-914,U-245 has been eliminated and U-914 has been
defined as ticket printer
On sheet A9.0 — Interior Construction Details:
2. Detail 2 — Stainless Steel @ Existing Wall — Provide on the plans a detail, and a reference to it, for
the required construction enclosing the Type I hood where it penetrates the ceiling per
International Mechanical Code (IMC) 507.10.
Response: See A9.1/Detail 1 for the enclosure for the Type I hood.
F:\JOBS\14012 Pizza Hut-Edmonds\Word\City\Comments\RESPONSE TO CITY COMMENTS 7-22-15.doe
Carl F. Pirscher, AIA
principal
20011 Ballinger Way NE Suite 200
PO BOX 55429
Shoreline, Washington 98155
Tel: (206)-368-9668
Fax: (206)-368-9558
3. Detail 14 — Framed Fur Down — Indicate of the plans the required construction/attachment to
structure at the top of the `furred -down' wall to guide proper review, installation and inspection.
Response: See A-9.1/Detail 2. The details shows the attachment to the structure.
On sheet 1 — Pizza Hut Wingstreet 3' BD:
4. Clarify the difference in the provided information/specifications for the Type I hood to be installed
and of that noted in the submittal documents for permit BLD2015-0821. The separate submittals
should consistently represent the proposed and required work to be done to meet the provisions of
the applicable codes.
Response: The prototype Captivaire Hood drawings have been taken out and See A2.0 now says
to see the Hood Drawing submitted separately.
Please do not esitate to call if you have any questions.
Sincerely,