20150929103537.pdfSeptember 24, 2015
Leif Bjorback, Building Official
City of Edmonds
R S. ,
Re: BLD2015-0949° rtu
Dear Mr. Bjorback HUH V ING luEPARTNE'
CITY OF EDM0NV%c'P'
Please find our responses below to your building review.
Comment #1
• Mechanical Drawings M1.01, M2.12, and M3.01 have been revised (and clouded) to indicate that all diffusers
and all return/exhaust grilles are provided with fire dampers to protect the openings.
• See Mechanical Drawings attached
Comment #2
• Doors 200, 201A, and 203A have been revised and clouded on Floor Plan A2.11 to swing in the direction of
exit travel. Changes have been made and bubbled.
Comment #3
• The north and west walls of SOILED WORK ROOM 204 have been revised (and clouded) to have a 1 -hour fire
rating, to complete the separation of the room from the rest of the space. Changes have been made and
bubbled.
Comment #4
• See Structural Drawings attached
Comment #5
• See Structural Drawings attached.
Sincerely,
Jeanelle Owens
I�7�f�1r7t 425 778.1530 7803 Edml1 76th Ave W, onds WA 9826uite 210 Www gba chitects comorated in the e of Washingtontgba
f 425.774
September
21, 2015
Jeanelle Owens
TG Architects
2191176th Ave W, Suite 210
Edmonds, WA 98026
Project: Kruger Clinic
Re: City of Edmonds Plan Check BLD2015-0949
Plan Review Comments
tA,ft0R4Q UE�° FITWERfib
CwiiY OF EDWI'lIO
Jeanelle,
We have reviewed the permit review comments from the City of Edmonds Building Division, dated September 17,
2015, with regard to the Kruger Clinic — SMG Urgent Care project, and have the following responses. Please note
our response numbers correspond to the comment number.
4. Sheet 52.11 has been revised and now shows the channels reinforcing the indicated beams.
5. Please see the Supplemental Structural Calculations, dated September 22, 2015, for the design of the
channel and connection.
Please call if you have questions,
Katie Blaesser, P.E. (CA)
Engineer
Lund Opsahl LLC
Attachments: Supplemental Structural Calculations, dated September 22, 2015
Sheet S2. 11, issued September 22, 2015
1201 First Avenue South, Suite 310 1 Seattle, Washington 98134 1 206-402-5156 1 www.lundopsahl.com
IVI
&AAZZE
T:425-672-1071 * F:425-778-8769 * www.mazzetti.com
19203 36th Avenue W, Suite 200 * Lynnwood, WA 98036
DATE: September 18, 2015 PROJECT #: 156-020
To: Jeanelle Owens PHONE: 425-778-1530
COMPANY: TGBA FAx:
PROJECT: SMG Urgent Care — Kruger Clinic
SUBJECT: Permit Revisions Narrative
COMMENTS
DWG DESCRIPTION
M0.01 Removed combination fire smoke damper symbol.
Added fire damper symbol to ceiling diffuser and exhaust grille symbols,
M2.12 Removed cross over duct over Central Work Area #205.
Added fire damper symbol to all ceiling supply diffusers and exhaust grilles.
Added fire rated grilles for all exhaust fans.
Added fire dampers in 5 ducts penetrating the Soiled Work Room #224 fire rated
Wall.
M3.01 Added `Fire Rated' to details 1 and 3 titles.
END OF MEMO
BY: Jon Della
SEP 2 1
CA OF EDMMIDS
C:\Users\Jowens\AppData\Local\Microsoft\Windows\Temporary Internet Files\Content.Outlook\MVTLOOCO\Project Memo - Permit