Loading...
20150929103537.pdfSeptember 24, 2015 Leif Bjorback, Building Official City of Edmonds R S. , Re: BLD2015-0949° rtu Dear Mr. Bjorback HUH V ING luEPARTNE' CITY OF EDM0NV%c'P' Please find our responses below to your building review. Comment #1 • Mechanical Drawings M1.01, M2.12, and M3.01 have been revised (and clouded) to indicate that all diffusers and all return/exhaust grilles are provided with fire dampers to protect the openings. • See Mechanical Drawings attached Comment #2 • Doors 200, 201A, and 203A have been revised and clouded on Floor Plan A2.11 to swing in the direction of exit travel. Changes have been made and bubbled. Comment #3 • The north and west walls of SOILED WORK ROOM 204 have been revised (and clouded) to have a 1 -hour fire rating, to complete the separation of the room from the rest of the space. Changes have been made and bubbled. Comment #4 • See Structural Drawings attached Comment #5 • See Structural Drawings attached. Sincerely, Jeanelle Owens I�7�f�1r7t 425 778.1530 7803 Edml1 76th Ave W, onds WA 9826uite 210 Www gba chitects comorated in the e of Washingtontgba f 425.774 September 21, 2015 Jeanelle Owens TG Architects 2191176th Ave W, Suite 210 Edmonds, WA 98026 Project: Kruger Clinic Re: City of Edmonds Plan Check BLD2015-0949 Plan Review Comments tA,ft0R4Q UE�° FITWERfib CwiiY OF EDWI'lIO Jeanelle, We have reviewed the permit review comments from the City of Edmonds Building Division, dated September 17, 2015, with regard to the Kruger Clinic — SMG Urgent Care project, and have the following responses. Please note our response numbers correspond to the comment number. 4. Sheet 52.11 has been revised and now shows the channels reinforcing the indicated beams. 5. Please see the Supplemental Structural Calculations, dated September 22, 2015, for the design of the channel and connection. Please call if you have questions, Katie Blaesser, P.E. (CA) Engineer Lund Opsahl LLC Attachments: Supplemental Structural Calculations, dated September 22, 2015 Sheet S2. 11, issued September 22, 2015 1201 First Avenue South, Suite 310 1 Seattle, Washington 98134 1 206-402-5156 1 www.lundopsahl.com IVI &AAZZE T:425-672-1071 * F:425-778-8769 * www.mazzetti.com 19203 36th Avenue W, Suite 200 * Lynnwood, WA 98036 DATE: September 18, 2015 PROJECT #: 156-020 To: Jeanelle Owens PHONE: 425-778-1530 COMPANY: TGBA FAx: PROJECT: SMG Urgent Care — Kruger Clinic SUBJECT: Permit Revisions Narrative COMMENTS DWG DESCRIPTION M0.01 Removed combination fire smoke damper symbol. Added fire damper symbol to ceiling diffuser and exhaust grille symbols, M2.12 Removed cross over duct over Central Work Area #205. Added fire damper symbol to all ceiling supply diffusers and exhaust grilles. Added fire rated grilles for all exhaust fans. Added fire dampers in 5 ducts penetrating the Soiled Work Room #224 fire rated Wall. M3.01 Added `Fire Rated' to details 1 and 3 titles. END OF MEMO BY: Jon Della SEP 2 1 CA OF EDMMIDS C:\Users\Jowens\AppData\Local\Microsoft\Windows\Temporary Internet Files\Content.Outlook\MVTLOOCO\Project Memo - Permit