Loading...
2015-0949 Kruger Clinic.pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: September 17, 2015 TO: Jeanelle Owens TGB Architects Email: jowens@tgbarchitects.com FROM: Leif Bjorback, Building Official RE: Plan Check: BLD2015-0949 Project: Kruger Clinic-SMG Urgent Care Project Address: 21600 Highway 99 #240 During review of the plans for the above noted project, it was found that the following information, clarifications or changes are needed. Please provide written responses as to where the changes can be found on the plans, and submit revised plans/documents to a permit coordinator in the Development Services Department. Thank you. Sheet A0.41 and M0.03 1.Penetrations through the 1 hour rated ceilings must be protected according to IBC 714.4. Show on the plans how the penetrations by ducts and exhaust fans are to be protected. Sheet A2.11 2.Doors serving an occupant load of 50 or more must swing in the direction of egress. Please reverse the swing of doors 200, 201A and 203A. IBC 1008.1.2 3.Soiled Work Room 204 appears to exceed 100 square feet, and must be protected by 1 hour assemblies. IBC Table 509 Structural 4.In the Forte structural calcs, floor beams at “line 2-span 1” and “line 6-span 2” are noted “Add channels to strengthen beam,” however, the channels are not shown on sheet S2.11. Please revise the plans as needed. 5.Please provide calcs for the C-channels at floor beams located at “line 4-span 4” and “line 4-span 5.”