2015-0996 Burlington Coat Factory mechanical - Heattransfer.pdf
City of Edmonds
PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
DATE: August 25, 2015
TO: Heattransfer Co.
Richard Sinnema
heattransfer1@aol.com
FROM: Chuck Miller, Plans Examiner
RE: Plan Check: BLD2015-0996
Project: Burlington Coat Factory mechanical
Project Address: 24111 Highway 99
During a review of the plans by the Building Division for the above noted project, it was found that
the following information, clarifications, or changes are needed. A complete review cannot be
performed until the revised plans/documents, including a written response indicating where the
clouded or otherwise highlighted changes can be found on the revised plans, have been submitted
to a Permit Coordinator. Reviews by other divisions, such as Planning, Engineering, or Fire, may
result in additional comments.
General Review Note:
1.Provide on the plans a detail, designed and stamped by an engineer, for the required
support and attachment of rooftop units RTU-1 and RTU-2 per IMC 301.15/18, IBC
1609/1613, and ASCE 7-10 chapter 13. The provided structural calculations appear to be a
design for rooftop mechanical replacement work done under permit BLD2014-0743.
Unfortunately, the proposed units to be replaced under this permit appear to be heavier and
larger than those replaced under permit BLD2014-0743, and beyond the design criteria of
the provided structural calculations.