Loading...
2015-1160 Rosewood Courte addition - Wright Arch.pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: October 28, 2015 TO: Charles Wright, Architect charles@wrightarch.com FROM: Chuck Miller, Plans Examiner RE: Plan Check: BLD2015-1160 Project: Rosewood Courte addition Project Address: 728 Edmonds Way During a review of the plans by the Building Division for the above noted project, it was found that the following information, clarifications, or changes are needed. A complete review cannot be performed until the revised plans/documents, including a written response indicating where the ‘clouded’ or otherwise highlighted changes can be found on the revised plans, have been submitted to a Permit Coordinator. nd Resubmittals must be made at the Development Services Department on the 2 Floor of City Hall. Permit Center hours are M, T, Th, & F from 8am-4:30pm. The Permit Center is closed on Wednesdays. Reviews by other divisions, such as Planning, Engineering, or Fire, may result in additional comments. General Review Note: 1.Washington State Energy Code (WSEC) Commercial Provisions Compliance Forms – Provide a completed ‘Lighting, Motor, and Transformer Permit Documents Checklist – LTG-CHK’ to guide proper review, installation, and inspection. On sheet A2.1: 2.Detail 2 - Living Room Floor Plan - Eliminate from the plans the following interior elevation callouts: 1/A6.1 · 2/A6.1 · 3/A6.1 · 4/A6.1 · There does not appear to be corresponding elevations and the similarly ‘numbered’ sections are properly referenced. On sheet A7.1: 3.Detail 9 – Eave at Patio Roof – Clarify the reference to detail ‘5/A7.1’. The referenced detail, or a detail corresponding to the indicated area, could not be found. 4.Detail 12 – Typical Wall Section – Change the detail reference from ‘17/A7.1’ to ‘13/A7.1’ to reflect the anticipated construction where referenced. 5.Detail 20 – Wall Section at Gas Fireplace - Clarify the reference to detail ‘11/A7.1’. The referenced detail, or a detail corresponding to the indicated area, could not be found. The construction represented in Detail ‘11/A7.2’ appears to be similar to that required except for the location of the foundation wall insulation. On sheet A7.2: 6.Detail 17 – Foundation at Patio Slab - Clarify the reference to detail ‘18 this sheet’. The referenced detail, or a detail corresponding to the indicated area, could not be found. Page 2 of 2