PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
DATE: October 28, 2015
TO: Charles Wright, Architect
charles@wrightarch.com
FROM: Chuck Miller, Plans Examiner
RE: Plan Check: BLD2015-1160
Project: Rosewood Courte addition
Project Address: 728 Edmonds Way
During a review of the plans by the Building Division for the above noted project, it was found that
the following information, clarifications, or changes are needed. A complete review cannot be
performed until the revised plans/documents, including a written response indicating where the
clouded or otherwise highlighted changes can be found on the revised plans, have been submitted
to a Permit Coordinator.
nd
Resubmittals must be made at the Development Services Department on the 2 Floor of City Hall.
Permit Center hours are M, T, Th, & F from 8am-4:30pm. The Permit Center is closed on
Wednesdays.
Reviews by other divisions, such as Planning, Engineering, or Fire, may result in additional
comments.
General Review Note:
1.Washington State Energy Code (WSEC) Commercial Provisions Compliance Forms
Provide a completed Lighting, Motor, and Transformer Permit Documents Checklist
LTG-CHK to guide proper review, installation, and inspection.
On sheet A2.1:
2.Detail 2 - Living Room Floor Plan - Eliminate from the plans the following interior
elevation callouts:
1/A6.1
·
2/A6.1
·
3/A6.1
·
4/A6.1
·
There does not appear to be corresponding elevations and the similarly numbered sections
are properly referenced.
On sheet A7.1:
3.Detail 9 Eave at Patio Roof Clarify the reference to detail 5/A7.1. The referenced
detail, or a detail corresponding to the indicated area, could not be found.
4.Detail 12 Typical Wall Section Change the detail reference from 17/A7.1 to 13/A7.1
to reflect the anticipated construction where referenced.
5.Detail 20 Wall Section at Gas Fireplace - Clarify the reference to detail 11/A7.1. The
referenced detail, or a detail corresponding to the indicated area, could not be found. The
construction represented in Detail 11/A7.2 appears to be similar to that required except for
the location of the foundation wall insulation.
On sheet A7.2:
6.Detail 17 Foundation at Patio Slab - Clarify the reference to detail 18 this sheet. The
referenced detail, or a detail corresponding to the indicated area, could not be found.
Page 2 of 2