2015-1185 Select Homes SFR - Nash.pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: November 23, 2015 TO: Select Homes, Inc. kayla.clark@outlook.com FROM: Chuck Miller, Plans Examiner RE: Plan Check: BLD2015-1185 Project: Select Homes SFR th Project Address: 929 9 Avenue N During a review of the plans by the Building Division for the above noted project, it was found that . A complete review cannot be the following information, clarifications, or changes are needed performed until the revised plans/documents, including a written response indicating where the ‘clouded’ or otherwise highlighted changes can be found on the revised plans, have been submitted to a Permit Coordinator. nd Resubmittals must be made at the Development Services Department on the 2 Floor of City Hall. Permit Center hours are M, T, Th, & F from 8am-4:30pm. The Permit Center is closed on Wednesdays. Reviews by other divisions, such as Planning, Engineering, or Fire, may result in additional comments. On sheet A6: 1.Upper Floor Plan a.Provide on the plans a detail, and a reference to it, for the required construction of the floor trusses to facilitate the installation of the specified holdowns along shear wall lines ‘A’ and ‘C’. b.Clarify the callout for the ‘T-2’ holdowns – MST48 – to tie each end of the ‘P1-6’ shear wall along the north wall of the ‘Master Bedroom’ to the beam below. c.Clarify the callout for the ‘T-1’ holdown – STHD14/14 RJ – at the east end of the ‘P1-6’ shear wall along wall line ‘B’.