2015-1185 Select Homes SFR - Nash.pdf
City of Edmonds
PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
DATE: November 23, 2015
TO: Select Homes, Inc.
kayla.clark@outlook.com
FROM: Chuck Miller, Plans Examiner
RE: Plan Check: BLD2015-1185
Project: Select Homes SFR
th
Project Address: 929 9 Avenue N
During a review of the plans by the Building Division for the above noted project, it was found that
. A complete review cannot be
the following information, clarifications, or changes are needed
performed until the revised plans/documents, including a written response indicating where
the clouded or otherwise highlighted changes can be found on the revised plans, have been
submitted to a Permit Coordinator.
nd
Resubmittals must be made at the Development Services Department on the 2 Floor of City
Hall. Permit Center hours are M, T, Th, & F from 8am-4:30pm. The Permit Center is closed
on Wednesdays.
Reviews by other divisions, such as Planning, Engineering, or Fire, may result in additional
comments.
On sheet A6:
1.Upper Floor Plan
a.Provide on the plans a detail, and a reference to it, for the required construction of
the floor trusses to facilitate the installation of the specified holdowns along shear
wall lines A and C.
b.Clarify the callout for the T-2 holdowns MST48 to tie each end of the P1-6
shear wall along the north wall of the Master Bedroom to the beam below.
c.Clarify the callout for the T-1 holdown STHD14/14 RJ at the east end of the
P1-6 shear wall along wall line B.