2015-1580 Roloff generator.pdf
City of Edmonds
PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
DATE: December 17, 2015
TO: Washington Energy Services
naida@nwpermit.com
FROM: Chuck Miller, Plans Examiner
RE: Plan Check: BLD2015-1580
Project: Roloff generator
th
Project Address: 720 14 Way
During a review of the plans by the Building Division for the above noted project, it was found that
. A complete review cannot be
the following information, clarifications, or changes are needed
performed until the revised plans/documents, including a written response indicating where
the clouded or otherwise highlighted changes can be found on the revised plans, have been
submitted to a Permit Coordinator.
nd
Resubmittals must be made at the Development Services Department on the 2 Floor of City
Hall. Permit Center hours are M, T, Th, & F from 8am-4:30pm. The Permit Center is closed
on Wednesdays.
Reviews by other divisions, such as Planning, Engineering, or Fire, may result in additional
comments.
On sheet 1:
1.Edmonds Site Plan Generator & A/C Placement Location
a.Clarify the representation of the generator installation between the two decks.
Generators must be installed per the International Mechanical Code (IMC), the
manufacturers installation requirements, and the National Fire Protection
Association (NFPA) 37. There must be a minimum clearance of 4 feet above, 3 feet
on the sides and front, and 18 inches on the back, between the unit and wooden
decks per the manufacturers installation requirements. Per the conditions of the
permit issuance, manufacturers specifications and installation instructions must be
provided to the Building Inspector at the time of inspection.
b.Clarify the difference in the proposed scope of work and of that represented on the
plan. There does not appear to be any information provided for the installation of the
A/C unit or notation of it as an existing installation.