2016-0078 Red Latern Chinese Restaurant type I hood - Great Sun Corp.pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: February 1, 2016 TO: Great Sun Corporation Keith Ta kta@greatsuncorp.com FROM: Chuck Miller, Plans Examiner RE: Plan Check: BLD2016-0078 th Project Address: 546 5 Avenue S Project: Red Lantern Chinese Restaurant Type I Hood Scope: disapproved Please be advised that the building plans for the above referenced project have been for the purposes of obtaining a building permit. During a review of the plans by the Building Division for compliance with the applicable building codes, it was found that the following . information, clarifications, or changes are neededReviews by other divisions, such as Planning, Engineering, or Fire, may result in additional comments that require attention beyond the scope of this letter. A complete review cannot be performed until the revised plans/documents, including a written response indicating where the ‘clouded’ or otherwise highlighted changes can be found on the revised plans, have been submitted to a Permit Coordinator. nd Resubmittals must be made at the Development Services Department on the 2 Floor of City Hall. Permit Center hours are M, T, Th, & F from 8am-4:30pm. The Permit Center is closed on Wednesdays. On sheet M-1: 1.Site/Roof Plan - Provide on the plans information regarding the installation, performance, and operation of the ‘existing hood to remain’ represented in the ‘Front View’ detail. The proposed hood to be installed under this permit cannot have an effect, or be affected, by the operation of the existing hood and its components (makeup air unit location, exhaust fan location, etc.). 2.Section Elevation View – Indicate on the plans the required installation of the field-applied grease duct enclosure (duct wrap) from the point at which the duct originates upwards toward the duct termination per IMC 506.3.11.2 and the product manufacturer. 3.Front View a.Indicate on the plans the required installation of the field-applied grease duct enclosure (duct wrap) from the point at which the duct originates upwards toward the duct termination per IMC 506.3.11.2 and the product manufacturer. b.Provide on the plans information regarding the installation, performance, and operation of the ‘existing hood to remain’. The proposed hood to be installed under this permit cannot have an effect, or be affected, by the operation of the existing hood and its components (makeup air unit location, makeup air supply location, exhaust fan location, etc.). Page 2 of 2