2016-0088 Red Lantern Chinese restaurant TI - King.pdf
City of Edmonds
PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
DATE: February 17, 2016
TO: Eddie King
edking11@hotmail.com
FROM: Chuck Miller, Plans Examiner
RE: Plan Check: BLD2016-0088
th
Project Address: 546 5 Avenue S
Project: Red Lantern Chinese restaurant
Scope: TI for restaurant A-2 occupancy group V-B construction - NFPA-13
sprinkler system required mechanical, plumbing, type I hood, fire suppression for
hood, fire sprinkler relocation, etc. under separate permits
disapproved
Please be advised that the building plans for the above referenced project have been
for the purposes of obtaining a building permit. During a review of the plans by the Building
Division for compliance with the applicable building codes, it was found that the following
.
information, clarifications, or changes are neededReviews by other divisions, such as Planning,
Engineering, or Fire, may result in additional comments that require attention beyond the scope of
this letter.
A complete review cannot be performed until the revised plans/documents, including a
written response indicating where the clouded or otherwise highlighted changes can be
found on the revised plans, have been submitted to a Permit Coordinator.
nd
Resubmittals must be made at the Development Services Department on the 2
Floor of City
Hall. Permit Center hours are M, T, Th, & F from 8am-4:30pm. The Permit Center is closed
on Wednesdays.
On sheet A1 Site Plan-Floor Plan-RCP Plan-Section/ADA Detail:
1.Scope of Work Clarify the indicated addition of a Bar as part of the proposed work under
this permit. There does not appear to be a corresponding area represented on detail 5
Proposed New Door Schedule (change to Proposed Floor Plan) see also review
comments #2a-2c.
2.Project Data Item #6 Clarify the indicated occupant loads as follows:
a.Entrance/Dinning (sic) Area The indicated floor area appears to be a bit low and
may not include the floor area adjacent the Beverage Serve Station. If this area is
to be used as a Bar (patrons served/consuming drinks etc.) the appropriate occupant
load factors per International Building Code (IBC) Table 1004.1.2 (i.e.
Concentrated Assembly or Standing Assembly) must be applied.
b.Kitchen Bar Area The indicated floor area appears to be a bit high and to include
an area identified as a Bar (patrons served/consuming drinks etc.) and not part of
the Kitchen and its applicable occupant load factor. Any area to be used as a Bar
(patrons served/consuming drinks etc.) must have the appropriate occupant load
factors per IBC Table 1004.1.2 (i.e. Concentrated Assembly or Standing
Assembly) applied.
c.Bar/Rest Room (sic)/Hallway/Storage The indicated area appears to include spaces
not typically associated with Accessory Storage Areas per IBC Table 1004.1.2 and
also uses an incorrect occupant load factor. Any area to be used as a Bar (patrons
served/consuming drinks etc.) must have the appropriate occupant load factors per
IBC Table 1004.1.2 (i.e. Concentrated Assembly or Standing Assembly) applied.
Areas such as Restrooms and Hallways are excluded from Net Floor Area
occupant load factors such as those for the Dining area, but could be accounted for
as part of the Kitchen area.
3.Min. Plumbing Fixtures (Group A) Clarify the indicated ratio of the minimum required
plumbing fixtures. It does not appear to coincide with that indicated for A-2 occupancy
groups in IBC Table 2902.1.
4.Detail # 4 Reflected Ceiling Plan Lighting Calculation - Clarify the indicated number of
Wall Mount Lights to be installed. It does not appear to coincide with that represented on
the Reflected Ceiling Plan.
5.Detail # 5 Proposed New Door Schedule
a.Change the label to Proposed Floor Plan to reflect that represented in the detail.
b.Clarify the indicated number of 49 for the posting of the occupant load per IBC
1004.3. The posted number is to only include that determined using the occupant
load factor(s) for areas identified as Assembly occupancies.
c.Change the identified element from Exit Sign to Means of Egress Illumination to
reflect that indicated by the leader line.
d.Verify that the indicated swing of the egress door is per IBC 1008.1.2 after re-
calculating the tenant space occupant loads in response to plan review comments
#2a-2c above.
e.Verify that the indicated number of exits or exit access doorways is per IBC 1015
after re-calculating the tenant space occupant loads in response to plan review
comments #2a-2c above.
f.Clarify the indicated Existing Walls at the Host and Waiting areas. It does not
appear to correspond to that proposed in detail #2 Demo Plan.
g.Provide a reference as required to detail #8 Partition Wall with Seismic Bracing
(Perpen.) - for the required attachment at the top of walls that do not extend to and
are attached to the roof structure.
h.Clarify the indicated (Existing) type I hood Type I Hood 1. There does not
appear to be a record of an approved installation of a type I hood and the required
fire suppression system. It could be included with the separate permit required for
Type I Hood 2 see also review comment #7.
i.Provide a note on the plans regarding the required maintenance of the minimum 1-
hour fire-resistance rated occupancy separation walls per IBC 508.4 where
applicable.
6.Detail #6 Proposed New Door Schedule
a.Remarks - Change the applicable code version for each of the doors from ICC/ANSI
1117.1-2003 to ICC A117.1-2009 to reflect that currently adopted.
Page 2 of 3
b.Indicate on the plans the required accessible door hardware for each of the doors per
IBC 1008.1.9.1 and ICC A117.1-2009 section 404.2.6.
7.Detail #7 Kitchen Equioment (sic) Schedule The required number, locations, etc. of the
noted items (and of those not listed) are not part of this review and will be determined under
separate permits and reviews by the appropriate agencies.
Page 3 of 3