2016-0212 Affinity Dental TI - JPC Arch.pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: March 24, 2016 TO: JPC Architects christineb@jpcarchitects.com FROM: Chuck Miller, Plans Examiner RE: Plan Check: BLD2016-0212 nd Project Address: 123 2 Avenue S, Suite 110 Project: Affinity Dental TI Scope: Tenant improvement for dental office – B occupancy group – 22 occupants - II-B construction - NFPA-13 sprinkler system required– permits for mechanical, plumbing, are to be deferred submittals – required fire systems under separate permit disapproved Please be advised that the building plans for the above referenced project have been for the purposes of obtaining a building permit. During a review of the plans by the Building Division for compliance with the applicable building codes, it was found that the following . information, clarifications, or changes are neededReviews by other divisions, such as Planning, Engineering, or Fire, may result in additional comments that require attention beyond the scope of this letter. A complete review cannot be performed until the revised plans/documents, including a written response in itemized letter format indicating where the ‘clouded’ or otherwise highlighted changes can be found on the revised plans, have been submitted to a Permit Coordinator. nd Resubmittals must be made at the Development Services Department on the 2 Floor of City Hall. Permit Center hours are M, T, Th, & F from 8am-4:30pm and from 8:30am-12pm on Wednesdays. On sheet I-0.0 – Cover Sheet & Site Plan: 1.Drawing Index – Provide as part of a complete submittal sheet ‘I-9.5 – Firestopping Detail. It could not be found among the submitted construction documents. On sheet I-0.1 – General Notes & Symbols: 2.Door Notes a.Note #4 – Clarify the reference to IBC Table 715.3 for the required labeling of rated doors. Table 715.3 cannot be found in the 2012 IBC. b.Note #9 – Change the period during which egress doors are not to be secured from the egress side from ‘open to the general public’ to ‘occupied’ per IBC 1008.1.9.3. On sheet I-CS.1 – Exit Plan and Codes Summary: 3.Code Notes – Note #3 – Change the number of occupants from ‘23’ to ‘22’. 4.Exit Plan – Occupant Load - Change the number of occupants from ‘23’ to ‘22’. 5.Exit Plan Key Notes a.Change the note label from ‘Exit Plan’ to ‘Accessibility’ to reflect the applicable information provided. b.Note #1 – Change the code section from ‘804.4’ to ‘804.2 & 804.5.1’. Section ‘804.4’ regards sinks. c.Note #2 – Eliminate the provided incorrect information or change it to reflect that applicable to the element noted in space ‘118’ – Restroom - on the ‘Exit Plan’. Section ‘308’ regards reach range. On sheet I-2.1 – Dimension Plan: 6.Key Notes a.Note #3 – Provide on the plans the detail referenced regarding the clear framed glass relite at the entrance to space ‘116’ – Pan. b.Note #14 – Change on the plans the elevation reference for the partial-height partition from ‘16/I-8.1.1’ to ‘16/I-8.1’. On sheet I-3.1 – Floor Plan: 7.Floor Plan a.Clarify the maneuvering clearance on the ingress side of door ‘103’ to space ‘104’ – Checkout. It does not appear to comply with that required per ICC A117.1-2009 Table 404.2.3.2. b.Clarify the maneuvering clearance on the egress side of door ‘118’ to space ‘118’ – Restroom. It does not appear to comply with that required per ICC A117.1-2009 Table 404.2.3.2. 8.Key Notes – Note # 8 – Clarify the difference in the noted height above finished floor for the installation of the shelving bracket and of that indicated in the referenced detail – 1/I- 9.3.1 to guide proper installation – see also review note #24 below. On sheet I-4.1.2 – Reflected Ceiling Plan: 9.Key Notes – Note #2 – Indicate on the plans the proposed location(s) of the 1-hour-rated shaft enclosure(s) for the required supply and exhaust ventilation ducts from space ‘122’ – Medical Gas’ – to the exterior per IFC 5306.2.2. While the installation of the mechanical ventilation system components to provide the required minimum rate of 1 CFM per square foot of room may be permitted and performed under deferred or separate permit, the required shaft enclosure(s) must be represented on the plans to guide proper review, construction, and inspection. Page 2 of 4 On sheet I-8.1 – Interior Elevations: 10.Elevation 8 – Checkout 104 – North View – Verify on the plans that the final installation of the ‘Checkout’ counter meets the requirements of ICC A117.1-2009 section 904.3.1. Allowing for the vertical portion, from below the 42” high transaction surface to the top of the 30” portion below, to be open for a depth of at least 1 foot would appear to allow that portion to meet the requirement for use as an accessible service counter using a parallel approach at the end of the counter. 11.Elevation 9 – Checkout 104 – East View – See review comment #10 above. On sheet I-8.2 – Interior Elevations: 12.Elevation 4 – Cerec 126 – East View – Change on the plans the section reference for the casework from ‘16/I-9.3.3’ to ‘13/I-9.3.3’. 13.Elevation 7 – Operatory #4-134 – South View - Change on the plans the section reference for the casework with a sink from ‘11/I-9.3.2’ to ‘12/I-9.3.2’. 14.Elevation 13 – Lab 127 – South View - Change on the plans the section reference for the casework below the ‘vacuformer’ from ‘2/I-9.3.2’ to ‘3/I-9.3.2’. On sheet I-8.3 – Interior Elevations: 15.Elevation 2 a.Change on the plans the elevation label from ‘Operatory #2-132 – East View, Op #4- 134 Sim.’ to ‘Sterilization 120 – North View’. b.Change on the plans the section reference for the casework from ‘6/I-9.3.2’ to ‘2/I- 9.3.2’. On sheet I-9.1 – Construction Details: 16.Detail 4 – Full Ht. Partition a.Indicate on the plans the ‘measure’ (expressed in inches/fractions of an inch) of ‘designed deflection’ to allow for in the installation of the full height partitions to avoid moment reversal in the horizontal floor framing structural members and to guide proper review, construction and inspection. The information could not be found in the provided structural calculations. b.Indicate on the plans the required installation criteria of the top of full height walls at the deflection track. Most manufacturers require very specific installation to perform as intended to prevent moment reversal. 17.Detail 5 – Partial Ht. Partition – Change on the plans the detail reference for the steel stanchion used to support the partial height partition from ‘14/I-9.1’ to ‘10/I-9.1’. 18.Detail 6 – 1 Hr. Rated Full Ht. Partition a.See review note #16.a. above. b.See review note #16.b. above. c.Provide on the plans the required installation criteria of the materials noted in UL Design No. U419 (type of fasteners, fastener length, fastener spacing, type of gypsum wallboard) used to construct the 1-hour fire-resistance rated wall to guide proper construction and inspection. Page 3 of 4 d.Change on the plans as needed the installation criteria of the various materials represented to coincide with that required in UL Design No. 419. For example, there does not appear to be an allowance for the spacing of fasteners used to attach floor or ceiling runners at greater than 24” on-center. 19.Detail 9 – Med Gas Tank Storage Room – Change on the plans the required fire-resistance rating of the door(s) used to access the ‘med gas tank storage room’ from ’45-MIN’ to ‘1- HR’ per International Fire Code (IFC) 5306.2 – see also review note #26.b. below. 20.Detail 10 – Partial Ht. Partition Bracing – Provide on the plans a table, or indicate the ‘measure’ (expressed in inches/fractions of an inch), needed to determine the height of the vertical element of the bracing required for the partial height partition to be constructed. On sheet I-9.2 – Ceiling Details: 21.Detail 9 – Cantilevered GWB Soffit at Entry a.Clarify the noted allowable deflection measurement found in the information regarding the deflection track. The information could not be found in the provided structural calculations – see also review note # 16.a. above. b.See review note #16.b. above. 22.Detail 15 – Ceiling Mounted Equipment – Clarify the reference to detail ‘8/I-9.1’ for the required attachment to the structure above to support ceiling mounted equipment. The referenced detail does not appear to apply. Verify that any detail provided and referenced in response to this review comment accounts for the tension loads developed by the variety of equipment to be installed. 23.Detail 16 – Wood Veneer Bridge at Hallway a.Clarify the noted allowable deflection measurement found in the information regarding the deflection track. The information could not be found in the provided structural calculations – see also review note # 16.a. above. b.See review note #16.b. above. On sheet I-9.3.1 – Casework Details: 24.Detail 1 – Standards & Brackets - Clarify the difference in the noted height above finished floor for the installation of the shelving bracket and of that indicated on sheet ‘I-3.1’ – Floor Plan – Key Notes – Note #8 – see also review note #8 above. 25.Detail 3 – Lead Apron Hanger – Clarify the note for the installed height of the hanger to ‘REFER TO ELEVATION’. Elevation ‘5/I-8.3’ does not appear to specify the installation height. On sheet I-10.1 – Door Schedule, Elevations & Details: 26.Door Schedule a.Clarify on the plans the indicated fire-resistance rating of door ‘104’. It does not appear to meet the requirements for use as an interior exit stairway fire barrier opening protective per IBC Table 716.5. b.Clarify on the plans the indicated fire-resistance rating of door ‘122’. It does not appear to meet the requirements for an opening into a one-hour rated interior medical gas room per IFC 5306.2. The assembly is also required to provide smoke- and draft-control and be labeled per IBC 716.5.7.3 – see also review note #19 above. Page 4 of 4