20160405103449.pdfq�� S� T 4 RBBNE r T City of Edmonds Building Division Chuck Miller Re: Plan Check Comments: BLD2016-0212 Mr. Miller, March 30, 2016 Thank you for your comments on the above referenced project and taking the time to speak over the phone. Below are responses to comments related to the structural support of the metal framing. 16. A note regarding allowable deflection has been added to detail 4/1-9.1. 18. A note regarding the allowable deflection has been added to detail 6/I-9.1. We have been informed that the architect will add information regarding the screw specification as required per the UL rating. 21. Per our conversation, Stabbert Engineering LLC has reviewed the note on detail 9/I-9.2 and finds it acceptable. 22. Reference revised detail 22/1-9.2. 23. Per our conversation, Stabbert Engineering, LLC has reviewed the note on detail 9/I-9.2 and finds it acceptable. Sincerely, Stabbert Engineering, LLC Matthew Stabbert, PE, SE 227 BELLEVUE WAY NE #462 • BELLEVUE, WA 98004 - 425.968.5432 C ARCHITECTS Date: March 31, 2016 Project: Affinity Dental TI Project Address: 123 2"d Ave S Floor 1 /Suite 110 Edmonds, WA 98020 Permit #: BLD2016-0212 Scope: Tenant improvement for dental office — B occupancy group — 22 occupants - II -B construction - NFPA-13 sprinkler system required— permits for mechanical, plumbing, are to be deferred submittals — required fire systems under separate permit Reviewer: Chuck Miller (Building Division) Contact: Christine Benda (JPC Architects) Please see our responses in red below: On sheet 1-0.0 — Cover Sheet & Site Plan 1. Drawing Index —Provide as part of a complete submittal sheet 1-9.5 — Firestopping Detail. It could not be found among the submitted construction documents. Sheet 1-9.5 FirestoppingDetails have been added to the revised Ins . On sheet 1-0.1 — General Notes & Symbols: 2. Door Notes a. Note #4 — Clarify the reference to IBC Table 715.3 for the required labeling of rated doors. Table 715.3 cannot be found in the 2012 IBC. IBC reference has been revised o` 11 .' b. Note #9 — Change the period during which egress doors are not to be secured from the egress side from `open to the general public' to `occupied' per IBC 1008.1.9.3. Revised. On sheet I-CS.1 — Exit Plan and Codes Summary: 3. Code Notes —Note #3 —Change the number of occupants from `23' to `22'.. Revised. 4. Exit Plan — Occupant Load - Change the number of occupants from `23' to `22'. Revised. 5. Exit Plan Key Notes a. Change the note label from 'Exit Plan' to `Accessibility' to reflect the applicable information provided. Revised. 425 641 9200 1 909 112th Ave NE Suite 206 Bellevue, WA 98004 I www.jpcarchitects.com J P C ARCHITECTS b. Note #1 — Change the code section from '804.4' to '804.2 & 804.5.1'. Section '804.4' regards sinks. Revised. c. Note #2 — Eliminate the provided incorrect information or change it to reflect that applicable to the element noted in space '118'— Restroom - on the 'Exit Plan'. Section '308' regards reach range. Removed. On sheet 1-2.1 — Dimension Plan: 6. Key Notes a. Note #3 — Provide on the plans the detail referenced regarding the clear framed glass relite at the entrance to space '116'— Pan. Added new Construction Detail 4/1-9.1.2. b. Note #14 — Change on the plans the elevation reference for the partial - height partition from `16/1-8.1.1' to '16/1-8.1'. Revised. On sheet 1-3.1 — Floor Plan: 7. Floor Plan a. Clarify the maneuvering clearance on the ingress side of door '103' to space '104'— Checkout. It does not appear to comply with that required per ICC A117.1-2009 Table 404.2.3.2. Per the Dimensionl n Sheet 1-2.1, the front approach on the pull side of Door 103 is 18" Fin. Clear parallel to doorwayi requirements of referenced TabI is door is confirmed in compliance with referenced requirements. b. Clarify the maneuvering clearance on the egress side of door '118' to space "118'— Restroom. It does not appear to comply with that required per ICC A117.1-2009 Table 404.2.3.2. The size of the Restroomrevised r ss the 18" finished clear requirement r II latch/pull si of the door. 8. Key Notes — Note # 8 — Clarify the difference in the noted height above finished floor for the installation of the shelving bracket and of that indicated in the referenced detail — 1/19.3.1 to guide proper installation — see also review note #24 below. Installation of br i on Detail 1-9.3.1 has been revised . On sheet 1-4.1.2 — Reflected Ceiling Plan: 9. Key Notes — Note #2 — Indicate on the plans the proposed location(s) of the 1 - hour -rated shaft enclosure(s) for the required supply and exhaust ventilation ducts from space '122' — Medical Gas'— to the exterior per IFC 5306.2.2. While the installation of the mechanical ventilation system components to provide the required minimum rate of 1 CFM per square foot of room may be permitted and performed under deferred or separate permit, the required shaft enclosure(s) must be represented on the plans to guide proper review, construction, and 425 641 9200 1 909 112th Ave NE Suite 206 Bellevue, WA 98004 I www,jpcarchitects.com iRevised keynote #2 to include fire wrap specification and installation method, Added proposed location for rated shaft enclosure. nspection. On sheet 1-8.1 — Interior Elevations: 10. Elevation 8 — Checkout 104 — North View — Verify on the plans that the final installation of the 'Checkout' counter meets the requirements of ICC A117.1-2009 section 904.3.1. Allowing for the vertical portion, from below the 42" high transaction surface to the top of the 30" portion below, to be open for a depth of at least 1 foot would appear to allow that portion to meet the requirement for use as an accessible service counter using a parallel approach at the end of the counter. Transaction count r height has been revised to +36"AFF. 11. Elevation 9 — Checkout 104 — East View — See review comment #10 above. Transaction counter height has been revised o . On sheet 1-8.2 — Interior Elevations: 12. Elevation 4 — Cerec 126 — East View — Change on the plans the section reference for the casework from '16/1-9.3.3' to '13/1-9.3.3'. Revised. 13. Elevation 7 — Operatory #4-134 — South View - Change on the plans the section reference for the casework with a sink from '11/1-9.3.2' to '12/1-9.3.2'. Revised. 14. Elevation 13 — Lab 127 — South View - Change on the plans the section reference for the casework below the 'vacuformer' from '2/1-9.3.2' to '3/1-9.3.2'. On sheet 1-8.3 — Interior Elevations: 15. Elevation 2 a. Change on the plans the elevation label from 'Operatory #2-132 — East View, Op #4134 Sim.' to 'Sterilization 120 —North View'. Revised. b. Change on the plans the section reference for the casework from '6/1- 9.3.2' to '2/19.3.2'. Revised. On sheet 1-9.1 — Construction Details: 16. Detail 4 — Full Ht. Partition a. Indicate on the plans the 'measure' (expressed in inches/fractions of an inch) of 'designed deflection' to allow for in the installation of the full height partitions to avoid moment reversal in the horizontal floor framing structural members and to guide proper review, construction and inspection. The information could not be found in the provided structural calculations. Detail has been revised — refer to Structural Engineer response attached. 425 641 9200 1 909 112th Ave NE Suite 206 Bellevue, WA 98004 I www.jpcarchitects..com PC ARCHITECTS b. Indicate on the plans the required installation criteria of the top of full height walls at the deflection track. Most manufacturers require very specific installation to perform as intended to prevent moment reversal. Detail has been revised — refer to Structural Engineerrs ons c . 17. Detail 5 — Partial Ht. Partition — Change on the plans the detail reference for the steel stanchion used to support the partial height partition from `14/1-9.1' to '10/1- 9.11 . Revised. 18. Detail 6 — 1 Hr. Rated Full Ht. Partition a. See review note #16.a. above. Detail has beenris —rro Structural Engineerrs s . b. See review note #16.b. above. Detail has been revised — refer to Structural Engineerrs ons c . c. Provide on the plans the required installation criteria of the materials noted in UL Design No. U419 (type of fasteners, fastener length, fastener spacing, type of gypsum wallboard) used to construct the 1 -hour fire - resistance rated wall to guide proper construction and inspection. Revised til 6 and added UL Design UL263/U419 on Sheets 1-11.1 & I- 11.2. d. Change on the plans as needed the installation criteria of the various materials represented to coincide with that required in UL Design No. 419. For example, there does not appear to be an allowance for the spacing of fasteners used to attach floor or ceiling runners at greater than 24" on - center. Revised til 6 andsin UL263/U41 9 on Sheets 1-11.1 & I- 11.2. 19. Detail 9 — Med Gas Tank Storage Room — Change on the plans the required fire -resistance rating of the door(s) used to access the 'med gas tank storage room' from '45 -MIN' to `1 HR' per International Fire Code (IFC) 5306.2 — see also review note #26.b. below. Revised. 20. Detail 10 — Partial Ht. Partition Bracing — Provide on the plans a table, or indicate the 'measure' (expressed in inches/fractions of an inch), needed to determine the height of the vertical element of the bracing required for the partial height partition to be constructed. Added ll Type El and E2 to confirm finished wall height requirements. it 10/1-9.1 confirms structural stanchion i is to match the height partition. On sheet 1-9.2 — Ceiling Details: 21. Detail 9 — Cantilevered GWB Soffit at Entry a. Clarify the noted allowable deflection measurement found in the information regarding the deflection track. The information could not be found in the provided structural calculations — see also review note # 16.a. 425 641 9200 1 909 112th Ave NE Suite 206 Bellevue, WA 98004 i www,jpcarchitects.com J C ARCHITECTS above. Detail has been revised —rfr to Structural Engineerrs ons c . b. See review note #16.b. above. Detail has been revised —rfr to Structural Engineerrs ons . 22. Detail 15 — Ceiling Mounted Equipment — Clarify the reference to detail '8/1-9.1' for the required attachment to the structure above to support ceiling mounted equipment. The referenced detail does not appear to apply. Verify that any detail provided and referenced in response to this review comment accounts for the tension loads developed by the variety of equipment to be installed. Detail has been revised —rro Structural Engineerrsos til attached. 23. Detail 16 — Wood Veneer Bridge at Hallway a. Clarify the noted allowable deflection measurement found in the information regarding the deflection track. The information could not be found in the provided structural calculations — see also review note # 16.a. above. Detail has been revised —rfr to Structural Engineerrs ons c. b. See review note #16.b. above. Detail has been revised —rfr to Structural Engineerrs ons c . On sheet 1-9.3.1 — Casework Details: 24. Detail 1 — Standards & Brackets - Clarify the difference in the noted height above finished floor for the installation of the shelving bracket and of that indicated on sheet 'I-3.1' — Floor Plan — Key Notes — Note #8 — see also review note #8 above. Installation of rcket height on Detail -.1 has beenris . 25. Detail 3 — Lead Apron Hanger — Clarify the note for the installed height of the hanger to 'REFER TO ELEVATION'. Elevation '5/1-8.3' does not appear to specify the installation height. Installation i s been added to Detail 3/1-9.3. On sheet 1-10.1 — Door Schedule, Elevations & Details: 26. Door Schedule a. Clarify on the plans the indicated fire -resistance rating of door' 104'. It does not appear to meet the requirements for use as an interior exit stairway fire barrier opening protective per IBC Table 716.5. Revised 1 -Hr Rating. b. Clarify on the plans the indicated fire -resistance rating of door '122'. It does not appear to meet the requirements for an opening into a one-hour rated interior medical gas room per IFC 5306.2. The assembly is also required to provide smoke- and draft -control and be labeled per IBC 716.5.7.3 -see also review note #19 above. Revised 1- r Rating withregarding smoke & dr r I. Also revised til 9/1-9.1. 425 641 9200 1 909 112th Ave NE Suite 206 Bellevue, WA 98004 I www.jpcarchitects.com