20160427164151.pdfChandler Stever, Architect
1715 223rd Place NE
Sammamish, WA 98074
425-985-2176
Date 4-20-16
City of Edmonds building Division
Attn: Kevin Zweber, Fire Marshal
Attn: Chuck Miller, Plans Examiner
1215 th Ave N.
Edmonds, WA 98020
RE, Plan review correction response, permit # BLD2016-0222
for the 190 Sunset Restaurant T.I. located at Salish Crossing
Center, 190 Sunset Ave S.
We have addressed and revised Permit plans according to the plan review
comments received from Fire on 3-17-16 and following, Building Division
on 4-15-16, each department comments are addressed per your numbering
and are on sheets as follows; all revisions have been clouded.
Kevin Zweber, Fire comments;
1) See Sheet TS1.01 for added deferred submittal for Fire Suppression for
type 1 hood.
2) See A2.02 ceiling exit light plan for added illuminated exit sign with
arrow.
3) See attached Cut sheet for UL listed gas fire pit for outdoor patio.
4) See A2.00a for clearly shown exit path at outdoor dining patio.
5) See A2.01 for added note, "Fire extinguishers appropriately spaced
through suite, located per fire Marshal walk through.
Chuck Miller, Building Division;
1) See A2.02 lighting plan for added notes, occupancy sensors, offices and
restrooms and day light controls at exterior glazed areas per WSEC C405.13
and C405.2
2) See TSl.Oland A2.01 for updated occupancy per comments.
3) See revised kitchen employee restroom with access revised from kitchen
to access through office as discussed.
4) a) See TS1.01 and A2.01 with updated occupancy, with clarification note
on A2.01 seat count list indicating this seat calculation is intended for
Grease Interceptor sizing, not occupancy.
b) See A2.01 for added note, 5% accessible seating, and proposed locations
shown.
c) See A2.01 for added locations for posted Occupant load sign for each
dining area (East, South and Outdoor dining areas).
d) See A2.01 for added note for posted signs at grids C / 3.35 at door to east
space, "Not an Exit, posted on both sides of door.
5) See A3.02 with revised type 1 hood duct requirement 40" above roof.
Please let me know if you have any additional question or clarifications.
Sincerely
Chandler Stever Architect
425-985-2176