2016-0466 North Sound Church remodel-TI - TGBA.pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: June 23, 2016 TO: Jessica Hardin/Steve Butterfield jhardin@tgbarchitects.com FROM: Chuck Miller, Plans Examiner RE: Plan Check: BLD2016-0466 th Project Address: 201 4 Avenue N Project: North Sound Church remodel-TI Scope: – A-3/B occupancy group – XX occupants – V-A construction – existing building is not sprinkled disapproved Please be advised that the building plans for the above referenced project have been for the purposes of obtaining a building permit. During a review of the plans by the Building Division for compliance with the applicable building codes, it was found that the following . information, clarifications, or changes are neededReviews by other divisions, such as Planning, Engineering, or Fire, may result in additional comments that require attention beyond the scope of this letter. A complete review cannot be performed until the revised plans/documents, including a written response in itemized letter format indicating where the ‘clouded’ or otherwise highlighted changes can be found on the revised plans, have been submitted to a Permit Coordinator. nd Resubmittals must be made at the Development Services Department on the 2 Floor of City Hall. Permit Center hours are M, T, Th, & F from 8am-4:30pm and from 8:30am-12pm on Wednesdays. On sheet A0.21 – Site & Code Plans & Code Analysis: 1.Detail 1 – Life Safety / Site Plan – Level 1 and Detail 2 – Life Safety – Level 2 a.Clarify the difference in the indicated areas and occupant loads and of those determined using International Building Code (IBC) section 1004/Table 1004.1.2. IBC sections 1014.1.2 and Table 1004.1.2 have specific dimensional and ‘function of area’ criteria that determine the occupant load factor to be applied when calculating occupant loads. The areas identified in the ‘function of space’ column of IBC Table 1004.1.2 are intended to be applied to the general use of the space as a whole when the ‘occupant load factor’ is based on gross floor area, and all areas of the building capable of being occupied are to be accounted for. The presence of restrooms, small mechanical and storage areas, etc., are accounted for in the assigned occupant load factors for the various functions of space. b.Indicate on the plans the requirement that the doors between the ‘Worship Center’ and the ‘Foyer’ must not have a latch or lock unless provided with panic hardware per International Building Code (IBC) 1008.1.10. c.Indicate on the plans the required posting of the occupant load of 485 occupants for the ‘Worship Center’ per IBC 1004.3. d.Indicate on the plans the required posting of the occupant load of 186 occupants for the ‘Foyer’ per IBC 1004.3. On sheet A2.11 – Floor Plan: 2.Detail 1 – Floor Plan – Level 1 – New or Detail 2 – Floor Plan – Level 2 – New – Indicate on the plans the required family or assisted-use toilet room installation per IBC 3411.7/1109.2.1. 3.Detail 1 – Floor Plan – Level 1 – New and Detail 2 – Floor Plan – Level 2 – New – Indicate on the plans the required corridor walls of not less than one-hour fire-resistive construction for the following locations to maintain that required at the time of original construction under the ’94 Uniform Building Code (UBC) 1005.8.1 and to remain per IBC 3401.2: Adjacent door ‘109’ – Enlarged Warming Kitchen · Adjacent door ‘208’ - Men · 4.Detail 1 – Floor Plan – Level 1 – New – Indicate on the plans the required minimum ventilation rate for space ‘111’ – Worship Center – per International Mechanical Code (IMC) Table 403.3. Verification of the existing mechanical system to provide the minimum rate will be required, or an alteration can be done under this permit or a separate permit. 5.Detail 2 – Floor Plan – Level 2 – New a.Clarify the representation of what appears to be a ‘dead-end’ in space ‘200’ – Corridor – with a length beyond that permitted per IBC 1018.4. b.Indicate on the plans the required accessible water closet in the following locations per IBC 3411.7/1109.2: Space 208 – Men · Space 209 – Women · The required family or assisted-use toilet room installation noted in plan review comment #2 will meet both of the requirements noted above if placed on Level 2. 6.Door Schedule – Indicate on the plans the required tight-fitting smoke- and draft-control doors having a fire-protection rating of not less than 20 minutes for the following locations to maintain that required at the time of original construction under the ’94 UBC 1005.8.1 and to remain per IBC 3401.2: Door 109 – Enlarged Warming Kitchen · Door 208 – Men (verify rating of the existing door if to be re-used) · On sheet S1.1 – Structural Notes and Schedules: 7.Holdown Schedule a.Provide on the plans the information for ‘Note 4’ referenced in the ‘Anchor Bolt’ column to guide proper review, construction, and inspection. b.Note 2 – Clarify the reference to detail ‘4/S3.1’ for the installation of the ‘HD’ holdowns. The detail does not appear to apply. Page 2 of 2