PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
DATE: July 26, 2016
TO: Pride Ventures, LLC
Jake Lyon
jake@prideventuresllc.com
FROM: Andrew Gahan, Plans Examiner
th
RE: Permit Numbers: BLD2016-0600 Building 2 (21294 80 Avenue W.)
th
BLD2016-0602 Building 4 (21298 80 Avenue W.)
th
BLD2016-0611 Building 11 (21230 80 Avenue W.)
th
BLD2016-0613 Building 13 (21236 80 Avenue W.)
Project: Bracketts Corner Detached Condominiums
During a review of the plans by the Building Division for the above noted project, it was found that
the following information, clarifications, or changes are needed. A complete review cannot be
performed until the revised plans/documents, including a written response indicating where the
clouded or otherwise highlighted changes can be found on the revised plans, have been submitted
to a Permit Coordinator. Reviews by other divisions, such as Planning, Engineering, or Fire, may
result in additional comments.
Sheet A2.0
1.The note sheet references the Seattle Building Code. Please update this sheet with the
appropriate Code references.
Sheet A2.1
2.See item 1 above.
Sheet A3.0
3.It appears that the roof plan does not match the elevation on Sheet A3.1:
a.The elevations show that the overframing at the north half of the structure meets at
the top of the ridge. The roof plan shows the overframing stopping short of the
ridge. Please coordinate the drawings.
b.The south elevation shows that there is a gable all the way across, and a smaller
gable in front of that. The roof plan only shows the small gable. Please coordinate
the drawings.
4.Relocate the smoke detector to be within the southeast bedroom.
Sheet S2
5.Detail GPA shows that the lag bolts are to be concealed under the post (2 edge distance at
each side), but the calculations provided show the bolts configured with ½ edge distance.
Please revise the detail or revise the calculations to match.
Sheet S3
6.It appears that the structural drafting is reversed relative to the floor plans in the
architectural set. The City of Edmonds does not accept flipped plans. Structural plans
matching the architectural plans are required.
Sheet S4
7.See comment 6 above.
8.It appears that a window is missing by the bonus room upstairs as shown on the architectural
sheets. Please coordinate the drawings.