2016-0661 Fashion Dim Sum TI - 3-D Design.pdf
City of Edmonds
PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
DATE: July 8, 2016
TO: Wenke Yang
wenkeyang312@yahoo.com
FROM: Chuck Miller, Plans Examiner
RE: Plan Check: BLD2016-0661
Project Address: 22923 Highway 99, Suite J
Project: Fashion Dim Sum TI
Scope: Add non-bearing interior walls, two restrooms, type I hood B occupancy
group 32 occupants III-B construction no NFPA-13 sprinkler system
mechanical and plumbing included
disapproved
Please be advised that the building plans for the above referenced project have been
for the purposes of obtaining a building permit. During a review of the plans by the Building
Division for compliance with the applicable building codes, it was found that the following
.
information, clarifications, or changes are neededReviews by other divisions, such as Planning,
Engineering, or Fire, may result in additional comments that require attention beyond the scope of
this letter.
A complete review cannot be performed until the revised plans/documents, including a
written response in itemized letter format indicating where the clouded or otherwise
highlighted changes can be found on the revised plans, have been submitted to a Permit
Coordinator.
nd
Resubmittals must be made at the Development Services Department on the 2 Floor of City Hall.
Permit Center hours are M, T, Th, & F from 8am-4:30pm and from 8:30am-12pm on Wednesdays.
On sheet FS-0.1 Cover Page:
1.General Notes Note #3 Clarify the note All rough-ins are subject to change and
verification pending the final selection and location of all equipment. regarding the
plumbing, electrical, and refrigeration systems installations. Typically, the plans reflect the
well-determined locations and configurations specific to the needs of the project and do not
change significantly once the review has been completed and a permit for the work has been
issued. Allowances are made for unforeseeable circumstances and these are often resolved
on the project site during the inspection process. Significant changes, especially to the
plumbing system, may require additional review to determine the allowances and
requirements of the applicable codes to the work different than that represented on the
originally submitted construction documents. Such changes must be submitted to the permit
center as a revision and be reviewed at additional cost.
2.Code Requirements Building Construction Type Change on the plans the following
information to reflect that originally constructed as approved under permit BLD1985-0301:
Building Is: Change from Type-II-B to Type III-B.
·
Exterior wall construction: Change from Steel Roof Deck, Steel Trusses, CMU
·
Construct <20 (existing) to Wood Roof Trusses, Pre-cast Span-Deck floor
system, Pre-cast/Tilt-up Wall construction.
If the existing construction does not reflect that originally permitted, contact the City of
Edmonds Building Division (425-771-0220).
3.Index Add sheet A-2 Floor Plan, Elev. and RCP and sheet A-3 Bracing Detail &
ADA Restrooms to reflect that submitted at the time of application.
On sheet FS-1 Equipment Plan:
4.Detail 1 Equipment
a.Provide on the plans a mark for the following items listed in the Equipment
Schedule 1:
Mark 22 Hand Sink w/Fct. in the Womens Lav. It appears to be behind
·
mark 27.
Mark 24 Floor Sink in the Scullery below the Dish Machine.
·
Mark FP Fire Alarm Pull Station in the Kitchen along the wall adjacent
·
the Cabinet Heater/Proofer.
b.Clarify on the plans the representation of the lavatory in the Mens Lav. It does not
appear to allow for the required clearance width around the water closet per ICC
A117.1-2009 section 604.3.3.
c.Clarify on the plans the placement of the fixtures and equipment in the Service
area. It does not appear to allow for the required accessible route to the work area
space between the Cabinet Heater/Proofer and the Deli Refrigerator per
International Building Code (IBC) 1103.2.3.
d.Provide as part of a complete submittal manufacturer information for the following
appliances:
Mark 10 Cabinet Heater/Proofer.
·
Mark 14 Electric 3 Pan Steam Table.
·
Mark 19 Dish Machine.
·
Of particular concern is the required installation of Type II hoods above dishwashers
and appliances that produce heat or moisture per International Mechanical Code
(IMC) 507.2.2. An HVAC system design that incorporates the heat and moisture
loads from the appliances or a separate removal system are acceptable alternatives
that must be noted on the plans.
e.Note on the plans that the installation of a beverage dispenser utilizing a carbonator
is not proposed as part of this project.
5.Detail 2 Floor Plan Identify on the plans the space/use of the space in the plan
northwest corner adjacent the Scullery to guide proper review.
Page 2 of 4
On sheet FS-2 Plumbing:
6.Detail 1 - Plumbing
a.Provide on the plans a mark for the following items listed (see also plan review
comment 6.b. below) in the Plumbing schedule:
Mark 16 2 Comp Sink in the Scullery.
·
Mark 16.1 Wall Mt Faucet for the second sink in the Scullery.
·
Mark 16.1 Wall Mt Faucet for the sink in the Service area.
·
Mark 24 Floor Sink for the floor sink in the Scullery.
·
Mark 26 Low Profile Grease Trap below the 3 Comp Dirty Dish Table in
·
the Scullery.
b.Note on the plans that the installation of backflow prevention device to protect the
potable water supply to a carbonator is not proposed as part of this project.
c.Provide as part of a complete submittal line drawings or a similar representation of
the proposed drain, waste, and venting (DWV) system serving the proposed
plumbing fixtures to guide proper review, construction, and inspection.
7.Plumbing
a.Add to the schedule the following fixtures marked on Detail 1 - Plumbing:
Mark 16 2 Comp Sink in the Scullery.
·
Mark 18 3 Comp Dirty Dish Table in the Scullery.
·
Mark 19 Dish Machine in the Scullery.
·
Mark WC1 Water Closet in each of the restrooms.
·
b.Provide on the schedule the noted information for the following fixtures:
Mark 11 Icemaker & Bin the minimum cold water supply size.
·
Mark 12 Work Table (sink) the minimum trap arm size.
·
Mark 16 2 Comp Sink the minimum trap arm size.
·
Mark 16.1 Wall Mt Faucet the minimum cold and hot water supply size.
·
Mark 18 3 Comp Dirty Dish Table the minimum trap arm size.
·
Mark 19 Dish Machine the minimum cold or hot water supply size.
·
Mark WC1 Water Closet the minimum cold water supply size.
·
On sheet FS-3 Electric:
8.Detail 1 Electric Plan - Provide on the plans a mark for the Reach-in Refrigerator listed
in the Electrical new format schedule.
On sheet FS-4 Elevations:
9.Detail 3 Womens Lav Provide on the plans a mark for the Hand Sink w/Fct..
On sheet M-1 Hood Plan:
10.(Cooking) Equipment schedule Clarify the difference in the specification of the following
cooking appliances and of that described on sheet FS-1 Equipment Schedule 1:
Item 2 Six Burner Range
·
Item 3 5 Hole Wok Range
·
Page 3 of 4
On sheet A-2 Floor Plan, Elev. And RCP:
11.Detail A Floor Plan
a.Indicate on the plans the required installation of non-combustible wall framing for
the placement of the Type I hood per Section Elevation View on sheet M-1 along
the plan east wall of the Kitchen.
b.Indicate on the plans the means to be used to support the top of the half wall to
resist lateral forces. Typically, stanchions or other rigid vertical elements are
attached to the floor to minimize movement at the top of walls that are not full-height
and lack bracing at the top.
12.Detail C RCP
a.Indicate on the plans the required minimum mechanical outdoor air ventilation rate
per IMC Table 403.3 for the Dining area see also plan review note 4.d.
b.Indicate on the plans the locations of the required lighting controls per Washington
State Energy Code (WSEC) C405.2.
On the provided Washington State Energy Code (WSEC) Compliance Forms for Commercial
Buildings:
13.Provide as part of a complete submittal a completed checklist LTG-CHK. The applicable
required information noted on the completed checklist must be indicated on the plans as
specified see also plan review comment 12.b. above.
14.LTG-INT-SPACE checklist Clarify the indicated watts/fixture for the proposed Track
Light in the Service area. It does not appear to comply with that specified in WSEC
C405.5.1.4. Resubmit checklist LTG-INT-SPACE as required to verify compliance of the
proposed Interior Lighting Power Allowance in the response to the plan review comment.
General Note:
15.Provide as part of a complete permit application submittal a copy of the Snohomish County
Health District review/approval letter per the City of Edmonds Tenant Improvement Permit
Submittal Requirements.
Page 4 of 4