2016-0669 Swedish Radia Imaging TI - AWerks.pdf
City of Edmonds
PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
DATE: June 30, 2016
TO: Radia Medical Imaging
Stephanie Aplin
saplin@radiax.com
FROM: Chuck Miller, Plans Examiner
RE: Plan Check: BLD2016-0669
Project Address: 21700 Highway 99
Project: Radia Medical Imaging TI
Scope: Remove overhead door/add infill wall & windows, remove/add interior non-
bearing walls, new suspended ceiling/lighting/controls B occupancy group 58
occupants V-B construction no NFPA-13 sprinkler system installed
mechanical, plumbing, and fire system alteration/addition under separate permits
disapproved
Please be advised that the building plans for the above referenced project have been
for the purposes of obtaining a building permit. During a review of the plans by the Building
Division for compliance with the applicable building codes, it was found that the following
.
information, clarifications, or changes are neededReviews by other divisions, such as Planning,
Engineering, or Fire, may result in additional comments that require attention beyond the scope of
this letter.
A complete review cannot be performed until the revised plans/documents, including a
written response in itemized letter format indicating where the clouded or otherwise
highlighted changes can be found on the revised plans, have been submitted to a Permit
Coordinator.
nd
Resubmittals must be made at the Development Services Department on the 2 Floor of City Hall.
Permit Center hours are M, T, Th, & F from 8am-4:30pm and from 8:30am-12pm on Wednesdays.
On sheet A2.1 Floor Plan:
1.Floor Plan
a.Indicate on the plans the required drinking fountain(s) installation to meet both the
accessible and standing spout outlet height requirements of International Building
Code (IBC) 3411.7/2902.5.1/1109.5.1 and ICC A117.1-2009 section 602.4.
b.Clarify the elevation bubbles as follows:
1/A7.1 in space 118 Ultrasound Techs
·
2/A7.1 in space 119 Scheduling
·
3/A7.1 in space 124 Ultrasound
·
Sheet A7.1 does not appear on the Sheet Index on sheet A0.1 and could not be
found among the submitted construction documents.
c.Identify on the plans the proposed elements to be placed along the north interior wall
of space 119 Scheduling to guide proper review, construction, and inspection.
On the provided Washington State Energy Code (WSEC) Compliance Forms for Commercial
Buildings checklist LTG-CHK:
2.Lighting Controls Clarify the stated indication of identified locations for the installation of
the following:
a.Light reduction controls per WSEC C405.2.1.2
b.Occupancy sensors per WSEC C405.2.2.2
c.Means of egress lighting per WSEC C405.2.3 item 7
d.Exit signs per WSEC C405.4
The controls and type of fixtures required by WSEC do not appear to be indicated on the
plans or in the Light Fixture Schedule on sheet A3.1.