Loading...
20160713141637.pdfCITY OF EDMONDS CORRECTION NOTICE #2 RESPONSE TEN GUN OFFICE T.I., PROJECT #BLD20160329 OVERVIEW ENGINEERING REVIEW FIRE REVIEW PLANNING REVIEW DST TRACKI NG BUILDING REVIEW BUILDING REVIEW APPROVED APPROVED APPROVED CORRECTIONS REQUIRED CORRECTIONS REQUIRED On sheets A1.0, A1.3, and A1.4 — Proposed Floor Plan: Chuck Miller Chuck Miller Floor Plan — Clarify the indicated height of seating/surfaces in space "123" — Coffee Bar. They do not appear to meet the requirements of IBC 1108.2.9.1/1109.11 and ICC A117.1 2009 sections 902 and 903. The response to the plane review comments states: "Not a primary function not required to be ADA accessible per IBC 1109." The scoping requirements of IBC 1103.1 require that facilities, elements, and spaces shall be accessible, with exemptions as allowed per IBC 1104 through 1110. There does not appear to be any qualifying language regarding the 'primary function' of the facility, element, or space in those sections. IBC 3411.7 requires that certain facilities serving an area of 'primary function', such as toilets, drinking fountains, and telephones, be included in the scope of work, even if outside of where the alterations affecting the area of primary function are to be completed. IBC 3411.6 requires that a facility that is altered comply with the applicable provisions of IBC Chapter 11. agreedRESPONSE: Per the July 1", 2016 phone conversation with Chuck Miller and David Squires, both parties single (1) ADA height seat at the Coffee Bar amenity for equal access. See revised Coffee Bar seating on A1.0, A1.4 and 2. Floor Plan (A1.0, A1.3, and A1.4 — Proposed Floor Plan) Clarify the added note —'NEW 1.5HR — Door' — and the wall construction callout — P3 — near space '108' — Exit. Those elements appeared to be represented as existing in the earlier submittal, although different than shown on the plans for the original construction under permit BLD1993-0593. If new construction is to be performed in this area, accommodations to meet the accessible route requirements per IBC 1103.2.3 and ICC A117.1-2009 section 404.2.3.2/Table 404.2.3.2 for door'R01' at the north end of space '109' — Hall A — should be made unless technically infeasible. RESPONSE: Mallet has clarified the confusion in this area. The only new construction is the new rated door and rated wall that propose to shorten the existing permitted (BLD1993-0593) hall to no lonN.er include the restroom areas. qf A 1W xr*-�2 11W-Az1rom- i M length with a new door and wall. Any doors and walls that were existing in that hallway (including those connecting the hall to 107 Mechanical Room A and the existing stair to the 2 Id 1floor) will remain as existing. An added note stating "Existing rated door, door hardware, and walls to remain, contractor to veriLbrA" has been added to these areas on all fieridumWiT13- W--m- sheetsand 3. On sheet A1.6 —Egress Plan: Informational Only— No response required.