20160822114859.pdfCity of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: July 14, 2016 TO: Nash Alibhai fdnash @icloud.corn FROM: Chuck Miller, Plans Examiner RE: Plan Check: BLD2015-1454 Project Address: 22617 76" Avenue W Project: Factory Direct Tire storage structure August 10/2016 y ��ik ��^� ���i 2016 i��„ elm: t G p0.' � 16 LRXM(! 0EPAFt r 11-t'1"m. C dl"Y OF t"DMOND5 Scope: Construct a metal framed structure for unspecified storage — undetermined occupancy group - 3 occupants — unspecified construction type - NFPA-13 sprinkler system not required— mechanical not included Please be advised that the building plans for the above referenced project have been disapproved for the purposes of obtaining a building permit. During a review of the plans by the Building Division for compliance with the applicable building codes, it was found that the following information, clarifications, or changes are needed. Reviews by other divisions, such as Planning, Engineering, or Fire, may result in additional comments that require attention beyond the scope of this letter. A complete review cannot be performed until the revised plans/documents, including a written response in itemized letter format indicating where the 'clouded' or otherwise highlighted changes can be found on the revised plans, have been submitted to a Permit Coordinator. Resubmittals must be made at the Development Services Department on the 2"d Floor of City Hall. Permit Center hours are M, T, Th, & F from 8am-4:30pm and from 8:30am-12pm on Wednesdays. On sheet A-0 — Site Plan — Site Information - General Notes: I. Site Plan a. Clarify the proposal to install gravity openings to provide ventilation for the proposed storage structure. It does not appear to meet the mechanical exhaust ventilation requirements per International Mechanical Code (IMC) 401 .2/T able 403.3. ai, l..he liprrrtx;rrred ven iik3tucn has been rir;.letrw.d as ir°u(:)te on ttie Slte lDM an Sheet -0 Rt ."t"tuamFn sI arro shalll be use a St:cairartrr r:rnli7. b. Provide on the plans a detail, and a reference to it, for the construction of the required one -hour fire -resistance rated exterior wall construction of the north wall of the proposed storage structure per [BC Table 602. b. i)rrr fide 1 lhr, t'trrted extrrr6or wail / 1 ttsr. I lt:ll. s4ru.uds ( 16" r .c, W/ bot:toim & top rn l tracks. IF'1ace sN:u t bE t (:,Iein shtjctur,4I 5/8" type n"x" gwb, both rriides, Advance Remodeling Solutions U,,, ,, 1802 NW 201ST SHORELINE, WA 98177 (206) 427-3525 apdi92@outlook.com 2. Code Analysis - Indicate on the plans the construction classification of the proposed storage structure per [BC 602. . t onstnict on clasui icahou°u 1tuu,. the stoic, rqc utiu°ur:Aturie is ii B as noted on fl'm revised Shieei[ _0 II 4. Detail #5 — Footing Detail 3A (36) — Clarify the identified footings for each of the specified footing lengths. The upper dimension appears to correspond to that anticipated at location '3A'. The lower dimension appears to correspond to that anticipated at location '313'. Page 2 of 2 See Stiructurar IEiuwgkieeru att:ar:at eci rostrrrrruo. If you have any questions regarding this letter, please contact our office Regards Michael Valiente Project Manager. Advance Remodeling Solutions U11,,, , 1802 NW 201ST SHORELINE, WA 98177 (206) 427-3525 apdi92@outlook.com