20160923100944.pdfw, a'r Ji FIKE ., DI "I'.�' CITY OF EDMONDS DEPARTMENT OF FIRE PREVENTION 9/22/16 DRC REVIEW NOTES FOR 21300 Hwy 99, DRC20160031 This review is conducted in accordance with 2015 International Fire Code and Edmonds Community Development Code. Provide under deferred submittal: 1. Fire connection permit. 2. Automatic fire sprinkler permit. 3. Automatic fire alarm permit. 4. Emergency radio system/Distributed antenna system (DAS) if required. 5. Spray booth fire suppression system. Provide upon occupancy: 1. Fire Operational Permit (IFC 105.6) The following requirements may apply: 1. Fire access roads, including fire lane marking — IFC 503.2 and 503.3 and COE/FD1 Standard. 2. Premise identification — IFC 505.1 + COE/FD1 Standard. 3. Fire department key box and gate controls — IFC 506 and COE/FD1 Knox Box Standard. 4. Fire protection water supplies/fire flow requirements — IFC 507 and Appendix B. 5. Fire hydrant locations — IFC Appendix C and ECDC standard. 6. Emergency Responder Radio System (if required) — IFC 510. 7. Fuel fire appliances — IFC 603.1 8. Emergency and Standby Power System — IFC 604. 9. Emergency elevator operation, maintenance and fire service keys — IFC 607. 10. Automatic Sprinkler System — IFC 903.2.8, 903.2.1.6 (WA), 903.3.1.2, 903.1.2.1, and individual floor control valves and attic protection. 11. Fire riser room — provide exterior access to co -located fire riser and fire alarm control panel room. 12. Fire standpipe system — IFC 905 13. Portable fire extinguishers — IFC 906. 14. Fire alarm system — IFC 907.2. 12425 Meridian Avenue S / Everett WA 98208 / 425-551-1200 www.firedistrictl.org 5� 12"IRE III��..,.`4 R " „o 15. Fire department connection — IFC 912.2 and COE/FD1 Standard (FH within 50' of FDC). 16. Fire pumps — IFC 913. 17. Motor fuel -dispensing facilities and repair garages IFC Chapter 23. 18. Flammable Finishes — IFC Chapter 24. 19. Fire Safety during construction and demolition — IFC Chapter 33. 20. Welding and other hot work — IFC Chapter 35 21. Flammable and combustible liquids, IFC Chapter 57. 22. Fire protection footprint — required for development of pre -incident planning. Project Contact: Kevin Zweber Fire Marshal 425-771-0213 12425 Meridian Avenue S / Everett WA 98208 / 425-551-1200 www.firedistrictl.org