20161202112953.pdfTo Mr. Chuck Miller
Plan Review Examiner
Building Division
City of Edmonds
November 28, 2016
Dear Mr. Miller,
OF", 0 A I!()I�"
Thanks for the review comments dated October 12 for Chinese Grace Evangelical Free Church
proposal. In the following I have prepared some clarification to your review notes number 3, 4,
12, 15, 21 and 22.
Review note 3 — We shall use slotted roof truss clips to allow for the deflection of the floor or
roof trusses above.
Review note 4 — We have resubmitted Washington State Energy Code (WSEC) Compliance
Forms. The attachment includes the followings:
Lighting Summary, Interior Lighting — Space -By -Space Method, and Lighting, Motor,
and Electrical Permit Checklist.
Lighting Plan (Page 7, 8 & 9)
Lighting Fixture Schedule (Page 6).
Review note 12 — We have added Page 4 to show the construction and electrical wiring of the 7
feet high architectural feature wall along the north wall of Room 109.
Review note 15 - We have Indicated that Range and Type II hood will be installed in Room 110
for the purpose of boiling, steaming, and warming precooked food, which shown in Page 2 & 5.
Review note 21—The occupant load of 2 on the proposed use of the space to the north of the
Meeting Room is based on occupant density 10/1000 sq ft multiply the area of 221 sq ft. In
reality, this area is primarily served as pathway to offices and the existing lunch area.
Review Note 22 — We shall use an Exit Door in the Meeting Room in a means of egress to
Hallway, which shown in Page 3.
I hope these editing and clarification will meet your approval. Thanks you.
Pastor David Lo
Simon Lui (Church Board) V✓