Loading...
20170123160116.pdfsN� �� towns 11 (A)RESUB ID""" 1 0 S 1 T R !T JAN 2 3 2017 SUILDNG DEPARTMENT CITY OF EDMONDS DEPARTMENT OF FIRE PREVENTION 1/10/2017 PLAN REVIEW NOTES FOR 8401 Main Street, Edmonds, Fire Alarm BLD20170028 Fire Alarm This review is conducted in accordance with 2015 International Fire Code, NFPA 72 and Edmonds Community Development Code. 1. FA1 — Call out correct Building Data. 2. FA2 — Call out at least one smoke detector and one horn strobe in the unoccupied space. 3. FA2 — Call out an enunciator at the main entrance. 4. FA1,2 — Call out on "The location of the exterior notification device will be as approved by the fire marshal." 5. Ensure all address points have adequate descriptions for fire fighter use and those descriptions are transmitted to the monitoring company. 6. Provide a certificate of competition, NFPA 72, 2013, 7.2.1 Please contact me if you have any questions. Kevin Zweber Fire Marshal 425-771-0213 12425 Meridian Avenue S / Everett WA 98208 / 425-551-1200 www.firedistrictl.org