20170306162336.pdfIPGSM-4G
Single or Dual Path Commercial
Fire Communicator
General
The IPGSM-4G is a commercial fire alarm communicator that
otters conlact ID reporting with any Fire Alarm Control Panel
(FACP) that has a built-in dialer. This single or dual 2111 com-
municator connects directly to the primary and secondary
communication potis of a fire panel's Digital Alarm Communi-
cator Transmitter (DACT). It offers three selectable reporting
paths which Include- Celkilar only, IP only, or IP primary/cellu-
lar backup. All signals from the IPGSM.4G are delivered to
Honeywell's AlarmNet Network Control Center, which routes
highly encrypted Ethernet data packets via a customer pro-
vided internet connection or cellular network to the appropriate
central station. The stale of the art AlarmNet network control
center is fully redundant and monitored 24/7. AlarmNel has
the abdty to route messages using Alarnri and 800 PLUS
services, providing true redundancy and multipath message
delivery.
Alternative communication methods are critical in the market-
place due to VoIP (Vo�ce over IP). migration from POTS (Plain
Old Telephone Service) and growth of digital radio networks.
The IPGSM-4G's single path communications solution allows
one technology to be used (Either IP or cellular) to provide the
appropriate connectivity to a central station. For added reliabil-
ity, our exclusive dual path solution allows both technologies
(P and cellular) to be used together for maximum survivability
or for local jurisdiction requirements that specify a clual tech-
nology system.
The I PGSM-4G is designed to operate over the most common
cellular networks including 2G,3G and 4G. Its multi -GSM plat-
form technology automatically chooses the best available cel-
lular signal In the area based on signal strength and
seamlessly self-adjusis to maintain critical life safety communk
Galion. In addition, It connects to any type of customer pro-
vided Ethernet 101100 base network connection (LAN or
WAN), DSL model or cable modem. Our selectable reporting
path feature allows the radio to be configured for a single or
dual path solution as well as Inin. appropriate supervision inter-
vals based on NFPA 72 requirements. (See diagram below for
selectable paths and supervision timing intervals.)
Selectable Path
I
Description
Supervision
Times
—
2010 GSM
2010 IP
Single Path (cellular only)
Single Path (IP only)
5 minutes
5 minutes
2010 IP & GSM
Dust Path (IP and cellular)
24 hours
2013 GSM
Single Path (cellular only)
1 hour
1 hour
2013 IP
Single Path (IP only)
2013 IP & GSM
Dual Path (IP and cellular)
6 hours
Features
Saves the cost of two dedicated phone lines,
Single or dual path communications. (Can communicate to
central station using cellular technology, internet or both.
Requires no change to the existing Fire Alarm Control
Panel configuration. (Connects directly to the primary and
secondary telephone ports of a DACT.)
Honeywell
• Multi -GSM platform compatibility for 2G, 3G and 40 net-
works,
• Operates over the following communication protocols:
HSPA+ (4G) HSPA (HISDPA & HSUPA) (3G) EDGE (2G)
GPRS (2G).
• Selectable reporting paths and supervision Intervals to
meet NFRA 72, chapter 26 requirements. (Compliant with
NFPA 72 2010 and 2013 supervision requirements.)
• Works over any type of customer provided Ethernet 10/100
based network connection (LAN or WAN), DSL modern or
cable modem.
• Data transmits over standard contact -ID protocol but is
secured with the industry's advanced encryption standard
(AES 256 bit).
• Supports both dynamic (DHCP) or Public and Private Static
IP addressing.
• Built -In Power Supply module: On board charging circuit
design accommodates back-up battery, Includes primary
power and battery supervision.
• Diagnostic LEDs: Signal strength and status indicators.
• Reliable connection: IP and GSM connection tested every
day.
• QOS: Quality of Service diagnostics via AlarmNet convoys
vital communicator information Including when message
was received, signal strength, and message path used.
• 7720P Hand-held programmer for easy setup.
Operation
When an event occurs, the Fire Alarm Control Panel goes off
hook to dial the central station. The IPGSM-4G Dialer Capture
Module detects the off -hook condition and provides the fire
panel with a dial tone- When the fire panel detects the dial
tone, it begins dialing the central station. After the dialing is
completed, the Dialer Capture Module returns a handshake to
the fire panel. The fire panel then sends the contact ID reports
to the Dialer Capture Module, which in turn sends a kiss -off
after the report is successfully received from the fire panal.
The Dialer Capture Module sends the contact ID reports to the
IPGSM communications module. When all the reports are
sent, the fire panel goes on -hook. The IPGSM communica-
lions module then transmits the messages to the central sta-
tion either over the GSM network or the Internet (dependent
on configuration),
R %, VVZ L.
ECEI
M A R 0 6' 2 017
DEVELOPMENT SERVICES
COUNTER
Easy to Program
The IPGSM-4G communicator can be pre-programmed using
the 7720P programmer to enter all central-slation information.
This is saved to the 1PGSM-4G communicator panel memory.
When the IPGSM-4G communicator is installed at the site and
connected to the Internetlintranet, if registers itself with the
AlarmNet receiver.
.For most installations, the only required parameters are:
• Primary City ID (two digits) obtained from your monitoring
station.
• Primary Central Station ID (two digits) obtained from your
monitoring station.
• Primary Subscriber ID (four digits) obtained from your mon-
itoring station,
• Communication Module's MAC ID, and MAC CRC number
located on outside of box, and inside of the modula.
All of these parameters are assigned by the monitoring station.
NOTE. Some assembly is required. See Installation and Setup
Guide #800-12454 for full details.
Fire Communicator Capability
The IPGSM-4G is compatible with fire panels that use the
Contact ID communications formal as described in the SIA
DC-05 standard.
Alarmlillet
Honeywell's AlarmNet has been the nationwide leader in
alarm communications technology since 1986. A reliable alter-
native for the transmission of alarm signals, our radio network
provides exiensive coverage in the United States and Canada.
AlarmNel Network Control center processes signals from pow-
erful servers in multiple locations equipped with 2417 inffa-
structure support. The AlarmNot network consist of redundant
hardware servers, hot back -kip databases and generators with
battery back-up at all locations to ensure continuity of service
Signals from Alarm -Not are transmitted to the central station's
receivers using multiple communications paths consisting of
the Internet, radio network or toll -free POTS service.
Installation Requirements
UL COMPUANCE
To meet UL864/NFPA, ensure the following:
IPGSM-4G must be installed in accordance with NFPA
(National Fire Protection Association) standards 70 and 72.
IPGSM-4G must be mounted in the same room and within
20 feet of the fire panel.
IPGSM-4G, and all equipment used for the IP connection
(such as the router, hub, modem, etc.) shall be listed, must
be powered from an un-switched branch circuit, and be pro-
vided with appropriate standby power.
IPGSM-4G must use the 7AH battery (not supplied) to pro-
vide 24-hour backup capability.
Electrical Specifications
Transformer:
— Primary 120VAC, 60Hz, 0.5A.
— Secondary: 18VDC, 50VA.
Battery:
— One 12 V 7.0 AH lead -acid battery (not supplied).
— Battery charging current: 1 Amp maximum.
— Battery discharge current: Standby 230mA, Active
950mA.
Cabinet Specifications
Dimensions: 14.875- H x 12.75- W x 3.0" D (37.8 cm H x 32.4
cm W x 7.6 cm D).
Color: Red.
Shipping Specifications
Weight: 5.3 lbs. (6-94 kg).
Dimensions: 15.625" H X 13.79- W x 9.25" 0 (39.7 crn H x
34.9 cm W x 23.9 cm D)
Temperature and Humidity Ranges
This system meets NFPA requirements for operation at 0 -
49'C/32 - 120'F and at a relative humidity 93% * 2% RH (non
condensing at 321C * 2'C (907 ± 3'F). However. the useful
life of the system's standby batteries and the electronic com-
ponents may be adversely affected by extreme temperature
ranges and humidity. Therefore. it is recommended that this
system and its peripherals be installed in an environment with
a normal room temperature of 15 - 27'C/60 - 801F.
Product Line Information
IPGSM-4G-. Internet and Digital Cellular Fire Alarm Communi-
cator Panel. Includes red cabinet with Ademco key and lock.
wall outlet box, Dialer Capture Module, IGSM Communications
Module, antenna & mounting adapter, PowerBoostl power
supply, LED display board, transformer, manual, & required
screws, cables, etc.
Antenna Kits
GSM-ANT3DB25KT: 25 ft. antenna kit. Includes GSM-ANTSDB,
WA7626-CA adapter cable, and a 25' RF cable.
Q8M-ANT3DB50KT: 60 ft. antenna kit. Includes GSM-ANT3DB,
VVA7626-CA adapter cable, and a 50'RF cable.
Antonno-ExIffirrial-haltdware
GSM-ANT3DO: 3db gain external/remote antenna.
WA7626-CA: SNA to N Adapter,
7626-SOHC: 50 ft. antenna cable, low loss.
7626-25HC: 25 ft. antenna cable, low loss.
NOTE., The GSM-AIYT3DB and the WA7626-CA are both required
lbr installing an oxternal antenna along Mth the necessary cable
noedod (7626-50HC. 50 ft. or 76P6-PSHC; 25 ft.)
QIftqLA90AM1941
7720P: IPGSM40 hand held programmer.
HPTCOVER: Plug in transformer box for 1PGSM communicator.
BAT-1270: Battery 12 Volts, 7 AH, sealed.
Agency Listings and Approvals
The listings and approvals below apply to the basic IPGSM-4G
communicator panel. In some cases, certain modules may not be
listed by certain approval agencies, or listing may be in process.
Consult factory for latest listing status.
UIL Listed: S789.
CSFM: 7300-1645:0199.
FDNY: COA #6150.
Page 2 of 3 — DH-60769:B - 3/25/13 www.honeywell.com
This document Is not intended to be used [or installation purposes. We try to keep our product Information up-to-date and accurate. We cannot coverall spKlrtc
applications or anticipate all requirements. All spedfications are subject to change without notice.
C2014 by Honeywell International Inc. All rights reserved, Unauthodzed use of this document is strictly prohibited.
Automation and Control Solutions
Honoywell
12 Clintonville Road 1(877) HPP-POWR
Norlhford, CT 06472-1610
www.honeywelipower.com
hppjechserv@honeywell.00m
DH-60769:8
April 2014
Made In the U.3A
OUSIRegistersdIrradam!rk IS9100
02014HonoyWellInternational m.
Page 3 of 3 INAUTY 113TIMS