20170321105014.pdfRESPONSES TO PLAN REVIEW COMMENT
TECHCRAFT CORPORATION RESUB
2126 NW 204" St, Shoreline, WA 98177 MAR 2 1 2017
Tele: 206-817-6081
Email: david6081(u-)qmail.com BUILDiNG DEPARTMENT
CITY OF EDMONDS
City of Edmonds Wastewater Pretreatment Program
Plan Check#: BLD20170032 Date: January 19, 2017
Project Name / Address: Sizzle Steak House / 23805 HWY 99 #10 1, Edmonds
Contact Person / Email / Phone: David Lee / david6081 gmail.com / 206 817 6081
Reviewer: Les Krestel
Division: Wastewater Treatment Plant / Pretreatment
Date: 3/8/2017
Les Krestel:
Thank you for your detailed review on this project. The flowing is our
responses for your comment regarding the changes you review comments.
The plumbing plans of the kitchen clearly show which fixtures go where. These
plans show the fixtures connected to the GT and fixtures going to the sanitary
with dedicated waste lines.
Response: We verifiod again and recalculated a// DFU acco�! i'li �g to plumbing
review corrections.
2. Pretreatment accepts the submitted kitchen plans and will offer no changes.
Response: Thank you.
3. An approved/signed GT sizing sheet is required before this permit can be
approved by pretreatment.
Response: GT sizing sheet is provided and also attached in this letter
4. Please complete and return to me by email the Hydromechanical Grease
Interceptor portion of the City of Edmonds Grease Trap & Grease Interceptor
Permit Submittal Requirements Form. The Hydromechanical Grease interceptor
sizing work sheet will be included with this plan review when sent to the permit
applicant.
Response.- provide City of Edmonds Grease Trap & Grease Interceptor 1'--"E�rmit
Submittal Requirements Form with permit application form &H"aid-thf,-
-appliGa-fiewh.-e- P-le-ase-verify. 1,0/ P1D-Q->fUi'T - i4j-
5. Will the GT be installed above ground or underground? If the GT is installed
underground, be sure to leave sufficient space above the GT for removing the lid
during GT maintenance.
Response: the GT will be installed underground, We set it Linder a removable s.s.
work table to prevent wolkers tripped on the grease trap cover. It will be easy for
grease trap cleaning process since the work table can be easily slide out.
6. The smallest size permitted for a grease trap is 35 gallons.
Response.- calculated size as 35 GPM, noted on plan as an min. size required.
Should you have any questions and concern, please contact me as your convenient: My
cell phone 206-817-6081, Email: david6081Agmail.com .
Sincerely,
David Lee
Techcraft Corp.