Citv of Edmonds
PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
May 1, 2017
Lawerence Houston
lawerencehouston&comcast.net
Eric Carter, Plans Examiner
Plan Check: BLD2017-0398
Project Address: 20902 HillCrest PL
Scope: Remodel / New Single Family Dwelling — R-3/U occupancy group — V-B
construction— mechanical and plumbing included
Please be advised that the building plans for the above referenced project have been disapproved
for the purposes of obtaining a building permit. During a review of the plans by the Building
Division for compliance with the applicable building codes, it was found that the following
information, clarifications, or changes are needed. Reviews by other divisions, such as Planning,
Engineering, or Fire, may result in additional comments that require attention beyond the scope of
this letter. Items that recur on this list appear in italics.
A complete review cannot be performed until the revised plans/documents, including a
written response in itemized letter format indicatin where the 'clouded' or otherwise
hil!hlil!hted changes can be found on the revised plans, have been submitted to a Permit
Coordinator.
Resubmittals must be made at the Development Services Department on the 2 d Floor of City Hall.
Permit Center hours are M, T, Th, & F from 8am-4:30pm and from 8:30am-12pm on Wednesdays.
This building plan review cannot be completed until we receive the following items:
Sheet A 0.0:
Energy Notes:
a. Item 2 references a climate zone of "I". Snohomish County is referenced as 4C. Please
change on the plans.
b. Item 6, details whole house ventilation per section M1508.4 of the IRC. Whole house
ventilation requirements are specified in section M1507.3 of the 2015 IRC. With a
ventilation rate of 50CFM for a total of 8 hours a day, your ventilation requirements are
not being met for a home of this size. Please change on the plans to comply with table
1507.3.3(l) or 1507.3.3(2)
c. Item 9 specifies using energy credit 5b. Credit 5b only allows for I credit. A home of this
size requires a minimum of 3.5 credits. Please indicate on the plans the additional credits
per table 406.2 of the Washington State Energy code that will be used. If high efficiency
heating and cooling appliances are opted, please indicate on the plans their location and
ratings.
TABLE M1507.3.3(l)
CONTINUOUS WHOLE -HOUSE MECHANICAL VENTILATION SYSTEM AIRFLOW RATE REQUIREMENTS
DWELLING UNIT
NUMBER OF BEDROOMS
FLOOR AREA
0-1 __F_2 — 3 1 4-5 1 6-7 1 > 7
(square feet)
Airflow In CFM
< 1,500
30
45
60
75
90
1,501 — 3,000
45
60
75
90
105
3,001 — 4,500
60
75
90
105
120
4,501 —6,000
75
90
105
120
135
6,001 — 7,500
90
105
120
135
150
> 7,500
105
120
135
150
165
For SI: I square foot = 0.0929 m', I cubic foot per minute = 0.0004719 m/s.
TABLE M1507.3.3(2)
INTERMITTENT WHOLE -HOUSE MECHANICAL VENTILATION RATE FACTORS6.b
RUN-TIME PERCENTAGE IN EACH 4-HOUR
SEGMENT
25%
33%
50%
66%
75%
100%
Factor'
4
3
2
1.5
1.3
1.0
a. For ventilation system run time values between those given, the factors are permitted to be determined by interpolation.
b. Extrapolation beyond the table is prohibited.
Sheet S2.0
1. References to plan notes are indicated. Page numbers are not associated with these notes.
Please indicate on the plans the applicable page in which these notes reference.
2. The foundation plan appears to indicate pier footing sizes but does not reference which plan
page to reference for details. Please add page reference to plans.
3. Beam callouts on the "upper floor and low roof' framing plan do not reference size or have
indications to reference S3.4. Indicate on the plans the beam sizes or add reference of where
to find the sizing.
Please be aware, upon review of your resubmitted information, additional comments may be
generated.