2017-04-10 Magic Toyota Edmonds_Permit Set - hvac.pdfA AMPS IBC INTERNATIONAL BUILDING CODE AC AIR CONDITIONING ICW INDUSTRIAL COLD WATER ACH AIR CHANGES PER HOUR ID INSIDE DIAMETER/DIMENSION ACT ACOUSTICAL CEILING TILE IE INVERT ELEVATION AD ACCESS DOOR IEER INTEGRATED ENERGY EFFICIENCY RATIO ADD'L ADDITIONAL IMC INTERNATIONAL MECHANICAL CODE AFF ABOVE FINISHED FLOOR IN INCHES AFG ABOVE FINISHED GRADE IN WG INCHES WATER GAUGE AHU AIR HANDLING UNIT IPLV INTEGRATED PART LOAD VALUE ALUM ALUMINUM KW KILOWATTS AMP/AMPS AMPERAGE LAT LEAVING AIR TEMPERATURE AP ACCESS PANEL LB/LBS POUND/POUNDS ARCH ARCHITECT LF/LIN FT LINEAL FOOT/FEET BC BEADED COLLAR LPG LIQUID PROPANE GAS BDD BACKDRAFT DAMPER LPS LOW PRESSURE STEAM BF BELOW FLOOR LVG LEAVING BHP BRAKE HORSEPOWER LWA SOUND POWER RATING LEVEL (IN DB) BLDG BUILDING LWG LOW WALL GRILLE BOD BOTTOM OF DUCT LWT LEAVING WATER TEMPERATURE BOP BOTTOM OF PIPE MAX MAXIMUM BOT BOTTOM MAU MAKE UP AIR UNIT BS BIRD SCREEN / BLACK STEEL MBH 1000 BRITISH THERMAL UNITS/HOUR BTU BRITISH THERMAL UNIT MCA MINIMUM CIRCUIT AMPACITY BTUH BRITISH THERMAL UNITS PER HOUR MD MOTORIZED DAMPER CAP CAPACITY MFR MANUFACTURER CBD CALIBRATED BALANCING DAMPER MISC MISCELLANEOUS cc CONTROLS CONTRACTOR MIN MINIMUM/MINUTE CD CEILING DIFFUSER/CONDENSATE DRAIN MPS MEDIUM PRESSURE STEAM CDWR CONDENSER WATER RETURN MT MOUNT CDWS CONDENSER WATER SUPPLY MTD MOUNTED CFM CUBIC FEET PER MINUTE MUW MAKE-UP WATER CHWR CHILLED WATER RETURN NA NOT APPLICABLE CHWS CHILLED WATER SUPPLY NC NORMALLY CLOSED/NOISE CRITERIA CLG CEILING NG/NGAS NATURAL GAS COL COLUMN NIC NOT IN CONTRACT CONC CONCRETE NO NORMALLY OPEN/NUMBER COND CONDENSATE NPW NON -POTABLE WATER CONN CONNECT/CONNECTED/CONNECTION N-R NON-RESIDENTIAL CONT CONTI NUOUS/CONTINUATION OA/OSA OUTSIDE AIR CONTR CONTRACTOR OBD OPPOSED BLADE DAMPER COORD COORDINATE OD OUTSIDE DIAMETER/DIMENSION COP COEFFICIENT OF PERFORMANCE PCF POUNDS PER CUBIC FOOT CT COOLING TOWER PD PRESSURE DROP CU CUBIC/CONDENSER UNIT PH PHASE CW DOMESTIC COLD WATER/CONDENSER WATER POC POINT OF CONNECTION DB DUCTBOARD/DRY BULB/DECIBEL P/PRESS PRESSURE DDC DIRECT DIGITAL CONTROL PSI POUNDS PER SQUARE INCH DEFL DEFLECTION PSIG POUNDS PER SQUARE INCH GAUGE DEG DEGREE/DEGREES QTY QUANITY DIA DIAMETER R RETURN GRILLE/RELOCATED/RETURN DMPR DAMPER RA RETURN AIR DN DOWN RD/RND ROUND DOAS DEDICATED OUTSIDE AIR SYSTEM REF REFERENCE DWG DRAWING REQ REQUIRED EXH EXHAUST RESID RESIDENTIAL EA EACH RF RELIEF EAT ENTERING AIR TEMPERATURE RG REFRIGERANT DISCHARGE GAS EC EGGCRATE GRILLE/END CAP/ELEC CONTRACTOR RL REFRIGERANT LIQUID EER ENERGY EFFICIENT RATING RPM REVOLUTIONS PER MINUTE EF EXHAUST FAN RS REFRIGERANT SUCTION EFF EFFICIENCY S SUPPLY EL ELEVATION SA SUPPLY AIR ELEC/ELECT ELECTRICAL/ELECTRIC SAT SATURATION/SUPPLY AIR TEMPERATURE EMCS ENERGY MANAGEMENT CONTROL SYSTEM SD SMOKE DETECTOR ENT ENTERING S/D SLIP & DRIVE CONNECTION EQUIP EQUIPMENT S-C SEATTLE --- CODE ESP EXTERNAL STATIC PRESSURE SEER SEASONAL ENERGY EFFICIENCY RATING EWT ENTERING WATER TEMPERATURE SENS SENSIBLE EXIST EXISTING SL SOUND LINED EXH EXHAUST SM SHEETMETAL F FAHRENHEIT SPEC SPECIFICATION FAC FIRE ALARM CONTRACTOR so SCREENED OPENING FD FIRE DAMPER SOG SLAB ON GRADE FDC FIRE DEPARTMENT CONNECTION SID STATIC PRESSURE FF FINISHED FLOOR SF SQUARE FEET FIC FURNISHED AND INSTALLED BY CONTRACTOR SS STAINLESS STEEL FIO FURNISHED AND INSTALLED BY OWNER STRUC STRUCTURAL FLA FULL LOAD AMPS SWS SERVICE WATER SUPPLY FLEX FLEXIBLE SWR SERVICE WATER RETURN FLR FLOOR TA TRANSFER AIR FOB FLAT ON BOTTOM TEMP TEMPERATURE/TEMPORARY FOIC FURNISHED BY OTHERS, TBD TO BE DETERMINED INSTALLED BY CONTRACTOR TOD TOP OF DUCT FOS FLAT ON SIDE TOS TOP OF STEEL/TOP OF SLAB FOT FLAT ON TOP TOT TOTAL FP FIRE PROTECTION TSP TOTAL STATIC PRESSURE FPM FEET PER MINUTE TSTAT THERMOSTAT FSD FIRE/SMOKE DAMPER TYP TYPICAL FT FOOT/FEET UH UNIT HEATER FLIT FUTURE UNO UNLESS NOTED OTHERWISE FV FACE VELOCITY V VOLT G GRILLE VD VOLUME DAMPER GA GAUGE/GALLON VEL VELOCITY GALV GALVANIZED VERT VERTICAL GC GENERAL CONTRACTOR VFD VARIABLE FREQUENCY DRIVE GPM GALLONS PER MINUTE VOL VOLUME GRD GRILLE/REGISTER/DIFFUSER W WRAPPED DUCT GWB GYPSUM WALL BOARD WB WET BULB HD HEAD WG WATER GAUGE HORIZ HORIZONTAL W/ WITH HP HORSEPOWER W/o WITHOUT HR HOUR W/SF WATTS PER SQUARE FOOT HSPF HEATING SEASONAL PERFORMANCE FACTOR WSEC WASHINGTON STATE ENERGY CODE HT HEIGHT HWTG HIGH WALL TRANSFER GRILLE HWR HOT WATER RETURN HWS HOT WATER SUPPLY HX HEAT EXCHANGER HZ HERTZ MECHANICAL LEGEND tioxio RECT SUPPLY AIR DUCT UP/TOWARD t1OX10 RECT SUPPLY AIR DUCT DN/AWAY tl OX1 0 RECT EXHAUST OR RETURN DUCT UP/TOWARD t10X107 RECT EXHAUST OR RETURN DUCT 1OX10 r7 DN/AWAY 100 GD ROUND DUCT - UP/TOWARD 100 ROUND DUCT - DN/ AWAY --1-0-0 S12X1O0ffl FLATOVAL DUCT - UP/ TOWARD S1 2X 100 "1 FLATOVAL DUCT - DN/ AWAY f3 DUCT OVERLAP *1 T 100 rN BOOT TAP t 100 At 100 45- TAP 100, VOLUME DAMPER 100 100 CALIBRATED BALANCING DAMPER RISE(R) & DROP(D) TRANSITION TURNING VANES/SPLITTERS (S) DUCT MOUNTED SMOKE DETECTOR BACK DRAFT DAMPER FLEXIBLE DUCT AIR FLOW (FORCED AIR) -A COMBINATION FSD FIRE DAMPER SMOKE DAMPER t4OTOV,--&QEV,ATEB44t11FEi f N I r_� I ACCESS DOORS SOUND TRAP FLEX CONNECTION 6X1 60D ACOUSTICALLY LINED DUCT OD OUTSIDE DIMENSIONS SL SOUND LINING (THICKNESS) rAN9999999,r FABRIC DUCT CLEARANCE SUPPLY AIR DIFFUSER (WITH CORE BLANKOFF) CEILING RETURN, TRANSFER OR EXHAUST AIR GRILLE SLOTTED DIFFUSER (PLAN VIEW) =A REVISION CLOUD & TRIANGLE ##0 ROUND DUCT SYMBOL ##X## 0 FLATOVAL DUCT SYMBOL ##0 DEGREES SYMBOL S POINT OF CONNECTION CD1-100 GRD TAG IDENTIFIER = TYPE-CFM 80 SIZE (D T'STAT/TEMP SENSOR CARBON DIOXIDE HUMIDITY SENSOR SENSOR SENSOR (DCARBON MONOXIDE SMOKE DETECTOR SENSOR (SHAND/AUTO SWITCH ()STATIC PRESSURE SENSOR &OX SENSOR () SLAB SENSOR EXISTING DUCTWORK DEMO DUCTWORK WALL -MOUNTED GRILLE oc PIPE ELBOW UP PIPE ELBOW DN DIRECTION OF FLOW DIRECTION OF SLOPE DOWN I PLUG OR CAP PRESS REDUCING ASSEMBLY SOLENOID VALVE PUMP Z--CHWS /CHWR-5 CHILLED WATER SUPPLY/RETURN z RL/RS REFRIGERANT LIQUID/SUCTION z NG NATURAL GAS z LPG LIQUID PROPANE GAS Z--CDWS /CDWR--S CONDENSER WATER SUPPLY/RETURI' Z--HWS/HWR--i HEATING WATER SUPPLY/RETURN Z-- COND --- i CONDENSATE z FOV FUEL OIL VENT FOS / FOR FUEL OIL SUPPLY/RETURN RDG REFRIGERANT DISCHARGE GAS T _FS -1 FLOW SWITCH MECHANICAL GENERAL NOTES 1. WORK SHALL CONFORM TO APPLICABLE CODES AND REGULATIONS, INCLUDING, BUT NOT LIMITED TO THE 2015 IBC, 2015 WSEC, 2015 IMC & 2005 SEATTLE BOILER AND PRESSURE VESSEL CODE WITH WASHINGTON STATE AMENDMENTS 2. DO NOT SCALE DRAWINGS, DIMENSIONS GOVERN. DIMENSIONS ARE TO FACE OF STUD, CONCRETE, OR MASONRY UNO. 3. LOCATION AND DETAILS OF EQUIPMENT, DUCT ROUTING, AND CONNECTIONS ARE APPROXIMATE. COORDINATE FINAL LOCATIONS WITH OTHER TRADES. INSTALL IN ACCORDANCE WITH APPROVED SUBMITTALS AND DETAIL DRAWINGS WHEN APPLICABLE. 4. VERIFY EXISTING CONDITIONS, DIMENSIONS, DETAILS, ETC. NOTIFY ENGINEER OF ANY DISCREPANCIES PRIOR TO PROCEEDING WITH WORK. 5. WHEN CONSTRUCTION DETAILS ARE NOT SHOWN OR NOTED FOR ANY PART OF THE WORK, DETAILS SHALL BE THE SAME AS FOR OTHER SIMILAR WORK. IF ADDITIONAL QUESTIONS REMAIN, CONTACT THE ENGINEER PRIOR TO PROCEEDING. 6. ALL STRUCTURAL OPENINGS AND PLATFORMS SHALL BE PROVIDED BY THE GENERAL CONTRACTOR UNO. 7. DUCT SEALING AND CONSTRUCTION TO MEET SMACNA AND ENERGY CODE REQUIREMENTS. UNLESS OTHERWISE NOTED, LOW PRESSURE DUCTWORK (DOWNSTREAM OF VAV BOXES, CONSTANT VOLUME AC SYSTEMS, TOILET EXHAUSTS, ETC.) TO MEET 2" CONSTRUCTION STANDARDS WITH SEAL CLASS C. MEDIUM PRESSURE DUCTWORK (UPSTREAM OF VAV BOXES, HIGH VELOCITY EXHAUSTS, ETC.) TO MEET 4" CONSTRUCTION STANDARDS WITH SEAL CLASS A. DUCT RISERS IN SHAFTS WITH DAMPERED PENETRATIONS TO MEET 6" CONSTRUCTION STANDARDS WITH SEAL CLASS A. 8. ALL CEILING DIFFUSERS ARE 4-WAY THROW UNLESS NOTED OTHERWISE. 9. ALL DUCT DIMENSIONS ARE OUTSIDE DIMENSIONS BEFORE SOUND LINING HAS BEEN ACCOUNTED FOR (SOUND LINING @ 1", UNO) 10. OUTSIDE AIR INTAKES ON ALL AIR HANDLING UNITS SHALL BE 10 FEET AWAY FROM ANY VENTS, STREETS, LOADING DOCK, NEIGHBORING LOT LINES & FUEL BURNING EQUIPMENT OR 3 FEET BELOW OR 25' ABOVE ANY CONTAMINANT SOURCE WITHIN 10 FEET. 11. ALL AIR ECONOMIZERS SHALL BE CAPABLE OF THE FOLLOWING PER C403.3.1 & C403.2.4.7: -0% TO 100% OF THE DESIGN SUPPLY AIR WITH FAULT DETECTION & DIAGNOSTIC REPORTING. -CONTROLLED BY A CONTROL SYSTEM DETERMINING IF THE OUTSIDE AIR CAN MEET PART OR ALL OF THE BUILDING COOLING LOADS. -INTEGRATED TO PROVIDE PARTIAL COOLING EVEN WHEN MECHANICAL COOLING IS REQUIRED. 12. OUTSIDE AIR INTAKE, RELIEF, AND EXHAUST OPENINGS SHALL BE CLASS 1 AND EQUIPPED WITH MOTORIZED (OR GRAVITY PER EXCEPTIONS IN C403.2.4.3) DAMPERS WHICH CLOSE AUTOMATICALLY WHEN SYSTEM IS OFF OR UPON POWER FAILURE, UNO FOR SMOKE CONTROL SYSTEM OPERATION 13. THE CONTROL SYSTEM SHALL MEET C403 AND BE PROGRAMMABLE, CAPABLE OF BEING SET FOR DIFFERENT DAY TYPES PER WEEK, DEADBAND SETTING OF AT LEAST 5-F (10-F FOR RESIDENTIAL BETWEEN THE HEATING AND COOLING SETPOINTS AND SETBACK TEMPERATURES WITH OPTIMAL START CONTROL. CNfROL SYSTEM SHALL INCLUDE A MICROPROCESSOR AND BE CAPABLE OF VARYING FLOWS AND RESETTING SUPPLY AIR & WATER TEMPERATURES BY REPRESENTATIVE BUILDING LOADS WHERE REQUIRED IN C403.4. 14. WHERE REQUIRED BY C408, RECORD DRAWINGS OF THE ACTUAL INSTALLATION SHALL BE PROVIDED TO THE BUILDING OWNER WITHIN 90 DAYS OF THE DATE OF SYSTEM ACCEPTANCE PER THE ENERGY CODE. AN OPERATING MANUAL AND MAINTENANCE MANUAL SHALL BE PROVIDED TO THE BUILDING OWNER. ALL HVAC SYSTEMS SHALL BE BALANCED AND A WRITTEN BALANCING REPORT SHALL BE PROVIDED TO THE OWNER. HVAC CONTROL SYSTEMS SHALL BE TESTED TO ENSURE THAT THEY OPERATE IN ACCORDANCE WITH APPROVED PLANS. A PRELIMINARY COMMISSIONING REPORT OF TEST PROCEDURES AND RESULTS SHALL BE PREPARED PRIOR TO ISSUANCE OF A FINAL CERTIFICATE OF OCCUPANCY. A COMPLETE FINAL COMMISSIONING REPORT OF TEST PROCEDURES AND RESULTS SHALL BE PROVIDED TO THE OWNER. 15. MECHANICAL SYSTEMS SHALL COMPLY WITH SEISMIC RESTRAINT REQUIREMENTS OF THE BUILDING CODE, SMACNA AND ASCE 7. ALL LIFE SAFETY OR HAZARDOUS MATERIAL RELATED SYSTEMS SHALL BE DEEMED AN Ip=1.5 FOR RESTRAINT METHODS OR AS NOTED ON THE DRAWINGS. REFER TO CODES FOR INSTALLATION REQUIREMENTS AND EXCEPTIONS BASED ON SIZING, WEIGHTS AND MOUNTING HEIGHTS. 16. PROVIDE EARTHQUAKE RESTRAINTS FOR HVAC EQUIPMENT AS REQUIRED BY SMACNA SEISMIC RESTRAINT MANUAL, SEISMIC HAZARD B. WIRES FOR CEILING SYSTEM ETC. SHALL NOT BE HUNG OFF HVAC EQUIPMENT OR HVAC EQUIPMENT SUPPORTS. 17. PROVIDE FIRE AND COMBINATION FIRE/SMOKE DAMPERS WHERE SHOWN ON PLANS AND WHERE REQUIRED PER CODE. i tell F.11 I a 9 1 a I IL [a a 0 Ll I a 1 162,111 [01 Ll 619 1 M 1 50111111 0 0 ,kill 10 11 F.13 &I I T, I Z 101 W.11 y a 1000 1115 9 1 iOki A [oil 1.1111 1, '14 1 Ll 19. SMOKE DETECTORS PROVIDING AUTOMATIC SHUTDOWN SHALL BE PROVIDED FOR HVAC EQUIPMENT DELIVERING >2000 CFM (INCLUDING MULTIPLE UNITS DUCTED INTO COMMON DISTRIBUTION OR RETURN, WITH A TOTAL SUPPLY >2000 CFM) OR EACH STORY OF RETURN SYSTEMS OVER 15,000 CFM IN A MULTI -STORY INSTALLATION, PER CODE. SMOKE DETECTORS SHALL BE FIC (ELEC) UNO. POWER -WIRING AND INTERLOCK TO FIRE ALARM SYSTEM BY ELECTRICAL CONTRACTOR AS APPLICABLE. VAV BOX (WITH FAN) SHUTDOWN CAN BE THROUGH CONTROLS SYSTEM. 20. MECHANICAL ACCESS PANELS SHALL BE PROVIDED BY MECHANICAL CONTRACTOR AND INSTALLED BY GENERAL CONTRACTOR. 21. ALL MOTOR STARTERS NOT SHOWN IN EQUIPMENT SCHEDULES SHALL BE FURNISHED AND INSTALLED BY ELECTRICAL CONTRACTOR. MOTOR EFFICIENCIES TO MEET OR EXCEED CODE MINIMUM. 22. FOR ALL "SEALED AIR TIGHT" OR PRESSURIZED SHAFTS/ROOMS, THE FOLLOWING SHALL OCCUR: -ALL VERTICAL JOINTS & CORNERS SHALL BE PROVIDED WITH A CONTINUOUS SEAL FOR THE LENGTH OF THE JOINT (BY GC). -TOP AND BOTTOM WALL TRACKS SHOULD BE CAULKED ALONG THEIR ENTIRE LENGTH (BY GC). -ANY FLOOR DECKING PERPENDICULAR TO THE CONSTRUCTION SHALL BE CAULKED (BY GC). FILLING WITH ROCK WOOL IS NOT ACCEPTABLE. -ANY PENETRATIONS OF THE CONSTRUCTION (DUCTWORK CONDUIT PIPING, ...) SHALL BE SEALED ON BOTH SIDES -ALL DOORS SHALL BE PROVIDED WITH TIGHT FITTING GASKETS MD THRESHOLD SWEEPS, AND OPEN AGAINST THE DIRECTION OF PRESSURE. -USE SECTION 909.5 OF THE 2012 IBC FOR MAX ALLOWABLE LEAKAGE AREA, FOLLOWING THE GUIDELINES FOR TIGHT STAIR SHAFT CONSTRUCTION. 23. ALL ADHESIVES, SEALANTS, PAINTS AND COATINGS USED DURING THE INSTALLATION/FINISH WORK SHALL MEET THE LEED REQUIREMENTS FOR IEQ. 24. MAXIMUM STANDARD LENGTH OF FLEXIBLE DUCT SHALL BE 12 FEET; UP TO 25' MAXIMUM LENGTH IS ACCEPTABLE IF; FLEX DUCT (UL-181 TESTED & NOT "CONNECTOR") IS USED DUCT 0 IS INCREASED BY 1 NOMINAL SIZE & BENDS DO NOT EXCEED 235* TOTAL. REFER TO INSTALLATION DETAILS FOR SUPPORT REQUIREMENYS. FLEXIBLE DUCT FLAME SPREAD RATING SHALL BE < 25 AND SMOKE DEVELOPED RATING SHALL BE < 50. USE THERMAFLEX MODEL G-KM FOR LOW AND MEDIUM PRESSURE APPLICATIONS OR APPROVED EQUAL. 25. ELECTRICAL METERING OF SYSTEMS AS REQUIRED BY ENERGY CODE SECTION C409 IS BY ELECTRICAL. THE ELECTRICAL DESIGN & CONTRACTOR TEAM WILL FURNISH THE NECESSARY ELECTRICAL DISTRIBUTION AND METERING COMPONENTS - SEE ELECTRICAL DRAWINGS. THE MECHANICAL CONTRACTOR WILL FURNISH A BUILDING MANAGEMENT SYSTEM CAPABLE OF COLLECTING AND STORING THE INFORMATION WITH A VISIBLE DISPLAY/NOTIFICATION READILY ACCESSIBLE TO OPERATION AND MANAGEMENT PERSONNEL AS REQUIRED. MINIMUM DUCT INSULATION LAST UPDATED 07/11/16 DUCT TYPE DUCT LOCATION (IN HEATED AND MECHANICALLY COOLED DUCT SYSTEM) INSULATION R-VALUE REMARKS SUPPLY & RETURN NOT WITHIN CONDITIONED SPACE: OUTSIDE BUILDING R-8 1,2,3 OUTSIDE AIR WITHIN CONDITIONED SPACE: INSIDE BUILDING SEE NOTES 4 & 5 1,2,3,4,5 SUPPLY & RETURN NOT WITHIN CONDITIONED SPACE: INSIDE BUILDING R-6 1,2 SUPPLY AIR <550 OR >1050 WITHIN CONDITIONED SPACE R-3.3 1,2 1 Kt:[-LK I U UqU3.2.8 t-UK 1-UK I HLK KLQUIKLIVILN I b & ALbU KI+UJ [-UK KLbIULI\J I IAL 11\4b I ALLA I IUI\Jb 2 INSULATED COOLED DUCTS REQUIRED A VAPOR RETARDER (PERM < 0.5) AND SEALED JOINTS 3 WEATHERPROOF BARRIER REQUIRED AROUND DUCTWORK TO MAINTAIN WATER TIGHTNESS 4 INSULATE OUTSIDE AIR DUCTS TO BUILDING EXTERIOR WALL LEVEL PER ENERGY CODE SECTION: C403.2.8.1 UNTIL CONNECTED TO EQUIPMENT SERVED OR TO THE CODE REQUIRED SHUTOFF DAMPER (AND 1"THICK INSULATION MIN. 2 TO PREVENT CONDENSATION ON DUCTS IN PLENUM UP TO THE HEATING OR COOLING EQUIPMENT) 5 R-7 CAN BE USED IN LIEU OF BUILDING ENVELOPE INSULATION LEVEL IF: DEDICATED OUTSIDE AIR SYSTEM AND <2,800 CFM SUPPLY AIR MINIMUM PIPE INSULATION LAST UPDATED: 07/11/16 FLUID DESIGN OPERATING TEMPOF INSULATION CONDUCTIVITY NOMINAL PIPE DIAMETER (INCH) ONDUCTIVITY LC RANGE MEAN TEMP RATING OF <1 1 TO < 1- 1/2 1-1/2 To 1 < 4 4 TO < 8 > 8 HEATING SYSTEMS (STEAM, CONDENSATE, HYDRONIC HOT WATER, DOMESTIC HOT WATER & RECIRC) >350 0.32-0.34 250 4.5 5.0 5.0 5.0 5.0 251-350 0.29-0.32 200 3.0 4.0 4.5 4.5 4.5 201-250 0.27-030 150 2.5 2.5 2.5 3.0 3.0 141-200 0.25-0.29 125 1.5 1.5 2.0 2.0 2.0 105-140 O�21-0.28 100 1.0 1 1.0 1 1.5 1.5 1.5 DOMESTIC COLD WATER AND HORIZONTAL RAIN LEADERS TO FIRST VERTICAL RAIN LEADER (TO PREVENT CONDENSATION) N/A 1 0.21-027 1 75 1 0.5 1 0.5 1 0.5 0.5 0.5 COOLING SYSTEMS (CHILLED WATER, BRINE AND REFRIGERANT, WATERSIDE ECONOMIZER SYSTEMS)" 40-60 O�21-0.27 75 7 0. 5 0.5 1.0 1.0 1.0 40 0.20-0.26 i_ 75 1 0.5 1.0 1.0 1.0 1.5 NOTE: NOT REQUIRED FOR STRAINERS, CONTROL VALVES & BALANCING VALVES ASSOCIATED WITH PIPING 1" OR LESS IN DIA. TYPICAL CONDENSER WATER PIPE IN NON -ECONOMIZER SYSTEMS IS NOT INSULATED SEE R403 FOR RESIDENTIAL INSTALLATIONS. DRAWING INDEX SHEET NO. SHEET TITLE CURRENT REVISION MO.00 LEGEND, ABBREVIATIONS, GENERAL NOTES & SHEET INDEX HVAC MO.01 SCHEDULE SHEET - HVAC MO.02 SEQUENCE OF OPERATIONS - HVAC MO.03 SEQUENCE OF OPERATIONS - HVAC MPO.01 H HYDRONIC SYSTEM: SCHEDULE SHEET - HVAC M2.01 1 ST FLOOR PLAN HVAC M2.02 2ND FLOOR PLAN HVAC M2.R1 ROOF PLAN - HVAC M5.01 DETAIL SHEET - HVAC MP2.01 1ST FLOOR PIPING PLAN HVAC MP2.02 2ND FLOOR PIPING PLAN HVAC MP2.R1 ROOF PIPING PLAN - HVAC MP6.01 SCHEMATIC PIPING DIAGRAM - HVAC MP2.01 H HYDRONIC SYSTEM: 1ST FLOOR PIPING PLAN HVAC MP2.02H HYDRONIC SYSTEM: 2ND FLOOR PIPING PLAN HVAC M I K I W11 w 0 of *1 off of of off of 0 LEGAL DESCRIPTION NE 1/4 OF THE NW 1/4 SECTION 29, TOWNSHIP 27N RANGE E4, W.M. VICINITY MAP NO SCALE M�W I MIN NO SCALE � 1,re-Y.03112 IN a M1 A C, 0 C, Hermanson Building Today, Defining Tomorrow Hermanson Company LLP 1221 2nd Avenue North Kent, Washington 98032 Tel: (206) 575-9700 Fax: (206) 575-9800 www.hermanson.com Contractor Reg #: HERMACLO05BJ M.AG I C TOYOTA OFEDMONDS 21300 HIGHWAY 99 EDMONDS, WA 98026 ODOR WAS Jk 36149 L Revisions 04/12/17 JMH ISSUE FOR PERMIT 03/31/17 JMH COORD SET REV3_ 03/24/17 JMH COORD SET REV2 - A 03/17/17 JMH COORD SET REV1_ 03/02/17 JMH DID SET No. Date By Description Design Team Design JMH Drawn FVP Checked DTN Project Number 11-17-10152 Issue Date 04/12/17 LEGEND, ABBREVIATION, GENERAL NOTES & SHEET INDEX-HVAC MOM00 UNIT TAG CU-1 LOCATION ROOF AREA SERVED ELEV. MACH. RM. BASIS OF DESIGN LG LAU 150HYV2 OUTDOOR AC UNIT COOLING CAPACITY BTUH TOTAL SENS. SEER/EER 15000 11250 24 SPLIT SYSTEM HEATING HEATING CAPACITY ELECTRICAL SOUND BTUH HSPF/COP MCA V/PH dBA 18000.00 12.5 19 208-230/1 57 AND COOLING UNIT SCHEDULE WEIGHT UNIT BASIS OF LBS TAG LOCATION SERVES DESIGN 122 IU-1 WALL ELEV. MACH. RM. LG LAN150HYV2 INDOOR AIR HANDLING UNIT SUPPLY OSA ESP CFM CFM IN WG 317/424/565/741 0.00 MAX REFR LINE FT 98.4 HEATER KW NA ELECTRICAL MCA V/PH NA NA LAST UPDATED: SOUND WEIGHT dBA LBS 47 34 04/10/17 REMARKS 1-11 CU-2 ROOF IT RM. LG LAU 150HYV2 15000 11250 24 18000.00 12.5 19 208-230/1 57 122 IU-2 WALL IT RM. LG LAN150HYV2 317/424/565/741 - 0.00 98.4 NA NA NA 47 34 1-11 CU-3 ROOF TECHLOUNGE LG LAU150HYV2 15000 11250 24 18000.00 12.5 19 208-230/1 57 122 IU-3 WALL TECHLOUNGE LG LAN150HYV2 317/424/565/741 0 0.00 98.4 NA NA NA 47 34 1-11 CU-4 ROOF WORK LG LAU150HYV2 15000 11250 24 18000.00 12.5 19 208-230/1 57 122 IU-4 WALL WORK LG LAN150HYV2 317/424/565/741 0 0.00 98.4 NA NA NA 47 34 1-11 CU-5 ROOF F&I LG LAU 150HYV2 15000 11250 24 18000.00 12.5 19 208-230/1 57 122 IU-5 WALL F&I LG LAN 150HYV2 317/424/565/741 0 0.00 98.4 NA NA NA 47 34 1-11 CU-6 ROOF SERVICE MGR. LG LAU150HYV2 15000 11250 24 18000.00 12.5 19 208-230/1 57 122 IU-6 WALL SERVICE MGR. LG LAN150HYV2 317/424/565/741 0 0.00 98.4 NA NA NA 47 34 1-11 CU-7 ROOF SUPPORT LG LAU150HYV2 15000 1 11250 1 24 18000.00 12.5 19 208-230/1 57 122 IU-7 WALL SUPPORT LG LAN150HYV2 317/424/565/741 0 0.00 98.4 NA NA NA 47 34 1-11 GENERAL ALL TRADES TO CONFIRM EQUIPMENT REQUIREMENTS (ELECTRICAL, WEIGHT, SIZE, ETC ... ) WITH APPROVED SUBMITTALS PRIOR TO INSTALLATION; FIELD COORDINATE FINAL LOCATION & INSTALL PER MANUFACTURERS REQUIREMENTS REMARKS: 1 ELECTRICAL CONTRACTOR TO PROVIDE SCCR PROTECTION FOR EQUIPMENT AS REQUIRED BY NATIONAL ELECTRICAL CODE. MANUFACTURER TO PROVIDE SCCR LISTING (5 KAIC MINIMUM) INSIDE CONTROL PANEL AS REQUIRED BY NATIONAL ELECTRICAL CODE. 2 SPLIT SYSTEM UNITS REQUIRE DISCONNECT AT THE ROOF CONDENSING UNIT BY ELECTRICAL CONTRACTOR 3 INVERTER DRIVEN COMPRESSOR, TEST CONDITIONS BASED ON AHRI 210/240 4 SINGLE CONDENSING UNIT FOR EACH INDOOR FAN COIL UNIT. PROVIDE WITH WALL -MOUNTED WIRELESS PROGRAMMABLE T'STAT, REFRIGERANT LINE SET (1/4" LIQUID &3/8" SUCTION LINES) FOR EACH UNIT CONNECTION, WIND BAFFLE, LOW AMBIENT OR HEAD PRESSURE CONTROL SUITABLE FOR LOW AMBIENT COOLING 5 REFRIGERANT: R-410A. PROVIDE ADDITIONAL CHARGING OF LINES AS REQUIRED FOR LONG LINE LENGTH APPLICATIONS 6 PROVIDE WALL MOUNTED FCU CONDENSATE DRAIN PUMP (GOBI 230-XL - 2.5 GPH @ 10 FT LIFT & < 100 FT HORIZ, 115V/1PH @ 32W, 5 LBS). TERMINATE DRAIN LINE IN HUB DRAIN BY NEAREST SINK TAILPIECE OR INDIRECT AT NEAREST FLOOR DRAIN OR PROVIDE CONDENSATE DRAIN PUMP (BECKETT 151UL - 15 GPH @ 15 FT LIFT 120V/1PH @ 60W, 4 LBS). TERMINATE DRAIN LINE IN HUB DRAIN BY NEAREST SINK TAILPIECE OR INDIRECT AT NEAREST FLOOR DRAIN 7 ECONOMIZER EXEMPT PER 2015 SEC C403.3.3 EXCEPTION 3 (UNIT IS 64% MINIMUM HIGHER EFFICIENCY THAN THE 14 SEER REQUIREMENT IN TABLE C403.2.3(lA)) 8 FOR TRADE COORDINATION REFER TO APPROVED EQUIPMENT SUBMITTALS 9 INSTALL PER MANUFACTURER RECOMMENDATION 10 FIELD COORDINATE EXACT UNIT LOCATION 11 UNIT UPSIZED TO MEET REFRIGERANT LINE LENGTH REQUIREMENTS FAN SCHEDULE LAST UPDATED: 04/10/17 UNIT TAG LOCATION AREA SERVED BASIS OF DESIGN TYPE MOUNTING LOCATION' MAX CFM MIN CFM ESP IN WG MOTOR VFD SYSTEM DAMPER ELECT V/PH SOUND (SONES) WEIGHT LBS REMARKS BHP HP/W EF-01 CEILING TECH TOILETS/LOCKER GHECK SQ-80-VG INLINE PLENUM 330 - 0.25 0.04 1/10 ECM MOTORIZED 115/1 7 49 1,2,3,10,12,13,14,18 EFR-02 ROOF OFFICE TOILETS/CAFE GHECK AE-12-433-A4 ROOF CAP CURB 520 - 0.25 0.11 1/4 ECM MOTORIZED 115/1 12 42 1,2,3,9,10,12,13,14,17,18 EFR-03 ROOF PVT. RESTROOMS GHECK G-070-D ROOF CAP CURB 190 - 0.25 0.02 1/30 MOTORIZED 115/1 3 20 1,2,3,9,12,13,14,17,18 EFR-04 ROOF 2ND FLOOR OFFICE GHECK AE-10-420-A8 ROOF CAP CURB 280 - 0.25 0.03 1/20 MOTORIZED 115/1 6 25 1,2,3,9,12,13,14,17,18 EFR-05 ROOF SERVICE G'HECK CUBE-420 ROOF CAP CURB 16,000 1,100 0.50 3.50 5.0 VFD MOTORIZED 480/3 15 130 1,2,3,4,6,9,12,13,14,15,16 EF-06 CEILING ELECTRICAL RM. G'HECK SQ-95-VG INLINE PLENUM 600 - 0.25 0.07 1/6 ECM MOTORIZED 115/1 7 49 1,2,10,11,12,13,14 EF-07 CEILING N.EW CAR DELIVERY GHECK SQ-100-VG INLINE PLENUM 1,050 75 0.25 0.13 1/4 ECM MOTORIZED 115/1 8 47 1,2,4,6,10,12,13,14,15,16 EF-08 CEILING OIL SUPPLY ROOM GHECK SQ-80-VG INLINE PLENUM 330 - 0.25 0.04 1/10 ECM MOTORIZED 115/1 7 49 1,2,3,8110,12,13,14 EF-09 ROOF MECH ROOM G'HECK CW141-VG SIDEWALL WALL_ 1,800 0.25 0.25 1/2 ECM MOTORIZED 115/1 11 66 1, 10,11,12,13,14 SF-01 CEILING TECH AREAOSASUPPLY GHECK CSP-A200 INLINE PLENUM 190 0.25 - 51.3 W MOTORIZED 115/1 1 49 1,2,3,12,13,14 SF-02 CEILING T ECH AREA OSA SU PPLY G'HECK CSP-A200 INLINE PLENUM 195 0.25 51.3 W MOTORIZED 115/1 1 49 1,2,3,12,13,14 GENERAL ALL TRADES TO CONFIRM EQUIPMENT REQUIREMENTS (ELECTRICAL, WEIGHT, SIZE, ETC ... ) WITH APPROVED SUBMITTALS PRIOR TO INSTALLATION; FIELD COORDINATE FINAL LOCATION & INSTALL PER MANUFACTURERS REQUIREMENTS REMARKS: 1 ELECTRICAL CONTRACTOR TO PROVIDE SCCR PROTECTION FOR EQUIPMENT AS REQUIRED BY NATIONAL ELECTRICAL CODE. MANUFACTURER TO PROVIDE SCCR LISTING (5 KAIC MINIMUM) INSIDE CONTROL PANEL AS REQUIRED BY NATIONAL ELECTRICAL CODE. 2 ELECTRICAL DISCONNECT AND MOTOR STARTER (AS REQUIRED) BY ELECTRICAL CONTRACTOR 3 FAN TO OPERATE DURING BUILDING OCCUPIED HOURS THROUGH TIMER BY CONTROLS CONTRACTOR 4 CONTROLLED BY CO AND NO2 SENSORS THROUGHOUT GARAGE FOR INTERMITTENT STOP/START AND AIRFLOW CONTROL (0.05 CFMISF MIN). USE MIN CFM FOR CONTINUOUS OPERATION OF THESE FANS AND THE MAX CFM (0.75 CFIVVSF) WHEN ACTIVATED BY SENSOR, 5 RESERVED 6 MOTORIZED DAMPER (LINE VOLTAGE, INTERLOCKED WITH FAN OPERATION BY ELECTRICAL CONTRACTOR) 7 BACKWARD INCLINED FAN WHEEL REQUIRED TO MINIMIZE PARTICULATE BUILDUP ON WHEEL 8 BACK DRAFT DAMPER PERMITED AS THE SPACE IS UNCONDITIONED 9 PROVIDE ROOF CURB 10 MOTOR TO BE ECM (OR 70% MINIMUM EFFICIENCY) PER ENERGY CODE C403.2.10.3 FOR MOTORS GREATER OR EQUAL TO 1/12 HIP & LESS THAN 1 HIP 11 FAN TO BE CONTROLLED BY T'STAT SET AT 80'F. 12 FOR TRADE COORDINATION REFER TO APPROVED EQUIPMENT SUBMITTALS 13 INSTALL PER MANUFACTURER RECOMMENDATION 14 FIELD COORDINATE EXACT UNIT LOCATION 15 PROVIDE MANUAL OVERIDE THAT ALLOWS THE EXHAUST TO GO TO MAXIMUM CFM WHEN ACTIVATED 16 PROVIDE WITH VARIABLE SPEED CONTROLLER MOUNTED IN MECH ROOM 17 RESTROOM EXHAUST FAN TO BE INTERCONNECTED WITH LIGHTING OCCUPANCY SENSOR AND TO RUN FOR 15 MINUTES AFTER LAST DETECTION. 18 RESTROOM EXHAUST FAN TO RUN CONTINUOUSLY DURING BUILDING OCCUPIED HOURS. HEAT PUMP SCHEDULE LAST UPDATED: 4/10/17 UNIT BASIS OF SUPPLY OSA ESP COOLING CAPACITY MBH HEATING CAPACITY MBH ELECTRICAL SOUND WEIGHT TAG LOCATION SERVES DESIGN CFM CFM IN WG TOTAL SENS SEER EER TOTAL" HSPF COP SUP. KW BHP MCA V/PH DBA LBS REMARKS HP-R01 ROOF EAST CARRIER 2,000 113 0.50 57 43 14.3 - 56 8.2 - 8.0 1.27 31 460/3 79 820 1-13 HP-R02 ROOF IST FLOOR CARRIER 4,000 425 0.50 118 88 - 11.0 116 - 3.3 9.7 1.98 51 460/3 87 1,364 1-15 HP-R03 ROOF ATRIUM CARRIER 4,000 160 0.50 118 1 88 - 11.0 116 - 1 3.3 9.7 1.98 51 1 460/3 87 1,364 1-15 HP-R04 ROOF 2ND FLOOR CARRIER 2,400 275 0.50 73 56 - 12.0 69 - 3.3 9.7 1.56 39 460/3 81 767 1-15 HP-R05 ROOF 2ND FLOOR CARRIER 2,400 170 0.50 73 56 - 12.0 69 - 3.3 9.7 1.56 39 460/3 81 767 1-15 GENERAL ALL TRADES TO CONFIRM EQUIPMENT REQUIREMENTS (ELECTRICAL, WEIGHT, SIZE, ETC ... ) WITH APPROVED SUBMITTALS PRIOR TO INSTALLATION; FIELD COORDINATE FINAL LOCATION & INSTALL PER MANUFACTURERS REQUIREMENTS GENERAL UNIT CAPACITY RATED AT 85/67 OUTSIDE AIR DESIGN TEMPERATURES 1 ELECTRICAL CONTRACTOR TO PROVIDE SCCR PROTECTION FOR EQUIPMENT AS REQUIRED BY NATIONAL ELECTRICAL CODE. MANUFACTURER TO PROVIDE SCCR LISTING (5 KAIC MINIMUM) INSIDE CONTROL PANEL AS REQUIRED BY NATIONAL ELECTRICAL CODE. 2 PROVIDE FULL ECONOMIZER (ENTHALPY) CYCLE. WITH (POWERED) RELIEF SYSTEM 3 ECONOMIZER SHALL BE CAPABLE OF PROVIDING PARTIAL COOLING IN ADDITION TO MECHANICAL COOLING AS REQUIRED TO MEET THE REMAINDER OF THE LOAD PER 2015 SEC SECTION C403.3.1.1.2. 4 MINIMUM UNIT EFFICIENCY TO MEET THE ENERGY CODE TABLE C403 5 PROVIDE WITH STAGED SUPPLEMENTAL ELECTRIC HEATER IN UNIT FOR OPERATION DURING DEFROST MODE 6 OUTSIDE AIR INDICATES MINIMUM CFM PER ASHRAE. TAB WORK MUST MEET OR EXCEED INDICATED QUANTITY. 7 PROVIDE SUPPLY & RELIEF FAN VFDS FOR VARIABLE VOLUME CAPACITY PER ENERGY CODE 8 SMOKE DETECTORS PROVIDED (BY MECHANICAL) AND INSTALLED (BY ELECTRICAL) IN THE RETURN AIR. 9 IF MULTI STORY, PROVIDE AT CONNECTION UPSTREAM OF THE RETURN AIR RISER AT EACH STORY PER SMC SECTION 606.2.3. PROVIDE WITH SPACE CO2 MONITORING AND DEMAND CONTROL VENTILATION RESET OF OUTSIDE AIR 10 PROVIDE WITH MERV 13 FILTERS 11 PROVIDE WITH ROOF CURB 12 PROVIDE WITH EXTERNAL LOW NOISE BLOWER KIT AND COMPRESSOR SOUND WRAP 13 PROVIDE STAND-ALONE DIGITAL 7-DAY THERMOSTAT 14 PROVIDE VARIABLE SPEED FAN CONTROL FOR SUPPLY FANS > 5 TONS (<66% OF DESIGN SPEED AT LOW SPEED SETTING MAXIMUM) PER ENERGY CODE C403.2.11.5 15 IF > 5 TONS & ECONOMIZER PROVIDED, UNIT TO INCLUDE TWO STAGE MIN COOLING (3 STAGE IF BETWEEN 5 & 20 TONS, 4 STAGE FOR > 20 TONS) AS DEFINED BY ENERGY CODE C403.3.1.2 SIDE WALL SUPPLY REGISTER SCHEDULE LAST UPDATED: 4/10/2017 UNIT BASIS OF MAX MIN. MAIN CORE FACE THROW TAG DESIGN CFM DUCT SIZE SIZE SIZE FT NC MOUNTING MATERIAL REMARK SR1 SHOEMAKER RS34-0 145 8 12X4 14 X6 10212,14 20 SURFACE STEELIALUMINUM 1,2,3 SR2 SHOEMAKER RS34-0 190 10 1 1OX6 12X8 12,14,16 20 SURFACE STEELIALUMINUM 1.2.3 REMARKS: 1 PROVIDE WITH RECESSED SCREWDRIVER OPERATED OPPOSED BLADE DAMPER 2 PROVIDE ALL GALVANIZED FINISH 3 PROVIDE DESIGNER COLOR, VERIFY WITH OWNER PRIOR TO ORDERING LINEAR SLOT GRILLE SCHEDULE LAST UPDATED: 1/6/16 UNIT BASIS OF NECK SIZE MAX NUMBER OF SLOT SLOT TAG DESIGN IN DIA CFM SLOTS LENGTH, IFT WIDTH, IN NC MOUNTING MATERIAL REMARKS LD6 TITUS ML-MP39 6 110 1 4 1.0 30 SURFACE STEEL 1,3,4,6,7,8 LD7 TITUS ML-MP39 8 200 2 4 1.0 30 SURFACE STEEL 1,3,4,6,7,8 LD8 TITUS ML-MP39 9 250 3 4 1.0 30 SURFACE STEEL 1,3,4,6,7,8 LD9 TITUS ML-MP39 10 350 3 4 1.0 30 SURFACE STEEL 1,3,4,6f7,8 LD10 TITUS ML-MP39 12 400 4 4 1.0 30 SURFACE STEEL 114,6,7,8f 9 LR1 TITUS ML-MP39 PLENUM 120 1 4 1.0 <20 T-BAR/SURF STEEL 2,3,5,8 LR2 TITUS ML-MP39 PLENUM 240 2 4 1.0 <20 T-BAR/SURF STEEL 2,3,5f 8 LR3 TITUS ML-MP39 PLENUM 360 3 4 1.0 <20 T-BAR/SURFj STEEL 2f 3,5f 8 LR4 TITUS ML-MP39 PLENUM 1 480 4 4 1 1.0 1 <20 IT-BAR/SURFI STEEL 1 2,3,5,8 GENERAL ALL TRADES TO CONFIRM EQUIPMENT REQUIREMENTS (ELECTRICAL, WEIGHT, SIZE, ETC .. WITH APPROVED SUBMITTALS PRIOR TO INSTALLATION; FIELD COORDINATE FINAL LOCATION &INSTALL PER MANUFACTURERS REQUIREMENTS NOTE: FOR CONTINUOUS LINEAR INSTALLATIONS, PROVIDE BLANK OFF PLATES BETWEEN SUPPLY AND RETURN SECTIONS I RUN OUT SIZE SAME SIZE AS NECK PERIPHERY SIZE 2 PROVIDE MANUFACTURER'S SHEET METAL BOOT 3 CUSTOM FINISH AS REQUIRED BY ARCHITECT TO BE BLACK, ANODIZED ALUMINUM, OR BRUSHED ALUMINUM. SUBMIT COLOR TO ARCHITECT FOR APPROVAL. 4 SEE DWG FOR THROW PATTERN DESIRED 5 PROVIDE LAY -IN TYPE FRAME 6 PROVIDE URFACE M LINT TYPE FRAME WITH REW FA ENIN 7 FOR LINEAR INSTALLATIONS, PROVIDE SUPPLY INLET PLENUM THAT MATCHES LENGTH OF LINEAR GRILLE, PLENUM TO BE DONCO DIP WITH HEMMED RAIL (AND 1" SOUNDLINING IF SPACE:!� NC-35 OR SAT < 550F) 8 WHERE VOLUME DAMPERS ARE NOT ACCESSIBLE, PROVIDE HAND HOLE ACCESS OR YOUNGS REGULATOR WITH CEILING PLATE OR DURODYNE CABLE OPERATED DAMPER WITH CABLE ROUTED INSIDE DUCT & ADJUSTMENT THROUGH GRILLE FACE 9 COLOR TO BE WHITE FOR LD10 LOCATED IN WOODEN CEILINGS ELECTRIC CABINET HEATER SCHEDULE LAST UPDATED: 04/03/17 UNIT TAG LOCATION AREA SERVED BASIS OF DESIGN WATTS CFM EAT OF LAT OF ELEC WEIGHT LBS REMARKS FLA V/PH ECH-1 LEVEL 1 SPRINKLER RISER KING PAW1215-U 500 75 45 65 8.4 120/1 9.5 1-4 ECH-2 LEVEL 1 VESTIBULE KING PAW1215-U 500 75 45 65 8.4 120/1 9.5 1-4 ECH-3 LEVEL 1 VESTIBULE KING PAW1215-U 500 75 45 65 8.4 120/1 9.5 1-4 ECH-4 LEVEL 1 TECH RESTROOM KING PAW1215-U 500 75 45 65 8.4 1 120/1 9.5 1-4 ECH-5 LEVEL 1 TECH RESTROOM KING PAW1215-U 500 75 45 65 8.4 1 120/1 9.5 1-4 ECH-6 LEVEL 1 TECH LOCKER RM KING PAW121r,-H rnO 7 5 45 6 S 8 4-T 1 -?n/ 1 9.5 1-4 REMARKS: 1 ELECTRICAL CONTRACTOR TO PROVIDE SCCR PROTECTION FOR EQUIPMENT AS REQUIRED BY NATIONAL ELECTRICAL CODE. MANUFACTURER TO PROVIDE SCCR LISTING (5 KAIC MINIMUM) INSIDE CONTROL PANEL AS REQUIRED BY NATIONAL ELECTRICAL CODE. 2 DISCONNECT AS REQUIRED BY ELECTRICAL CONTRACTOR 3 RECESSED WALL MOUNTED UNIT 4 UL APPROVED. PROVIDE WITH: FAN FORCED AIRFLOW, RECESSED CAN, INTERNAL T'STAT MODULAR DIFFUSER SCHEDULE LAST UPDATED: 03/21/16 BASIS OF DESIGN NECK SIZE INDIA REMARKS: 1 RUN OUT SIZE SAME SIZE AS DIFFUSER NECK SIZE, U.N.O. ON DWGS. 2 ALL DIFFUSERS TO HAVE SIDE INLET SHEET METAL CAN PLENUM IF < 1.5 DIA STRAIGHT FLEX AVAILABLE FOR TOP INLET 3 ECCO MFG DIFFUSER CAN TO HAVE PERFORATED INTERIOR PLATE (AND 1" SOUNDLINING IF SPACE <- NC-30 OR SAT < 550F) 4 STANDARD WHITE POWDER COAT 5 PROVIDE FRAME 3P, LAY -IN TYPE. 6 PROVIDE SURFACE MOUNTING FRAME MODEL TRM-S FOR GRILLE REMOVAL & INSTALLATION IN HARD LID CEILING 7 WHERE VOLUME DAMPERS ARE NOT ACCESSIBLE, PROVIDE HAND HOLE ACCESS OR YOUNGS REGULATOR WITH CEILING PLATE OR DURODYNE CABLE OPERATED DAMPER WITH CABLE ROUTED INSIDE DUCT & ADJUSTMENT THROUGH GRILLE FACE TRANSFER / RETURN EXHAUST AIR GRILLES LAST UPDATED: 4/10/2017 UNIT TAG BASIS OF DESIGN MAX CFM NECK SIZE IN DIA MOUNTING FACE SIZE MATERIAL REMARKS EC1 TITUS 5OF-8 500 T-BAR 24 x 12 ALUMINUM 2,9 EC2 TITUS 5OF-8 1,000 T-BAR 24 x 24 ALUMINUM 2,9 G9 TITUS 35ORL AG-15 150 8 GWB 8 x 8 STEEL 1, 3, 6, 7/8, 9, 12 G10 TITUS 35ORL AG-15 250 10 GWB 10 X 10 STEEL 1, 3, 6, 7/8, 9, 12 G11 TITUS 35ORL AG-15 375 12 GWB 12 x 12 STEEL 1, 3, 6, 7/8, 9, 12 G12 TITUS 35ORL AG-15 525 14 GWB 14 x 14 STEEL 1, 3, 6, 7/8, 9, 12 T1 TITUS 35ORL 150 GWB 8 x 8 STEEL 3,7/8,9,12 T2 TITUS 35ORL 250 GWB 10 X 10 STEEL 3,7/8,9,12 T3 TITUS 35ORL 375 GWB 12 x 12 STEEL 3,7/8,9,12 T4 TITUS 35ORL 525 GWB 18 x 12 STEEL 3,7/8,9,12 1 RUNOUT SAME AS DWG NECK SIZE U.N.O. ON DWG 2 CORE ONLY - LAY -IN 3 SURFACE MOUNT FRAME 4 CHANNEL FRAME - LAY -IN 5 T-BAR LAY -IN 6 PROVIDE OPPOSED BLADE DAMPER (OBD) 7 PROVIDE DUCTBOARD PLENUM 8 PROVIDE SHEETMETAL PLENUM 9 STANDARD #26 WHITE FINISH 10 PROVIDE ALUMINUM GRILLES IN SHOWERS/HUMID AREAS 11 ALL NON-FERROUS MATERIALS IN MRI ROOMS 10SUE 12 WHERE VOLUME DAMPERS ARE NOT ACCESSIBLE, PROVIDE HAND HOLE ACCESS OR YOUNGS REGULATOR WITH CEILING IQ PLATE OR DURODYNE CABLE OPERATED DAMPER WITH CABLE ROUTED INSIDE DUCT & ADJUSTMENT THROUGH GRILLE FACE Her,manson Building Today, Defining Tomorrow Hermanson Company LUP 1221 2nd Avenue North Kent, Washington 98032 Tel: (206) 575-9700 Fax: (206) 575-9800 www.hermanson.com Contractor Reg #: HERMACLO05BJ M.AG I C TOYOTA OFEDMONDS 21300 HIGHWAY 99 EDMONDS, WA 98026 0'a WODOR+ 0 'o 36149 L Revisions 04/12/17 JMH ISSUE FOR PERMIT A 03/31/17 JMH COORD SET REV3- A03/24/17 JMH COORD SET REV2 A 03/17/17 JMH COORD SET REV1- 03/02/17 JMH DID SET No. Date By Description Design Team Design JMH Drawn FVP Checked DTN Project Number 11-17-10152 Issue Date 04/12/17 SCHEDULESHEET -HVAC M0001 1. BUILDING OPERATIONS: THE BUILDING IS CONTROLLED BY STAND ALONE SYSTEMS THAT EACH HAVE CONTROLLERS AND TIMERS CONNECTED TO EACHITEM. 1.1. GENERAL- BUILDING OCCUPANCY SCHEDULE 1.1.1. OFFICE 1.1.1.1. OCCUPIED HOURS ARE MONDAY THRU FRIDAY 5:00 AM UNTIL 10-00 PM (ADJ.) SATURDAY 5-00 AM UNTIL 6:00 PM (ADJ.) SUNDAY 5:00 AM UNTIL 2-00 PM (ADJ.) 1.1.1.2. UNOCCUPIED HOURS ARE MONDAY THRU FRIDAY 10:00 PM 5-00 AM UNTIL (ADJ.) SATURDAY 6:00 PM UNTIL 5-00 AM (ADJ.) SUNDAY 2-00 PM UNTIL 5-00 AM (ADJ.) 1.1.2. SHOP 1.1.2.1. OCCUPIED HOURS ARE MONDAY THRU FRIDAY 6-00 AM UNTIL 10:00 PM (ADJ.) SATURDAY 6-00 AM UNTIL 2:00 PM (ADJ.) SUNDAY UNOCCUPIED (ADJ.) 1.1.2.2. UNOCCUPIED HOURS ARE MONDAY THRU FRIDAY 10:00 PM UNTIL 6:00 AM (ADJ.) SATURDAY 2-00 PM UNTIL 6:00 AM (ADJ.) SUNDAY UNOCCUPIED (ADJ.) 2. BUILDING SUPPLY AND EXHAUST FAN SYSTEMS AND INTAKE HOODS 2. 1. SERVICE BAY FAN (EFR-05 & EF-07) ARE CONTROLLED BY TIMER (EFR-05 ONLY), HAND AUTO SWITCHES, AND CO & NO2 SENSORS TO MAINTAIN A SAFE WORKING ENVIRONMENT AND PROVIDE VENTILATION AS NEEDED. 2.1.1. SHOP OCCUPIED MODE: FANS RUN AT LOW SPEED WITH MOTORIZED DAMPER FULLY OPEN. 2.1.2. SHOP UNOCCUPIED MODE: FANS RUN UNTIL THE CARBON MONOXIDE LEVEL FALLS BELOW 30 PPM AND NO2 LEVEL FALLS BELOW 5PPM THEN STOP EXHAUST FANS AND CLOSE MOTORIZED DAMPER. 2.1.3. OVERIDE- WHEN HAND AUTO SWITCH IS PLACED IN HAND THE EXHAUST FANS RUN IN HIGH SPEED AND MOTORIZED DAMPER OPENS UNTIL SWITCH DEACTIVATED 2.1.4. CO & NO2 OVERIDE: THE EXHAUST FANS RUN IN HIGH SPEED WHEN THE CO LEVEL EXCEEDS 50 PPM OR NO2 LEVELS EXCEED 5PPM AND RETURNS TO LOW SPEED AT LESS THAN 45 PPM(CO) AND 2PPM(NO2). 2.9. COOLING AND HEATING UNITS 2.9.1. ROOFTOP UNITS HP-1 THRU HP-5 ARE ROOFTOP MOUNTED PACKAGED HEAT PUMP UNITS CONTROLLED BY 7-DAY PROGRAMMABLE THERMOSTATS CU-3, CU-4, AND CU-5 AND IU-03, IU-04, AND IU-05) ARE SPLIT SYSTEM HEAT PUMPS CONTROLLED BY INDEPENDENT LINE VOLTAGE THERMOSTATS 2.9.1.1. OFFICE UNOCCUPIED MODE: WHEN THE THERMOSTAT INITIATES THE UNOCCUPIED MODE, THE UNIT WILL SHUT DOWN WITH THE OUTSIDE AIR DAMPERS IN THE CLOSED POSITION. THE UNIT WILL ASSUME THE UNOCCUPIED HEATING AND COOLING SET POINTS. IF THE UNOCCUPIED SET POINTS ARE EXCEEDED, THE FAN WILL COME ON, AND THE UNIT WILL HEAT OR COOL UNTIL THE SPACE TEMPERATURE IS WITHIN THE UNOCCUPIED SET POINTS (55-F HEATING, 85-F COOLING ADJ). 2.9.1.2. OFFICE UNOCCUPIED SETBACK TEMPERATURE CONTROL: DURING UNOCCUPIED HOURS, THE UNIT WILL BE CONTROLLED BY A STAND-ALONE THERMOSTAT TO MAINTAIN USER -DEFINED UNOCCUPIED HEATING AND COOLING SET POINTS (55-F HEATING, 85-F COOLING ADJ). THE FAN WILL CYCLE AS REQUIRED TO MAINTAIN THE SET POINTS. 2.9.1.3. OCCUPIED OPERATION: WHEN THE UNIT IS CONTROLLED TO THE OCCUPIED MODE, ALL ROOFTOP UNIT FUNCTIONS WILL BE ENABLED. THE UNIT WILL OPERATE IN SUPPLY AIR TEMPERATURE MODE TO SATISFY THE ROOM TEMPERATURE OCCUPIED SET POINTS (70-F HEATING, 75-F COOLING ADJ). THE ROOFTOP UNIT WILL DEFAULT TO THIS MODE IN THE EVENT THAT COMMUNICATION WITH THE THERMOSTAT IS LOST. 2.9.1.4. COOLING/ECONOMIZER: DURING THE OCCUPIED COOLING MODE OF OPERATION THE ECONOMIZER AND MECHANICAL COOLING ARE USED TO CONTROL THE SUPPLY AIR TEMPERATURE. IF THE DRY BULB OF THE OUTSIDE AIR IS LESS THAN THE RETURN AIR, THE ECONOMIZER WILL BE USED TO SATISFY THE SUPPLY AIR SET POINT (75-F ADJ). IF MORE COOLING IS THEN REQUIRED, MECHANICAL COOLING WILL BE STAGED ON AS NECESSARY. MINIMUM ON/OFF TIMING OF THE MECHANICAL COOLING WILL PREVENT RAPID CYCLING. 2.9.1.5. AT OUTDOOR AIR CONDITIONS ABOVE THE DRY BULB CONTROL SETTING, MECHANICAL COOLING ONLY WILL BE USED AND THE OUTSIDE AIR DAMPERS WILL REMAIN AT MINIMUM POSITION. 2.2. RESTROOM FANS (EFR-02, EFR-03, AND EFR-04) ARE CONTROLLED BY THE LIGHTING OCCUPANCY SENSOR AND TIMER 2.2.1. FANS ARE TO BE CONTROLLED BY THE LIGHTING OCCUPANCY SENSOR AND TIMER PROVIDED AND INSTALLED BY ELECTRICAL CONTRACTOR 2.2.2. FANS ARE ENERGIZED UPON DETECTION OF OCCUPANCY. 2.2.3. FANS ARE TO RUN FOR 15 MINUTES AFTER LAST DETECTION 2.3. TECH & LOCKER ROOM FAN (EF-01) OPERATES CONTINUOUSLY DURING SHOP OCCUPIED HOURS AND IS CONTROLLED BY A TIMER SET TO THE BUILDING SHOP OCCUPIED HOURS SCHEDULE. 2.3.1. FAN IS ENERGIZED DURING OFFICE OCCUPIED HOURS (ADJ) 2.3.2. FAN IS OFF DURING OFFICE UNOCCUPIED HOURS (ADJ) 2.4. TEMPERATURE CONTROLLED EXHAUST FANS (EF-06 & 09) ARE CONTROLLED BY WALL MOUNTED LINE VOLTAGE THERMOSTAT THAT PROVIDES 24/7 MONITORING 2.4.1. TEMPERATURE CONTROLLED EXHAUST FANS ARE STARTED BY THERMOSTATS PROVIDED BY THE MECHANICAL CONTRACTOR AND INSTALLED BY THE ELECTRICAL CONTRACTOR 2.4.2. EXHAUST FAN TO ACTIVATE AT 80OF SET POINT (ADJ). 2.5. OSA INTAKE THE OPERATION OF THE MOTORIZED DAMPER AT THE OSA INTAKE IS INTERLOCKED WITH THE OPERATION OF THE SERVICE BAY EXHAUST FANS. DAMPER IS TO OPEN WHEN FAN IS IN OPERATION AND CLOSED WHEN EXHAUST FAN IS OFF 2.5.1. INTAKE MOTORIZED DAMPER TO BE INTERLOCKED WITH EXHAUST FAN. 2.5.2. EXHAUST FAN IS ON INTAKE HOOD DAMPER TO FULLY OPEN 2.5.3. EXHAUST FAN IS OFF INTAKE HOOD DAMPER IS CLOSED 2.6. TECH SUPPORT SUPPLY FAN (SF-01 AND SF-02) IS CONTROLLED BY A TIMER SET TO THE SHOP SCHEDULE. 2.6.1 MOTORIZED DAMPER TO BE INTERLOCKED WITH SUPPLY FAN TO OPEN WHILE FAN IS ON AND TO CLOSE WHILE FAN IS OFF. 2.9.1.6. TIMED OVERRIDE- WHEN THE USER INITIATES A TIMED OVERRIDE, THE ROOFTOP UNIT WILL RETURN TO ITS NORMAL OCCUPIED MODE FOR A PERIOD OF TIME AS SPECIFIED AT THE THERMOSTAT. WHEN THE TIMED OVERRIDE PERIOD HAS ENDED, THE UNIT WILL AUTOMATICALLY RETURN TO ITS UNOCCUPIED CYCLE. THE THERMOSTAT WILL MONITOR AND STORE THE OVERRIDE TIME FOR ALL TIMED OVERRIDE INPUTS FOR DOCUMENTATION OF AFTER-HOURS OPERATION. THE THERMOSTAT WILL ALSO RECOGNIZE A TIMED OVERRIDE FUNCTION. 2.9.1.7. SUPPLY FAN CONTROL- THE SUPPLY FAN WILL OPERATE CONTINUOUSLY IN A CONSTANT VOLUME MODE DURING THE OCCUPIED OR TIMED OVERRIDE MODE EXCEPT WHEN MANUALLY SHUT DOWN. 2.9.2. HEATING MODE: 2.9.2.1. IN OCCUPIED MODE, THE UNIT WILL RUN CONTINUOUSLY TO MAINTAIN COMFORT CONDITIONS. THE ECONOMIZER WILL BE AT MINIMUM POSITION, THE RETURN AIR DAMPERS WILL BE FULLY OPEN, AND THE HEATING COIL WILL PROVIDE HEATING TO MAINTAIN ROOM AIR SET POINT (70OF HEATING ADJ). 2.9.2.2. IN UNOCCUPIED MODE, THE OUTSIDE AIR DAMPERS WILL BE CLOSED AND THE RETURN AIR DAMPERS OPEN. THE AC UNIT CONTROLS THE GAS HEATING COIL TO MAINTAIN UNOCCUPIED MODE SET POINT UNTIL UNOCCUPIED MODE SET POINT IS REACHED (55-F HEATING ADJ), THEN HP UNIT WILL BE DE - ENERGIZED. 2.7. ELECTRIC CABINET HEATERS 2.7.1. RISER ROOM (ECH-1) HEATER IS CONTROLLED BY FIXED TEMP BULLET SENSORS SET TO ENERGIZE HEATING AT 45-F (ADJ). 2.7.2. VESTIBULES (ECH-2 AND ECH-3) HEATERS ARE CONTROLLED BY FIXED TEMP BULLET SENSORS SET TO ENERGIZE HEATING AT 60-F (ADJ). 2.7.3. OTHER LOCATIONS (ECH-4, 5, & 6) HEATERS ARE CONTROLLED BY FIXED TEMP BULLET SENSORS SET TO ENERGIZE HEATING AT 60-F (ADJ). 2.8. SPLIT SYSTEM 24/7 UNITS 2.8.1. (CU-1 AND CU-2 AND IU-101 AND IU-102) ARE COOLING ONLY UNITS CONTROLLED BY INDEPENDENT LINE VOLTAGE THERMOSTATS. 2.8.1.1. SPLIT SYSTEM AIR CONDITIONING TO PROVIDE 24/7 OPERATION. 2.8.1.2. THE UNIT TO PROVIDE COOLING WHEN THE TEMPERATURE IN THE SPACE EXCEEDS SET POINT OF 750F (ADJ) Hermanson Building Today, Defining Tomorrow Hermanson Company LLP 1221 2nd Avenue North Kent, Washington 98032 Tel: (206) 575-9700 Fax: (206) 575-9800 www.hermanson.com Contractor Reg #: HERMACLO05BJ M.AG I C TOYOTA OFEDMONDS 21300 HIGHWAY 99 EDMONDS, WA 98026 '4 1�,ODO WAS,6�- 0�1 36149 L Revisions 04/12/17 JMH ISSUE FOR PERMIT 03/31/17 JMH COORD SET REV3_ 03/24/17 JMH COORD SET REV2 03/17/17 JMH COORD SET REV1_ 03/02/17 JMH DID SET No. Date By Description Design Team Design JMH Drawn FVP Checked DTN Project Number 11-17-10152 Issue Date 04/12/17 SEQUENCE OF OPERATION - HVAC MOmO2 F"d iiiii 1 0 RIM N i It= 3. HYDRONICS SYSTEMS 3.1. BOILERS (EB-01 AND EB-02) BOILERS TO BE SEQUENCED WITH THE COGEN HEAT RECOVERY ACTING AS THE PRIMARY HEAT SOURCE AND THE TWO BOILERS AUTOMATICALLY SEQUENCING, EACH HAVING 7 STAGES, TO STAGE ON AS REQUIRED TO MEET HEATING LOAD. 3.2. EACH ZONE IS CONTROLLED FROM A SPACE TEMPERATURE SENSOR AND AN EMBEDDED FLOOR (SLAB) SENSOR. WHEN THE OUTSIDE AIR TEMPERATURE IS LESS THAN 65-F (ADJ) SYSTEM ACTIVATES RADIANT FLOOR HEATING SYSTEM WHICH IS TO MAINTAIN SLAB TEMPERATURE AT 80-F (ADJ). IF THE SPACE TEMPERATURE FALLS BELOW SET POINT 70OF OCCUPIED 60OF UNOCCUPIED (ADJ) THEN THE SLAB TEMPERATURE SET POINT IS INCREASED 20F EVERY 30 MINUTES (ADJ) TO A MAXIMUM OF 840F (ADJ). WHEN SPACE TEMPERATURE REACHES SET POINT, SLAB TEMPERATURE IS RESET TO 800F. ON A CALL FOR ZONE HEATING FROM ZONE SENSORS, THE ASSOCIATED MANIFOLD ZONE VALVES ARE ENERGIZED TO OPEN AND CIRC PUMP TO RUN, THE HOT WATER CIRCULATING PUMP PP-01 OR PP-02 IS STARTED AND THE ELECTRIC BOILER SYSTEM IS ENABLED. THE END SWITCHES IN ZONE VALVES PROVIDE FEEDBACK INDICATION WHEN A VALVE IS OPEN. THE BOILER WILL NOT OPERATE WITHOUT FLOW BEING PROVEN BY A FLOW SWITCH. WHEN THERE IS NO LONGER A NEED FOR HEATING, THE BOILER AND PUMP ARE STOPPED AND THE ZONE VALVES ARE CLOSED. SHOULD THE SUPPLY WATER TEMPERATURE AT ANY OF THE MANIFOLDS EXCEED 11 40F (ADJ), THE BOILER IS DISABLED AND AN ALARM WILL SOUND. THE PUMP CONTINUES TO RUN AND THE ZONE VALVES REMAIN OPEN. WHEN THE SUPPLY WATER TEMPERATURE DROPS TO 950F (ADJ), THE BOILER IS RE -ENABLED. 3.3. SNOW MELT SYSTEM AT RAMPS 3.3.1. SNOW MELT MANIFOLDS ARE TO BE PROGRAMED TO SHUT OFF WHEN PAVEMENT TEMPERATURE EXCEEDS 50OF AND NO PRECIPITATION IS FALLING AND THE OUTDOOR AIR TEMPERATURE EXCEEDS 400F. NOTE: MANIFOLDS ARE PROVIDED WITH PRESSURE DIFFERENTIAL BYPASS VALVES, PRESET TO EXCESS WATER WHEN ZONE VALVES ARE CLOSED. SET UP THESE VALVES IS BY MECHANICAL CONTRACTOR. 4. PLUMBING 4.1.1. HOTWATER CIRCULATOR PUMP WILL BE INTERLOCKED WITH AN ADJUSTABLE 2417 WALL MOUNTED TIMER AND SET TO COME ON ONE HOUR BEFORE (ADJ) OFFICE OCCUPANCY. UPON RECEIVING AN (ON) SIGNAL FROM TIMER PUMP MOTOR WILL ENERGIZE AND OPERATE CONTINUOUSLY DURING OCCUPIED MODE. UPON RECEIVING AN UNOCCUPIED (OFF) SIGNAL FROM TIMER PUMP MOTOR WILL DE -ENERGIZE AND PUMP WILL REMAIN OFF IN UNOCCUPIED MODE. 4.1.2. PUMP AND TIMER WILL BE PROVIDED AND INSTALLED BY MECHANICAL CONTRACTOR. 4.1.3. POWER WIRING TO PUMP MOTOR, LINE VOLTAGE INTERLOCK WIRING AND WALL MOUNTING OF TIMER WILL BE PROVIDED AND INSTALLED BY THE ELECTRICAL CONTRACTOR. Her,manson Building Today, Defining Tomorrow Hermanson Company LLP 1221 2nd Avenue North Kent, Washington 98032 Tel: (206) 575-9700 Fax: (206) 575-9800 www.hermanson.com Contractor Reg #: HERMACLO05BJ MAGIC TOYOTA OFEDMONDS 21300 HIGHWAY 99 EDMONDS, WA 98026 toDo WAS 36149 L Revisions 04/12/17 JMH ISSUE FOR PERMIT 03/31/17 JMH COORD SET REV3_ 03/24/17 JMH COORD SET REV2 03/17/17 JMH COORD SET REV1_ 03/02/17 JMH DID SET No. Date By Description Design Team Design JMH Drawn FVP Checked DTN Project Number 11-17-10152 Issue Date 04/12/17 SEQUENCE OF OPERATION - HVAC MOmO3 164 S06111 a I N :3 ELECTRIC WATER BOILER LAST UPDATED: 02/17/17 UNIT TAG LOCATION AREA SERVED BASIS OF DESIGN KW EWT OF LWT OF GPM ELECTRICAL WEIGHT LBS REMARKS FLA I V/PH EB-01 MECH RM HYDRONICS LOC'VAR BWX3-210C 210 115 130 72 460/3 1,100 1-5 EB-02 �4-+ MECH RM I HYDRONICS ILOC'VAR BWX3-210C 210 115 130 72 460/31 1,100 1-5 I I I GENERAL ALL TRADES TO CONFIRM EQUIPMENT REQUIREMENTS (ELECTRICAL, WEIGHT, SIZE, ETC ... ) WITH APPROVED SUBMITTALS PRIOR TO INSTALLATION; FIELD COORDINATE FINAL LOCATION &INSTALL PER MANUFACTURERS REQUIREMENTS 1 ELECTRICAL CONTRACTOR TO PROVIDE SCCR PROTECTION FOR EQUIPMENT AS REQUIRED BY NATIONAL ELECTRICAL CODE. MANUFACTURER TO PROVIDE SCCR LISTING (5 KAIC MINIMUM) INSIDE CONTROL PANEL AS REQUIRED BY NATIONAL ELECTRICAL CODE. 2 DISCONNECT AS REQUIRED BY ELECTRICAL CONTRACTOR 3 REMOTE WALL MOUNTED EMERGENCY SHUTOFF FOR CSD-1 COMPLIANCE PROVIDED BY MECHANICAL, INSTALLED BY ELECTRICAL IF BOILER EXCEEDS WASHINGTON STATE @ 117 KWf 2100F, 120 GALLONS STORAGE NOTE: BOILER PRESSURE VESSLE PERMIT REQUIRED, PLEASE NOTE ON DRAWINGS IN MECHANICAL ROOM 4 UL LABELED. PROVIDE WITH MANUAL PROBE LOW WATER CUT OUT, FLOW SWITCH, ON/OFF CONTROL VIA LOCAL/REMOTE SWITCH FOR NEW DDC CONTROL SYSTEM 5 IF MULTIPLE BOILERS ARE INSTALLED, PROVIDE ISOLATION VALVES TO ISOLATE FLOW THROUGH INACTIVE BOILERS (BY CC) HYDRONIC PUMP SCHEDULE LAST UPDATED 04/03/17 UNIT TAG LOCATION AREA SERVED BASIS OF DESIGN TYPE GPM OPER. HEAD FT H20 MAX PRESS. (PSI) ELECTRICAL WEIGHT LBS REMARKS RPM BHP HP V/PH PP-01 MECH ROOM CLSD LOOP B&G e-80 1823M A5 IN -LINE 170 44.0 175.0 1,750 2.52 3 460/3 185 1-8 PP-02 MECH ROOM CLSD LOOP B&G e-80 1823M A5 IN -LINE 170 44.0 175.0 1,750 2.52 3 460/3 1 185 1-8 CP-01 SERVICE BAY SM A1-2 B&G PL 55 IN -LINE 28 21.9 150.0 3,250 2/5 115/1 13 1,2,3,4,5 CP-02 SERVICE BAY SM B 1-2 B&G PL 36 IN -LINE 24 18.6 150.0 3,250 1/6 115/1 13 1,2,3,4,5 CP-03 SERVICE BAY SM C1-2 B&G PL 55 IN -LINE 26 29.5 150.0 3,250 2/5 115/1 13 1,2,3,4,5 CP-04 SERVICE BAY SM D1-2 B&G PL 55 IN -LINE 24 21.6 150.0 3,250 2/5 115/1 13 1,2,3,4,5 CP-05 CORRIDOR SM E B&G PL 30 IN -LINE 7 14.4 150.0 3,300 1/12 115/1 12 1,2,3,4,5 CP-06 SERVICE BAY RM 1A&B B&G PL 55 IN -LINE 23 26.3 150.0 3,250 2/5 115/1 13 1,2,3,4,5 CP-07 SERVICE BAY RMP2 B&G PL 55 IN -LINE 28 21.7 150.0 3,250 2/5 115/1 13 1,2,3,4,5 CP-08 SERVICE BAY SM A3 B&G PL 30 IN -LINE 6 15.1 150.0 3,250 1/12 115/1 12 1,2,3,4,5 CP-09 SERVICE BAY SM C3 B&G PL 30 IN -LINE 4 7.3 150.0 3,250 1/12 115/1 12 1,2,3,4,5 HXP-01 MECH ROOM HEAT XCHNGR B&G e-80 1453M IN -LINE 30 25.0 175.0 1,200 0.38 3/4 460/3 68 1,2,3,5 BP-01 MECH ROOM BOILER 1 B&G e-80 1453M IN -LINE 70 20.0 175.0 1,800 0.48 3/4 460/3 68 1,2,3,5 BP-02 MECH ROOM BOILER 2 B&G e-80 1453M IN -LINE 70 20.0 175.0 1,800 0.48 3/4 460/3 68 1,2,3,5 ACCEPTABLEALTERNATE.5.- H&G, GRWPFQS� TACO I I I GENERAL ALL TRADES TO CONFIRM EQUIPMENT REQUIREMENTS (ELECTRICAL, WEIGHT, SIZE, ETC ... ) WITH APPROVED SUBMITTALS PRIOR TO INSTALLATION; FIELD COORDINATE FINAL LOCATION & INSTALL PER MANUFACTURERS REQUIREMENTS 1 ELECTRICAL CONTRACTOR TO PROVIDE SCCR PROTECTION FOR EQUIPMENT AS REQUIRED BY NATIONAL ELECTRICAL CODE. MANUFACTURER TO PROVIDE SCCR LISTING (5 KAIC MINIMUM) INSIDE CONTROL PANEL AS REQUIRED BY NATIONAL ELECTRICAL CODE. 2 DISCONNECT AND MOTOR STARTED BY ELECTRICAL CONTRACTOR 3 PROVIDE WITH P&T TAPS, DP GAUGE ACROSS PUMP 4 PROVIDE WITH WALL MOUNT, VIBRATION ISOLATION, MOUNT 8A.F.F. 5 WATER LOOP CONTAINS 30% PROPYLENE GLYCOL FOR FREEZE PROTECTION 6 VARIABLE FREQUENCY DRIVE WITH INTEGRAL DISCONNECT IN COMPLIANCE WITH SEC SECTION 403.2.12 (PROVIDED WITH PUMP ASSEMBLY) 7 PUMP TO BE MOUNTED IN A STACKED CONFIGURATION AND PROVIDED WITH FLEX CONNECTIONS TO PIPES 8 PUMPS TO BE CONTROLLED THROUGH DIFFERENTIAL PRESSURE SWITCHES AND RAMP UP OR DOWN TO MAINTAIN SYSTEM PRESSURE. rr""LATE AND FRAME HEAT EXC"HANG"ER SCHEDULE LAST UPDATED: 03/23/17 BASIS OF DESIGN CAPACITY MBH CLOSED WATER SIDE OPEN WATER SIDE GENERAL ALL TRADES TO CONFIRM EQUIPMENT REQUIREMENTS (ELECTRICAL, WEIGHT, SIZE, ETC...) WITH APPROVED SUBMITTALS PRIOR TO INSTALLATION; FIELD COORDINATE FINAL LOCATION & INSTALL PER MANUFACTURERS REQUIREMENTS 1 0% PROPYLENE GLYCOL ON CLOSED LOOP 2 PROVIDE WITH 150 PSI CONSTRUCTION, 316 SS PLATES, NITRILE GASKETS 3 AHRI LISTED TO COMPLY WITH ENERGY CODE REQUIREMENTS EXPANSION TANK SCHEDULE LAST UPDATED: 04/03/17 EPTANCE MIN �Q BASIS '�F HEIGHT CAPACIT AC MANT". PRESS MTITI 4 ELI I DESIGN INCHES GALLONS GALLONS TEMP (OF) RATING (PSI) 1 110 reTm ME. GENERAL ALL TRADES TO CONFIRM EQUIPMENT REQUIREMENTS (ELECTRICAL, WEIGHT, SIZE, ETC .. WITH APPROVED SUBMITTALS PRIOR TO INSTALLATION; FIELD COORDINATE FINAL LOCATION & INSTALL PER MANUFACTURERS REQUIREMENTS 1 ASME RATED CONSTRUCTION AIR SEPARATOR SCHEDULE LAST UPDATED: 04/03/17 L TAN OCA BASIS OF DESIGN GENERAL ALL TRADES TO CONFIRM EQUIPMENT REQUIREMENTS (ELECTRICAL, WEIGHT, SIZE, ETC ... ) WITH APPROVED SUBMITTAL�z PRIOR TO INSTALLATION; FIELD COORDINATE FINAL LOCATION &INSTALL PER MANUFACTURERS REQUIREMENTS 1 ASME CONSTRUCTION 2 GROOVED END CONNECTIONS WITH HANGING BRACKETS HYDRONIC MANIFOLD SCHEDULE UNIT TAG BASIS OF DESIGN # CIRCUITS TUBING SIZE SUPPLY TEMP (OF) TOTAL FLOW (USGPM) HEAD LOSS (FT WATER) TOTAL LOAD (BTU/HR) REMARKS SMA1 PRO -BALANCE 1" BRASS MANIFOLD WITH GAUGES 7 5/8" 130 10.76 19.8 102,040 1-4 SM A2 PRO -BALANCE 1" BRASS MANIFOLD WITH GAUGES 7 5/8" 130 10.55 20 100,180 1-4 SM A3 PRO -BALANCE 1" BRASS MANIFOLD WITH GAUGES 4 5/8" 130 5.78 15.1 54,825 1-4 SM B1 PRO -BALANCE 1" BRASS MANIFOLD WITH GAUGES 8 5/8" 130 10.96 17 104,065 1-4 SM B2 PRO -BALANCE 1" BRASS MANIFOLD WITH GAUGES 9 5/8" 130 12.09 16.4 114,778 1-4 SM C1 PRO -BALANCE 1" BRASS MANIFOLD WITH GAUGES 6 5/8" 130 10.99 27.1 94,313 1-4 SM C2 PRO -BALANCE 1" BRASS MANIFOLD WITH GAUGES 6 5/8" 130 10.45 23.6 90,425 1-4 SM C3 PRO -BALANCE 1" BRASS MANIFOLD WITH GAUGES 4 5/8" 130 4.05 7.3 38,441 1-4 SM D1 PRO -BALANCE 1" BRASS MANIFOLD WITH GAUGES 9 5/8" 130 13.17 19.8 124,971 1-4 SM D2 PRO -BALANCE 1" BRASS MANIFOLD WITH GAUGES 7 5/8" 130 10.5 18.3 99,656 1-4 SM E PRO -BALANCE 1" BRASS MANIFOLD WITH GAUGES 5 5/8" 130 6.61 13.1 62,700 1-4 RMP 1A PRO -BALANCE 1-1/4" BRASS MANIFOLD WITH GAUGES 6 3/4" 130 14.84 21.8 176,126 1-4 RMP1B PRO -BALANCE 1-1/4" BRASS MANIFOLD WITH GAUGES 5 311AT" 130 12.66 19.8 150,203 1-4 RMP2 PRO -BALANCE 1-1/4" BRASS MANIFOLD WITH GAUGES 10 3/4" 130 24.13 24.6 286,286 1-4 kEMARKS: 1 KEEP PIPE AT LEAST 6" FROM EDGES OF SLABS, WALLS, OR OTHER PERMANENT OBJECTS 2 LABEL PIPES AS THEY ARE INSTALLED. RECORD ON THE MANIFOLD, AND WITH TABS ON THE PIPE 3 SECURE PIPES EVERY 2'OR TON STRAIGHT RUNS AND ON THE START AND FINISH AND MIDPOINT OF ANY TURNS TO HOLD THE ESTABLISHED LAYING PATTERN. PIPE BENDS SHOULD BE FORMED TO PREVENT KINKING 4 AFTE12, I1JN7,ALL4TIO1J PE_12.F9J2,V P12ESSU9.E TE17 .4CCOqNIJG TG-1iWUFA,,A1_U2-,92S 12ECO Her,manson Building Today, Defining Tomorrow Hermanson Company LLP 1221 2nd Avenue North Kent, Washington 98032 Tel: (206) 575-9700 Fax: (206) 575-9800 www.hermanson.com Contractor Reg #: HERMACLO05BJ MAGIC TOYOTA OFEDMONDS 21300 HIGHWAY 99 EDMONDS, WA 98026 ODOR WAS,( 4 36149 IQ L Revisions 04/12/17 JMH ISSUE FOR PERMIT 03/31/17 JMH COORD SET REV3 A 03/24/17 JMH COORD SET REV2_ 03/17/17 JMH COORD SET REV1_ 03/02/17 JMH DD SET No. Date By Description Design Team esign Drawn FVP Checked DTN Project Number 11-17-10152 Issue Date 04/12/17 HYDRONIC SYSTEM: SCHEDULESHEET -HVAC MP0001 H I (��8" LOUVER -8 `�, - BY ARCH ARCHITECT TO PROVIDE 88"X36" LOUVER 18"X18" L BY 0 ECT TO 88"X36" 5 SWL--50-- (TYP 7) 2" HP—RO3� 1 —3 ECH 'UP TO P—u, Y�7 )0 )0 DTI-100 6"O:�, -------- --------- SEE DETAIL,�Z (TyP)' 115.01 111 W IS FOR PERMIT Hermanson Building Today, Defining Tomorrow Hermanson Company LLP 1221 2nd Avenue North Kent, Washington 98032 Tel: (206) 575-9700 Fax: (206) 575-9800 www.hermanson.com Contractor Reg #: HERMACLO05BJ MAGIC TOYOTA OFEDMONDS 21300 HIGHWAY 99 EDMONDS, WA 98026 toDo WAS 36149 L Revisions .04/12/17 JMH ISSUE FOR PERMIT A 03/31/17 JMH COORD SET REV3— A03/24/17 JMH COORD SET REV2- 03/17/17 JMH COORD SET REV1 03/02/17 JMH DID SET No. Date By Description Design Team Design JMH Drawn FVP Checked DTN Project Number 11-17-10152 Issue Date 04/12/17 1ST FLOOR PLAN - HVAC M2001 * ----------------------------- �)-8 ----------------- ----- OD 0- CH 2ND FLOOR PLAN - HVAC SCALE: 3/32" = V-0" Hermanson Building Today, Defining Tomorrow Hermanson Company LLP 1221 2nd Avenue North Kent, Washington 98032 Tel: (206) 575-9700 Fax: (206) 575-9800 www.hermanson.com Contractor Reg #: HERMACLO05BJ MAGIC TOYOTA OFEDMONDS 21300 HIGHWAY 99 EDMONDS, WA 98026 :WDOR WAS,( 36149 L Revisions 04/12/17 JMH ISSUE FOR PERMIT 03/31/17 JMH COORD SET REV3 03/24/17 JMH COORD SET REV2 03/17/17 JMH COORD SET REV1- 03/02/17 JMH DID SET No. Date By Description Design Team Design JMH Drawn FVP Checked DTN Project Number 11-17-10152 Issue Date 04/12/17 M 2ND FLOOR PLAN - HVAC M2002 SCALE: 3/32" = V-0" Hermanson Building Today, Defining Tomorrow Hermanson Company LLP 1221 2nd Avenue North Kent, Washington 98032 Tel: (206) 575-9700 Fax: (206) 575-9800 www.hermanson.com Contractor Reg #: HERMACLO05BJ MAGIC TOYOTA OFEDMONDS 21300 HIGHWAY 99 EDMONDS, WA 98026 tODOR 0� WAS 36149 L Revisions 04/12/17 JMH ISSUE FOR PERMIT 03/31/17 JMH COORD SET REV3_ 03/24/17 JMH COORD SET REV2- 03/17/17 JMH COORD SET REV1 03/02/17 JMH DID SET No. Date By Description Design Team Design JMH Drawn FVP Checked DTN Project Number 11-17-10152 Issue Date 04/12/17 ROOF PLAN - HVAC M20R1 PACKAGED AIR-CONDITIONING (A/C) UNIT J"LAG BOLTS 4'-O"O.C. 10,11161MIM 2X4 WOOD NAILER BY FACTORY INSULATION (a) RTU MOUNTING DETAIL M5.01 NOT TO SCALE UNION (TYP) BALL VALVE (TYP) i" (TYP) TO SUCTION SIDE OF PUMP INSULATION CHEMICAL POT FEEDER R] Fill 1 13 Ww" (�j:) CHEMICAL POT FEEDER DETAIL M5.01 NOT TO SCALE ROOF MOUNTED UPBLAST CENTRIFUGAL EXHAUST FAN FAN SECURED TO CURB WITH LONG SHEET METAL SCREWS 12" OC. (MINIMUM 2 PER) VENTED CURB 3 EXTENSION 4 FACTORY CURB IF COMBUSTIBLE ROOF (OR IN SEATTLE) M5.01 NOT TO SCALE ALL HANGERWIRES MUST BE VERTICAL (NOT SPLAYED) \ X-111 HANGER STRAP RADIUS 1 X DIA. NNNN0dUM9MM= I , DOUBLE I LAY -IN DIFFUSER >< DEFLECTION TEE -BAR CLG GRID DIFFUSER NEAM M5.01 NOT TO SCALE M WA111 WWI 511 2� --a 1511-7 Slab Stress Joint—/ \—Protective sleeve Slab Installation PROTECTIVE SLEEVE IN STRESS JOINTS DETAIL M SIDEWALL DIFFUSER DETAIL M5.01 NOT TO SCALE Note: Place fasteners every 2' to 3' so that the pipe does not loat in the slab. More maybe required if pipe rises. Ensure bends and turns are sew red. M5.01 NOT TO SCALE M5.01 NOT TO SCALE UNIT MOUNTED DISCONNECT SWITCH WITH CONDUIT THROUGH CURB __4___'(BY ELECTRICAL) ' " MESH BIRD SCREEN 2 NOTE: CURB HEIGHT WILL VARY WITH SLOPE OF ROOF. CURB WILL BE LEVELED FROM HIGHEST POINT OF ROOF. L INSULATED, GASKETED ROOF CURB. SECURED TO PACK TIGHT WITH 3M OVERLAP SHEET METAL S S TRUCTURE WITH APPROPRIATE EXPANDING EPDXY �b_ I MMIW=M cb IL TO PROVIDE DRIP EDGE S FASTENERS12"OC FOAM INSULATION REFER. PIPING (MINIMUM 2 PER SIDE) MIN. 2" DROP AT 12" WIDE X 6" DEEP ENTRANCE ROOFING MEMBRANE UP ROOF UTILITY CAP In CURB AND OVER TOP CU B "X24" LAG BOLT n Y (BY ROOFER) 0 0 F (4 REQUIRED) CANT STF ANT STRIP ;(BR i ROOF LINE I , �pqD ROOFING, BLOCKING AND CANT STRIP C' C '?c6?n� (BY GC) ROOF MOTORIZED DAMPER INTERLOCKED WITH FAN IF < 3-STORY BUILDING FILL VOID WITH OR LESS THAN 300 CFM BATT INSULATION IN SEATTLE USE GRAVITY BACKDRAFT DAMPER. NO DAMPER REQUIRED IF FAN OPERATES 24/7 A PLANS OR SPECIFICATIONS M5.01 NOT TO SCALE THERMOMETER BALL VALVE STRA BOILER PUMP CHECK VALVE GATE VALVE DRAIN TO FLC HKI IVI'l ki I I I IEF VALVE PIPED - SIZE TO DRAIN 11,011110 ISOLATION PAD NOTE: INSTALL STRAINER AT UNIT IF NOT INSTALLED AT DISTRIBUTION PUMP. LOW TEMPERATURE ELECTRIC /� 4 ELECTRIC BOILER DETAIL M5.01 NOT TO SCALE 11_� Concrete Slab Note: Minimum 2" concrete required from top of pipe to surface of slab Hermanson Building Today, Defining Tomorrow Hermanson Company LLP 1221 2nd Avenue North Kent, Washington 98032 Tel: (206) 575-9700 Fax: (206) 575-9800 www.hermanson.com Contractor Reg #: HERMACLO05BJ MAGIC TOYOTA OF EDMONDS 21300 HIGHWAY 99 EDMONDS, WA 98026 �V' 0�, WAS,(-,, 36149 GIs L Revisions 04/12/17 JMH ISSUE FOR PERMIT 03/31/17 JMH COORD SET REV3 A 03/24/17 JMH COORD SET REV2_ 03/17/17 JMH COORD SET REV1_ 03/02/17 JMH DID SET No. Date By Description Design Team Design JMH Drawn FVP Checked DTN Project Number 11 —17-10152 Issue Date 04/12/17 DETAIL SHEET - HVAC M5mOl ISSUE FOR PERMIT Hermanson Building Today, Defining Tomorrow Hermanson Company LLP 1221 2nd Avenue North Kent, Washington 98032 Tel: (206) 575-9700 Fax: (206) 575-9800 www.hermanson.com Contractor Reg #: HERMACLO05BJ MAGIC TOYOTA OFEDMONDS 21300 HIGHWAY 99 EDMONDS, WA 98026 toDo WAS 36149 L Revisions 04/12/17 JMH ISSUE FOR PERMIT 03/31/17 JMH COORD SET REV3 03/24/17 JMH COORD SET REV2 03/17/17 JMH COORD SET REV1- 03/02/17 JMH DID SET No. Date By Description Design Team Design JMH Drawn FVP Checked DTN Project Number 11-17-10152 Issue Date 04/12/17 1ST FLOOR PIPING PLAN - HVAC MP2001 * ----------------------------- �)-8 ----------------- ----- OD 0- CH 2ND FLOOR PIPING PLAN - HVAC SCALE: 3/32" = 1 P—O'p Hermanson Building Today, Defining Tomorrow Hermanson Company LLP 1221 2nd Avenue North Kent, Washington 98032 Tel: (206) 575-9700 Fax: (206) 575-9800 www.hermanson.com Contractor Reg #: HERMACLO05BJ MAGIC TOYOTA OFEDMONDS 21300 HIGHWAY 99 EDMONDS, WA 98026 :WDOR WAS,( 36149 L Revisions 04/12/17 JMH ISSUE FOR PERMIT 03/31/17 JMH COORD SET REV3 03/24/17 JMH COORD SET REV2 03/17/17 JMH COORD SET REV1- 03/02/17 JMH DID SET No. Date By Description Design Team Design JMH Drawn FVP Checked DTN Project Number 11-17-10152 Issue Date 04/12/17 M 2ND FLOOR PIPING PLAN - HVAC MP2002 a 111111111111 0 0 1111111111�0 SCALE: 3/32" = V-0" Hermanson Building Today, Defining Tomorrow Hermanson Company LLP 1221 2nd Avenue North Kent, Washington 98032 Tel: (206) 575-9700 Fax: (206) 575-9800 www.hermanson.com Contractor Reg #: HERMACLO05BJ MAGIC TOYOTA OFEDMONDS 21300 HIGHWAY 99 EDMONDS, WA 98026 tODOR 0� WAS 36149 L Revisions 04/12/17 JMH ISSUE FOR PERMIT 03/31/17 JMH COORD SET REV3_ 03/24/17 JMH COORD SET REV2- 03/17/17 JMH COORD SET REV1 03/02/17 JMH DID SET No. Date By Description Design Team Design JMH Drawn FVP Checked DTN Project Number 11-17-10152 Issue Date 04/12/17 ROOF PIPING PLAN - HVAC MP20R1 CO—GEN MANIFOLD MANIFOLD RMP 1 (A&B) SM E MANIFOLD SM D(1&2) - HW MR ------------- iAS-HUI -HWR- HWS-HM-"WS E CO-GIEN WATER SUPPLY SCHEMATIC PIPING DIAGRAM SCALE: NONE MANIFOLD SM C(l &2) MANIFOLD SM B(l &2) MANIFOLD SM A(l &2) Hermanson Building Today, Defining Tomorrow Hermanson Company LLP 1221 2nd Avenue North Kent, Washington 98032 Tel: (206) 575-9700 Fax: (206) 575-9800 www.hermanson.com Contractor Reg #: HERMACLO05BJ MAGIC TOYOTA OF EDMONDS 21300 HIGHWAY 99 EDMONDS, WA 98026 taODOI& -� WAS,( 0 z,, 36149 t L Revisions 04/12/17 JIVIH ISSUE FOR PERMIT 03/31/17 JIVIH COORD SET REV3 03/24/17 JMH COORD SET REV2 03/17/17 JMH COORD SET REV1- 03/02/17 JIVIH DID SET No. Date By Description Design Team Design JIVIH Drawn FVP Checked DTN Project Number 11 —17-10152 Issue Date 04/12/17 SCHEMATIC PIPING DIAGRAM - HVAC MP6mOl ISSUE FOR PERMIT C1 H) . ........... �"[� - --------------------------------------- Hermanson Building Today, Defining Tomorrow Hermanson Company LLP 1221 2nd Avenue North Kent, Washington 98032 Tel: (206) 575-9700 Fax: (206) 575-9800 www.hermanson.com Contractor Reg #: HERMACLO05BJ MAGIC TOYOTA OFEDMONDS 21300 HIGHWAY 99 EDMONDS, WA 98026 toDo WAS 36149 L Revisions 04/12/17 JMH ISSUE FOR PERMIT 03/31/17 JMH COORD SET REV3 03/24/17 JMH COORD SET REV2 03/17/17 JMH COORD SET REV1- 03/02/17 JMH DID SET No. Date By Description Design Team Design JMH Drawn FVP Checked DTN Project Number 11-17-10152 Issue Date 04/12/17 HYDRONIC SYSTEM: 1ST FLOOR PIPING PLAN - HVAC MP2001 H 12 ---------------------------------- ----- --------------------------- ---- --------------------- ---- I ------------------- (A 8) - - - ---- -- --- ---------------------- ---- --------------------- ---- �OD — - 1 10 9 8 C7 C6P 4 C-3 D Hermanson Building Today, Defining Tomorrow Hermanson Company LLP 1221 2nd Avenue North Kent, Washington 98032 Tel: (206) 575-9700 Fax: (206) 575-9800 www.hermanson.com Contractor Reg #: HERMACLO05BJ MAGIC TOYOTA OFEDMONDS 21300 HIGHWAY 99 EDMONDS, WA 98026 ODOR 0� WAS 36149 IQ L Revisions 04/12/17 JMH ISSUE FOR PERMIT 03/31/17 JMH COORD SET REV3 03/24/17 JMH COORD SET REV2 03/17/17 JMH COORD SET REV1- 03/02/17 JMH DID SET No. Date By Description Design Team Design JMH Drawn FVP Checked DTN Project Number 11-17-10152 Issue Date 04/12/17 HYDRONIC SYSTEM: 2ND FLOOR PIPING PLAN - HVAC MP2002H