2017-0499 Pt Edwards Bldg 10 mech-gas piping - Gasline Mech.pdfOV EQ_4 City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: April 28, 2017 TO: Darren Neubauer Gasline Mechanical dneubauer@gaslinemechanical.com FROM: Chuck Miller, Plans Examiner RE: Plan Check: BLD2017-0499 Project Address: 50 Pine Street Project: Pt Edwards Building 10 mechanical & gas piping Scope: Install mechanical ventilation and exhaust system for multi-unit/multi-use structure — install fuel piping for mechanical equipment — A-3/R-2/S-2 occupancy groups — 604 occupants — VA construction - NFPA-13 sprinkler system required Please be advised that the building plans for the above referenced project have been disapproved for the purposes of obtaining a building permit. During a review of the plans by the Building Division for compliance with the applicable building codes, it was found that the following information, clarifications, or changes are needed. Reviews by other divisions, such as Planning, Engineering, or Fire, may result in additional comments that require attention beyond the scope of this letter. A complete review cannot be performed until the revised plans/documents, including a written response in itemized letter format indicatin2 where the 'clouded' or otherwise highlighted changes can be found on the revised plans, have been submitted to a Permit Coordinator. Resubmittals must be made at the Development Services Department on the 2 d Floor of City Hall. Permit Center hours are M, T, Th, & F from 8am-4:30pm and from 8:30am-12pm on Wednesdays. On sheet MOOO — Legend, Notes, & Index: 1. Applicable Codes — Change on the plans the referenced code versions from '2012' to '2015'. 2. Parking Garage Ventilation Notes a. Second 'Note 3' — Change on the plans the numbering of the note from '3' to W. b. Note 5 — Change on the plans the referenced code section regarding enclosed parking garage exhaust ventilation controls from 'C403.2.6.4' to that found in the currently adopted code version. On sheet M001 — Schedules: 3. Fan Schedule — Note I I — Change on the plans the referenced code section regarding the elevator pressurization system fan activation from '905' to that found in the currently adopted code version. 4. Split System Heat Pump Schedule — Indoor Unit — FCU- I — Clarify on the plans the specified minimum 'OSA' to be provided for the 'Exercise Room'. It does not appear to meet the minimum requirements of International Mechanical Code (IMC) Table 403.3. 1. 1. On sheet M002 — Schedules: 5. General plan review note — Provide as part of a complete mechanical permit submittal information regarding the proposed fire/smoke dampers to be installed. Provide a corresponding schedule and applicable references to details for the required installation (such as those found on sheet 'M400'- details '1', '2', and '3' — although the details should be 'updated' to reflect current code versions and code sections). 6. Wa State Energy Code Notes a. Note 2 — Change on the plans the referenced code section regarding the thermostat deadband range from 'C403.2.4.2' to that found in the currently adopted code version. b. Note 3 — Change on the plans the referenced code section regarding the duct insulation from 'C403.2.7' to that found in the currently adopted code version. c. Note 4 — Change on the plans the referenced code section regarding the shutoff dampers from 'C402.4.5.2' to that found in the currently adopted code version. 7. Whole House Ventilation Notes a. Note 1 - Change on the plans the referenced code version from '2012' to '2015'. b. Note 4 - Change on the plans the referenced code version from '2012' to '2015'. On sheet M203.E — Level 3 Plan East: Garage Ventilation Calculation a. Change on the plans the referenced code version from '2012' to '2015'. b. Change on the plans the referenced code table regarding minimum ventilation rates from '403.3' to that found in the currently adopted code version. On sheet M203.W — Level 3 Plan West: 9. Garage Ventilation Calculation a. Change on the plans the referenced code version from '2012' to '2015'. b. Change on the plans the referenced code table regarding minimum ventilation rates from '403.3' to that found in the currently adopted code version. On sheet M205.W — Level 5 Plan West: 10. Level 5 Plan — West — Clarify on the plans the 'callout' to 'EDH-2' in the upper -right comer of the plan sheet. Page 2 of 8 On sheet M300 — Enlarged Unit Plans: 11. Plan 1 — Unit A2 - Enlarged Unit Plan — Clarify on the plans the specified whole house ventilation rate for fan 'EF- I'. It does not appear to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms. 12. Plan 2 — Unit A2 — FCU - Enlarged Unit Plan — Clarify on the plans the specified whole house ventilation rate for fan 'EF- I'. It does not appear to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms. 13. Plan 3 — Unit A2 — RTU - Enlarged Unit Plan — Clarify on the plans the specified whole house ventilation rate for fan 'EF- I'. It does not appear to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms. 14. Flag Notes — Note 1 a. Change on the plans the referenced code version from '2012' to '2015'. b. Change on the plans the referenced code section regarding dryer duct length identification from '504.6' to that found in the currently adopted code version. 15. Dryer Notes — Clarify on the plans the reference to detail '8' on sheet 'M4.00-E' regarding the maximum length of the dryer duct. A corresponding detail could not be found on sheet 'M400'. On sheet M301 — Enlarged Unit Plans: 16. Plan 1 — Unit A3 - Enlarged Unit Plan — Clarify on the plans the specified whole house ventilation rate for fan 'EF- I'. It does not appear to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms. 17. Plan 2 — Unit A4 - Enlarged Unit Plan — Clarify on the plans the specified whole house ventilation rate for fan 'EF- I'. It does not appear to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms. 18. Plan 3 — Unit B2 - Enlarged Unit Plan — Clarify on the plans the specified whole house ventilation rate for fan 'EF- I'. It does not appear to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms. 19. Plan 4 — Unit B2 A - Enlarged Unit Plan — Clarify on the plans the specified whole house ventilation rate for fan 'EF- I'. It does not appear to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms. 20. Plan 5 — Unit B2 — Shaft - Enlarged Unit Plan — Clarify on the plans the specified whole house ventilation rate for fan 'EF- I'. It does not appear to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms. 21. Flag Notes — Note 1 a. Change on the plans the referenced code version from '2012' to '2015'. b. Change on the plans the referenced code section regarding dryer duct length identification from '504.6' to that found in the currently adopted code version. 22. Dryer Notes — Clarify on the plans the reference to detail '8' on sheet 'M4.00-E' regarding the maximum length of the dryer duct. A corresponding detail could not be found on sheet 'M400'. Page 3 of 8 On sheet M302 — Enlarged Unit Plans: 23. Plan 1 — Unit B2 Shaft — FCU - Enlarged Unit Plan — Clarify on the plans the specified whole house ventilation rate for fan 'EF- I'. It does not appear to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms. 24. Plan 2 — Unit B2 Shaft — RTU A - Enlarged Unit Plan — Clarify on the plans the specified whole house ventilation rate for fan 'EF- I'. It does not appear to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms. 25. Plan 3 — Unit B2 Shaft — RTU B - Enlarged Unit Plan — Clarify on the plans the specified whole house ventilation rate for fan 'EF- I'. It does not appear to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms. 26. Flag Notes — Note I a. Change on the plans the referenced code version from '2012' to '2015'. b. Change on the plans the referenced code section regarding dryer duct length identification from '504.6' to that found in the currently adopted code version. 27. Dryer Notes — Clarify on the plans the reference to detail W on sheet 'M4.00-E' regarding the maximum length of the dryer duct. A corresponding detail could not be found on sheet 'M400'. On sheet M303 — Enlarged Unit Plans: 28. Plan I — Unit B4 - Enlarged Unit Plan — Clarify on the plans the specified whole house ventilation rate for fan 'EF- I'. It does not appear to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms. 29. Plan 2 — Unit B4 — FCU - Enlarged Unit Plan a. Clarify on the plans the specified whole house ventilation rate for fan 'EF- I'. It does not appear to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms. b. Clarify on the plans the represented location of the 'FCU' — fan coil unit — in the 'Laundry' area (and the associated location of the water heater in the bedroom closet). It does not correspond with that represented on the approved plans for work under permit BLD2015-0846 or under permit BLD2016-1003 — sheet 'P204.W' and plan '3' on sheet 'P301'. 30. Plan 3 — Unit B4 — RTU - Enlarged Unit Plan — Clarify on the plans the specified whole house ventilation rate for fan 'EF- 1'. It does not appear to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms. 3 1. Flag Notes — Note 1 a. Change on the plans the referenced code version from '2012' to '2015'. b. Change on the plans the referenced code section regarding dryer duct length identification from '504.6' to that found in the currently adopted code version. 32. Dryer Notes — Clarify on the plans the reference to detail '8' on sheet 'M4.00-E' regarding the maximum length of the dryer duct. A corresponding detail could not be found on sheet 'M400'. Page 4 of 8 On sheet M304 — Enlarged Unit Plans: 33. Plan 1 — Unit B5 - Enlarged Unit Plan a. Clarify on the plans the specified whole house ventilation rate for fan 'EF- I'. It does not appear to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms. b. Indicate on the plans the method to be used to provide the required makeup air where the closet is designed for the installation of a clothes dryer per IMC 504.6 (provided elsewhere on the plans by the means indicated by 'flag' '3'). 34. Plan 2 — Unit C 1 - Enlarged Unit Plan — Clarify on the plans the specified whole house ventilation rate for fan 'EF- I'. It does not appear to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms. 35. Plan 4 — Unit C I Shaft - Enlarged Unit Plan — Clarify on the plans the specified whole house ventilation rate for fan 'EF- I'. It does not appear to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms. 36. Flag Notes — Note 1 a. Change on the plans the referenced code version from '2012' to '2015'. b. Change on the plans the referenced code section regarding dryer duct length identification from '504.6' to that found in the currently adopted code version. 37. Dryer Notes — Clarify on the plans the reference to detail '8' on sheet 'M4.00-E' regarding the maximum length of the dryer duct. A corresponding detail could not be found on sheet 'M400'. On sheet M305 — Enlarged Unit Plans: 3 8. Plan I — Unit C 1 IDF - Enlarged Unit Plan — Clarify on the plans the specified whole house ventilation rate for fan 'EF- I'. It does not appear to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms. 39. Plan 2 — Unit C I Shaft — FCU - Enlarged Unit Plan — Clarify on the plans the specified whole house ventilation rate for fan 'EF- I'. It does not appear to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms. 40. Flag Notes — Note I a. Change on the plans the referenced code version from '2012' to '2015'. b. Change on the plans the referenced code section regarding dryer duct length identification from '504.6' to that found in the currently adopted code version. 4 1. Dryer Notes — Clarify on the plans the reference to detail W on sheet 'M4. 00-E' regarding the maximum length of the dryer duct. A corresponding detail could not be found on sheet 'M400'. On sheet M306 — Enlarged Unit Plans: 42. Plan I — Unit C I IDF — RTU - Enlarged Unit Plan — Clarify on the plans the specified whole house ventilation rate for fan 'EF- I'. It does not appear to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms. Page 5 of 8 43. Plan 2 — Unit C1 Shaft — RTU - Enlarged Unit Plan a. Clarify on the plans the specified whole house ventilation rate for fan 'EF- I'. It does not appear to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms. b. Clarify on the plans the indicated 'POC' — point -of -connection - of the 'range hood' duct. It does not appear to correspond with the represented location of the cooking appliance. c. Clarify on the plans the representation of the ductwork serving 'Unit C 1 Shaft — RTU'. It does not appear to correspond with the 'grille' and 'diffuser' locations represented on the 'equipment plan' below. 44. Flag Notes — Note I a. Change on the plans the referenced code version from '2012' to '2015'. b. Change on the plans the referenced code section regarding dryer duct length identification from '504.6' to that found in the currently adopted code version. 45. Dryer Notes — Clarify on the plans the reference to detail '8' on sheet 'M4.00-E' regarding the maximum length of the dryer duct. A corresponding detail could not be found on sheet 'M400'. On sheet M307 — Enlarged Unit Plans: 46. Plan I — Unit C1 IDF — FCU - Enlarged Unit Plan a. Clarify on the plans the specified whole house ventilation rate for fan 'EF- I'. It does not appear to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms. b. Clarify on the plans the represented location of the 'FCU' — fan coil unit — in the 'Laundry' area (and the associated location of the water heater in the bathroom closet). It does not correspond with that represented on the approved plans for work under permit BLD2015-0846 — sheet Al 14 - or under permit BLD2016-1003 — sheet 'P204.W' and sheet 'P302'. 47. Plan 2 — Unit C2 South — FCU - Enlarged Unit Plan - Clarify on the plans the specified whole house ventilation rate for fan 'EF- I'. It does not appear to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms. 48. Plan 3 — Unit C2 South - Enlarged Unit Plan — Clarify on the plans the specified whole house ventilation rate for fan 'EF- I'. It does not appear to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms. 49. Plan 4 — Unit C2 South A - Enlarged Unit Plan — Clarify on the plans the specified whole house ventilation rate for fan 'EF- 1'. It does not appear to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms. 50. Flag Notes — Note 1 a. Change on the plans the referenced code version from '2012' to '2015'. b. Change on the plans the referenced code section regarding dryer duct length identification from '504.6' to that found in the currently adopted code version. 5 1. Dryer Notes — Clarify on the plans the reference to detail '8' on sheet 'M4.00-E' regarding the maximum length of the dryer duct. A corresponding detail could not be found on sheet 'M400'. Page 6 of 8 On sheet M308 — Enlarged Unit Plans: 52. Plan 1 — Unit C4 - Enlarged Unit Plan — Clarify on the plans the specified whole house ventilation rate for fan 'EF- I'. It does not appear to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms. 53. Plan 2 — Unit C3 — RTU - Enlarged Unit Plan — Clarify on the plans the specified whole house ventilation rate for fan 'EF- I'. It does not appear to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms. 54. Flag Notes — Note I a. Change on the plans the referenced code version from '2012' to '2015'. b. Change on the plans the referenced code section regarding dryer duct length identification from '504.6' to that found in the currently adopted code version. 55. Dryer Notes — Clarify on the plans the reference to detail '8' on sheet 'M4.00-E' regarding the maximum length of the dryer duct. A corresponding detail could not be found on sheet 'M400'. On sheet M309 — Enlarged Unit Plans: 56. Plan I — Unit C3 - Enlarged Unit Plan — Clarify on the plans the specified whole house ventilation rate for fan 'EF- I'. It does not appear to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms. 57. Plan 3 — Unit C4 A - Enlarged Unit Plan — Clarify on the plans the specified whole house ventilation rate for fan 'EF- I'. It does not appear to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms. 58. Flag Notes — Note I a. Change on the plans the referenced code version from '2012' to '2015'. b. Change on the plans the referenced code section regarding dryer duct length identification from '504.6' to that found in the currently adopted code version. 59. Dryer Notes — Clarify on the plans the reference to detail '8' on sheet 'M4.00-E' regarding the maximum length of the dryer duct. A corresponding detail could not be found on sheet 'M400'. On sheet M401 — Details & Diagrams: 60. General plan review note — Provide on the plans where applicable, a reference to the provided details to guide proper installation and inspection. On sheet GOOO — Legend, Notes, & Index: 61. Applicable Codes — Change on the plans the referenced code versions from '2012' to '2015'. On sheet G001 — Schedules: 62. General plan review note — Provide on the plans where applicable and required, a reference to the provided detail to guide proper installation and inspection. Page 7 of 8 On sheets G201E, G202.E, G202.W, G203.E, G203.W, G204.E, G204.W, and G205.W: 63. General plan review note — Specify on the plans the minimum required size of the vertical branches ('up' and/or 'down') to meet the corresponding demands of the appliances located on the levels 'above' and/or below' to guide proper installation and inspection. On sheet G204.E — Level 4 Gas Plan East: 64. Level 4 Gas Plan — East a. Clarify on the plans the method used to establish the 3/4-inch range outlet at 'gridline' '5.9/C.5'. There does not appear to be a corresponding 'branch' represented below on sheet 'G203.E' — Level 3 Gas Plan East. b. Clarify on the plans the method used to establish the 1 -inch branch serving 'RTU-2' at 'gridline ' ' 3. 1 IC'. There does not appear to be a corresponding 'branch' represented below on sheet 'G203.E' — Level 3 Gas Plan East. Page 8 of 8