Loading...
2017-0499 Pt Edwards Bldg 10 mech-gas piping 2- Gasline Mech.pdfCity of Edmonds. PLAN R.EVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: July 6, 2017 TO: Darren Neubauer Gasline Mechanical dneubauer(d)gaslinemechanical.com FROM: Chuck Miller, Plans Examiner RE: Plan Check: BLD2017-0499 — 2nd review Project Address: 50 Pine Street Project: Pt Edwards Building 10 mechanical & gas piping Scope: Install mechanical ventilation and exhaust system for multi-unit/multi-use structure — install fuel piping for mechanical equipment — A-3/R-2/S-2 occupancy groups — 604 occupants — VA construction - NFPA- 13 sprinkler system required Please be advised that the building plans for the above referenced project have been disapproved for the purposes of obtaining a building permit. During a review of the plans by the Building Division for compliance with the applicable building codes, it was found that the following information, clarifications, or changes are needed. Reviews by other divisions, such as Planning, Engineering, or Fire, may result in additional comments that require attention beyond the scope of this letter. Items that recur on this list appear in italics. A complete review cannot be performed until the revised plans/documents, including a written response in itemized letter format indicating where the 'clouded' or otherwise highlighted changes can be found on the revised plans, have been submitted to a Permit Coordinator. Resubmittals must be made at the Development Services Department on the 2nd Floor of City Hall. Permit Center hours are M, T, Th, & F from 8am-4:30pm and from 8:30am-12pm on Wednesdays. On sheet MOOO — Legend, Notes, & Index: 1. Applicable Codes — Resolved - The referenced code versions have been changed from '2012' to '2015' on the plans. 2. Parking Garage Ventilation Notes a. Second 'Note 3' — Resolved - The numbering of the note has been changed from '3' to '4' on the plans. b. Note 5 — Resolved - The referenced code section regarding enclosed parking garage exhaust ventilation controls has been changed from 'C403.2.6.4' to that found in the currently adopted code version on the plans. On sheet MOO I — Schedules: 3. Fan Schedule — Note I I — Resolved - The proposed elevator pressurization system installation has been removed from the scope of work. 4. Split System Heat Pump Schedule — Indoor Unit — FCU-1 — Partially resolved - Clarify on theplans the specified minimum 'OSA'to beprovidedfor the 'Exercise Room � It does not appear to meet the minimum requirements of International Mechanical Code (1MQ Table 403.3.1.1. The response to the earlier plan review comment states: "OSA is correct per table 403.3.1.1 for health club/weight room. Ref sheet MOM.". While the proposed minimum 'OSA' meets/exceeds that required for the use of the 'Exercise Room' by 7 occupants for weights per IMC Table 403.3. 1. 1, it is less than half of what is required for the use of the space by a greater number of occupants for other anticipated activities (cycle - /stair -type equipment, treadmills, etc.) with higher occupant densities per IMC Table 403.3. 1. 1, and limits the occupant load of the space to 10 occupants. On sheet M002 — Schedules: 5. General plan review note — Resolved - Information regarding the proposed fire/smoke dampers installations, including a schedule and applicable references to details for the required installation has been provided on the plans. 6. Wa State Energy Code Notes a. Note 2 — Resolved - The referenced code section regarding the thermostat deadband range has been changed from 'C403.2.4.2' to that found in the currently adopted code version on the plans. b. Note 3 — Resolved - The referenced code section regarding the duct insulation has been changed from 'C403.2.7' to that found in the currently adopted code version on the plans. c. Note 4 — Resolved - The referenced code section regarding the shutoff dampers has been changed from 'C402.4.5.2' to that found in the currently adopted code version on the plans. 7. Whole House Ventilation Notes a. Note I — Resolved - The referenced code version has been changed from '2012' to '2015' on the plans. b. Note 4 — Resolved - The referenced code version has been changed from '2012' to '2015' on the plans. On sheet M203.E — Level 3 Plan East: Garage Ventilation Calculation a. Resolved - The referenced code version has been changed from '2012' to '2015' on the plans. Page 2 of 9 b. Resolved - The referenced code table regarding minimum ventilation rates has been changed from '403.3' to that found in the currently adopted code version on the plans. On sheet M203.W — Level 3 Plan West: 9. Garage Ventilation Calculation a. Resolved - The referenced code version has been changed from '2012' to '2015' on the plans. b. Resolved - The referenced code table regarding minimum ventilation rates has been changed from '403.3' to that found in the currently adopted code version on the plans. On sheet M205.W — Level 5 Plan West: 10. Level 5 Plan — West — Resolved - The 'callout' to 'EDH-2' in the upper -right comer of the plan sheet has been removed from the plans. On sheet M300 — Enlarged Unit Plans: 11. Plan I — Unit A2 - Enlarged Unit Plan — Resolved - The specified whole house ventilation rate for fan 'EF- I' has been changed to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms on the plans. 12. Plan 2 — Unit A2 — FCU - Enlarged Unit Plan — Resolved - The specified whole house ventilation rate for fan 'EF- V has been changed to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms on the plans. 13. Plan 3 — Unit A2 — RTU - Enlarged Unit Plan — Resolved - The specified whole house ventilation rate for fan 'EF- V has been changed to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms on the plans. 14. Flag Notes — Note 1 a. Resolved - The referenced code version has been changed from '2012' to '2015' on the plans. b. Resolved - The referenced code section regarding dryer duct length identification has been changed from '504.6' to that found in the currently adopted code version on the plans. 15. Dryer Notes — Resolved - Detail '8' regarding the maximum length of the dryer duct has been provided on sheet 'M400' of the plans. On sheet M301 — Enlarged Unit Plans: 16. Plan I — Unit A3 - Enlarged Unit Plan — Resolved - The specified whole house ventilation rate for fan 'EF- I' has been changed to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms on the plans. 17. Plan 2 — Unit A4 - Enlarged Unit Plan — Resolved - The specified whole house ventilation rate for fan 'EF- I' has been changed to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms on the plans. Page 3 of 9 18. Plan 3 — Unit B2 - Enlarged Unit Plan — Resolved - The specified whole house ventilation rate for fan 'EF- V has been changed to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms on the plans. 19. Plan 4 (changed to '5') — Unit B2 A - Enlarged Unit Plan — Resolved - The specified whole house ventilation rate for fan 'EF- l' has been changed to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms on the plans. 20. Plan 5 (changed to W) — Unit B2 — Shaft - Enlarged Unit Plan — Resolved - The specified whole house ventilation rate for fan 'EF- V has been changed to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms on the plans. 2 1. Flag Notes — Note I a. Resolved - The referenced code version has been changed from '2012' to '2015' on the plans. b. Resolved - The referenced code section regarding dryer duct length identification has been changed from '504.6' to that found in the currently adopted code version on the plans. 22. Dryer Notes — Resolved - Detail '8' regarding the maximum length of the dryer duct has been provided on sheet 'M400' of the plans. On sheet M302 — Enlarged Unit Plans: 23. Plan I — Unit B2 Shaft — FCU - Enlarged Unit Plan — Resolved - The specified whole house ventilation rate for fan 'EF- V has been changed to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms on the plans. 24. Plan 2 — Unit B2 Shaft — RTU A - Enlarged Unit Plan — Resolved - The specified whole house ventilation rate for fan 'EF- V has been changed to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms on the plans. 25. Plan 3 — Unit B2 Shaft — RTU B - Enlarged Unit Plan — Resolved - The specified whole house ventilation rate for fan 'EF- I' has been changed to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms on the plans. 26. Flag Notes — Note 1 a. Resolved - The referenced code version has been changed from '2012' to '2015' on the plans. b. Resolved - The referenced code section regarding dryer duct length identification has been changed from '504.6' to that found in the currently adopted code version on the plans. 27. Dryer Notes — Resolved - Detail '8' regarding the maximum length of the dryer duct has been provided on sheet 'M400' of the plans. On sheet M303 — Enlarged Unit Plans: 28. Plan I — Unit B4 - Enlarged Unit Plan — Resolved - The specified whole house ventilation rate for fan 'EF- V has been changed to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms on the plans. Page 4 of 9 29. Plan 2 — Unit B4 — FCU - Enlarged Unit Plan a. Resolved - The specified whole house ventilation rate for fan 'EF- I' has been changed to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms on the plans. b. Resolved - The represented location of the 'FCU' — fan coil unit — in the 'Laundry' area (and the associated location of the water heater in the bedroom closet) for 'Unit 412' has been changed on the approved plans for work under permit BLD2015-0846 and under permit BLD2016-1003 — sheet 'P204.W' and plan '3' on sheet 'P301' to correspond with that represented under this permit. 30. Plan 3 — Unit B4 — RTU - Enlarged Unit Plan — Resolved - The specified whole house ventilation rate for fan 'EF- V has been changed to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms on the plans. 3 1. Flag Notes — Note 1 a. Resolved - The referenced code version has been changed from '2012' to '2015' on the plans. b. Resolved - The referenced code section regarding dryer duct length identification has been changed from '504.6' to that found in the currently adopted code version on the plans. 32. Dryer Notes — Resolved - Detail W regarding the maximum length of the dryer duct has been provided on sheet 'M400' of the plans. On sheet M304 — Enlarged Unit Plans: 33. Plan I — Unit B5 - Enlarged Unit Plan a. Resolved - The specified whole house ventilation rate for fan 'EF- I' has been changed to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms on the plans. b. Resolved - The method to be used to provide the required makeup air where the closet is designed for the installation of a clothes dryer per IMC 504.6 has been indicated by 'flag' '3' on the plans. 34. Plan 2 — Unit C 1 - Enlarged Unit Plan — Resolved - The specified whole house ventilation rate for fan 'EF- V has been changed to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms on the plans. 3 5. Plan 4 — Unit C I Shaft - Enlarged Unit Plan — Resolved - The specified whole house ventilation rate for fan 'EF- V has been changed to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms on the plans. 36. Flag Notes — Note 1 a. Resolved - The referenced code version has been changed from '2012' to '2015' on the plans. b. Resolved - The referenced code section regarding dryer duct length identification has been changed from '504.6' to that found in the currently adopted code version on the plans. 37. Dryer Notes — Resolved - Detail W regarding the maximum length of the dryer duct has been provided on sheet 'M400' of the plans. Page 5 of 9 On sheet M305 — Enlarged Unit Plans: 3 8. Plan I — Unit C I IDF - Enlarged Unit Plan — Resolved - The specified whole house ventilation rate for fan 'EF- I " has been changed to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms on the plans. 3 9. Plan 2 — Unit C I Shaft — FCU - Enlarged Unit Plan — Resolved - The specified whole house ventilation rate for fan 'EF- V has been changed to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms on the plans. 40. Flag Notes — Note 1 a. Resolved - The referenced code version has been changed from '2012' to '2015' on the plans. b. Resolved - The referenced code section regarding dryer duct length identification has been changed from '504.6' to that found in the currently adopted code version on the plans. 4 1. Dryer Notes — Resolved - Detail W regarding the maximum length of the dryer duct has been provided on sheet 'M400' of the plans. On sheet M306 (changed to M306A) — Enlarged Unit Plans: 42. Plan I — Unit C I IDF — RTU - Enlarged Unit Plan — Resolved - The specified whole house ventilation rate for fan 'EF- V has been changed to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms on the plans. 43. Plan 2 — Unit C 1 Shaft — RTU - Enlarged Unit Plan a. Resolved - The specified whole house ventilation rate for fan 'EF- 1' has been changed to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms on the plans. b. Resolved - The indicated 'POC' — point -of -connection - of the 'range hood' duct has been changed to correspond with the represented location of the cooking appliance on the plans. c. Resolved - The representation of the ductwork serving 'Unit C I Shaft — RTU' has been changed to correspond with the 'grille' and 'diffuser' locations represented on the 'equipment plan' below on the plans. 44. Flag Notes — Note I a. Resolved - The referenced code version has been changed from '2012' to '2015' on the plans. b. Resolved - The referenced code section regarding dryer duct length identification has been changed from '504.6' to that found in the currently adopted code version on the plans. 45. Dryer Notes — Resolved - Detail W regarding the maximum length of the dryer duct has been provided on sheet 'M400' of the plans. On sheet M307 — Enlarged Unit Plans: 46. Plan I — Unit C I IDF — FCU - Enlarged Unit Plan a. Resolved -The specified whole house ventilation rate for fan 'EF-l' has been changed to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms on the plans. Page 6 of 9 b. Resolved - The represented location of the 'FCU' — fan coil unit — in the 'Laundry' area (and the associated location of the water heater in the bathroom closet) for 'Unit 408' has been changed on the approved plans for work under permit BLD2015-0846 — sheet Al 14 - or under permit BLD2016-1003 — sheet 'P204.W' and sheet 'P302' to correspond with that represented under this permit. 47. Plan 2 — Unit C2 South — FCU - Enlarged Unit Plan — Resolved - The specified whole house ventilation rate for fan 'EF- V has been changed to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms on the plans. 48. Plan 3 — Unit C2 South - Enlarged Unit Plan — Resolved - The specified whole house ventilation rate for fan 'EF- V has been changed to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms on the plans. 49. Plan 4 — Unit C2 South A - Enlarged Unit Plan — Resolved - The specified whole house ventilation rate for fan 'EF- V has been changed to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms on the plans. 50. Flag Notes — Note 1 a. Resolved - The referenced code version has been changed from '2012' to '2015' on the plans. b. Resolved - The referenced code section regarding dryer duct length identification has been changed from '504.6' to that found in the currently adopted code version on the plans. 5 1. Dryer Notes — Resolved - Detail W regarding the maximum length of the dryer duct has been provided on sheet 'M400' of the plans. On sheet M308 — Enlarged Unit Plans: 52. Plan I (changed to 3) — Unit C4 - Enlarged Unit Plan — Resolved - The specified whole house ventilation rate for fan 'EF- 1' has been changed to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms on the plans. 53. Plan 2 — Unit C3 — RTU - Enlarged Unit Plan — Resolved - The specified whole house ventilation rate for fan 'EF- V has been changed to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms on the plans. 54. Flag Notes — Note I a. Resolved - The referenced code version has been changed from '2012' to '2015' on the plans. b. Resolved - The referenced code section regarding dryer duct length identification has been changed from '504.6' to that found in the currently adopted code version on the plans. 55. Dryer Notes — Resolved - Detail W regarding the maximum length of the dryer duct has been provided on sheet 'M400' of the plans. On sheet M309 — Enlarged Unit Plans: 56. Plan I — Unit C3 - Enlarged Unit Plan — Resolved - The specified whole house ventilation rate for fan 'EF- V has been changed to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms on the plans. Page 7 of 9 57. Plan 3 (changed to 4) — Unit C4 A - Enlarged Unit Plan — Resolved - The specified whole house ventilation rate for fan 'EF- I' has been changed to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms on the plans. 58. Flag Notes — Note I a. Resolved - The referenced code version has been changed from '2012' to '2015' on the plans. b. Resolved - The referenced code section regarding dryer duct length identification has been changed from '504.6' to that found in the currently adopted code version on the plans. 59. Dryer Notes — Resolved - Detail W regarding the maximum length of the dryer duct has been provided on sheet 'M400' of the plans. On sheet M401 — Details & Diagrams: 60. General plan review note — Resolved - A reference to the details has been provided on the plans where applicable to guide proper installation and inspection. On sheet GOOO — Legend, Notes, & Index: 61. Applicable Codes — Resolved - The referenced code versions has been changed from '2012' to '2015' on the plans. On sheet GOO I — Schedules: 62. General plan review note —Resolved - A reference to the detail has been provided on the plans where applicable and required to guide proper installation and inspection. On sheets G20 I E, G202.E, G202.W, G203.E, G203.W, G204.E, G204.W, and G205.W: 63. General plan review note — Resolved - The minimum required size of the vertical branches ('up' and/or 'down') to meet the corresponding demands of the appliances located on the levels 'above' and/or below' have been specified/added by the plans examiner on the plans to guide proper installation and inspection. On sheet G204.E — Level 4 Gas Plan East: 64. Level 4 Gas Plan — East a. Resolved — A corresponding 'branch' has been represented on sheet 'G203.E' — Level 3 Gas Plan East — to serve the3/4-inch range outlet at 'gridline' '5.9/C.5' on the plans. b. Resolved - A corresponding 'branch' has been represented on sheet 'G203.E' — Level 3 Gas Plan East — to supply the I -inch branch serving 'RTU-2' at 'gridline' '3. 1 /C' on the plans. Page 8 of 9 Additional plan review comments regarding resubmitted construction documents: On sheet M206.W — Roof Plan West: 65. Roof Plan West — Clarify on the plans the 'vent hoods' protecting the termination point of various exhaust outlets and ducts represented at the following locations: • 'Gridline' ' 16/J.5' —near 'RTU-512' • 'Gridline' ' 15/H.6' —near 'RTU-5 10' • 'Gridline' ' 13.9/J.3'— near 'RTU-l' • 'Gridline' ' 13/H.6' —near 'RTU-509' • 'Gridline' ' 12.9/J.3' —near 'RTU-509' • 'Gridline' 'I I/J.3 9 —near 'RTU-507' They do not appear to meet the required minimum distance from the mechanical air intake of the adjacent rooftop mechanical units (RTUs) per IMC 5 01.3. 1, Item 3. On sheet M301 — Enlarged Unit Plans: 66. Plan 4 — Unit A3 — Roof — Enlarged Unit Plan - Clarify on the plans the specified whole house ventilation rate for fan 'EF-F. It does not appear to meet the required minimum ventilation rate per IMC Table 403.8.1 for the represented floor area/number of bedrooms. Page 9 of 9