20170522110308.pdfCity of Edmonds, PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: April 13, 2017 TO: Qian Zhang HGL Design hL,,I.designconstructioiiO,P-mail.com FROM: Chuck Miller, Plans Examiner RE: Plan Check: BLD2017-0275 Project Address: 22001 Highway 99, Suite 400 Project: DTC Hunan Restaurant RESUB MAy 19 2017 BUILDING DEPARTMENT ciTY OF EDMONDS Scope: Tenant improvement for restaurant — A-2 occupancy group — 121 occupants — VB construction - NFPA- 13 sprinkler system required — mechanical, plumbing, type I hood, fire suppression for hood, fire sprinkler, fire alarm, etc. under separate permits Please be advised that the building plans for the above referenced project have been disapproved for the purposes of obtaining a building permit. During a review of the plans by the Building Division for compliance with the applicable building codes, it was found that the following information, clarifications, or changes are needed. Reviews by other divisions, such as Planning, Engineering, or Fire, may result in additional comments that require attention beyond the scope of this letter. A complete review cannot be performed until the revised Vlans/documents, includ' written response in itemized letter format indicating where the 'clouded' or other -wise highlighted changes can be found on the revised plans, have been submitted to a Permit Coordinator. Resubmittals must be made at the Development Services Department on the 2 d Floor of City Hall. Permit Center hours are M, T, Th, & F from 8am-4:3 Opin and from 8:3 Oam- I 2pin on Wednesdays. yeUaW 0--&aL General plan review note: Provide as part of a complete permit application submittal a copy of the required review approval letter from the Envirom-nental Health Division of the Snohomish Health District for the proposed project per the City of Edmonds 'Tenant Improvement Permit Submittal Requirements'. (health district submitted. Due to [lie flact ofl'significa.nL understaffed and backlog of submission, (lie waiting time is expected to be several months, Please proceed to the permit applicaiion reviewand issue the building permit., thanks) On sheet A- I — Project Information, Description, Notes, Code Information, Occupant Load Calculation, Vicinity Map, and Site Plan: 2. Project Description — Note 2 — Clarify on the plans the stated presence of "Landlord provided 2 hour fire rated walls between suites.". A record of permitted work requiring or allowing the construction of such work could not be found — see also plan review comments '3a', '3b', and'6a'.(It is confirmed that the 2 hour fire rated walls were perinitted under BLD 2015-1265) 3. Code Information a. Indicate on the plans the required automatic fire sprinkler system for fire areas exceeding 5000 square feet per International Building Code (IBC) 903.2.1.2, Item L(notapplicable, the plan has area less Lh,,m 5,000 sq ft) b. Indicate on the plans the required automatic fire sprinkler system for fire areas with an occupant load of 100 or more per IBC 903.2.1.2, Item 2 — see also plan review comment'4'. (not applicable, the updated plaii with occupiiicy Imid calcLita(ioll per guidance gives less than 100 occLipants.) 4. Occupancy Load Calculation - Clarify on the plans the accounting of the functions of use of the proposed tenant space per International Building Code (IBC) Table 1004.1.2. Approximately 25% of the 'occupiable' space has not been accounted for. Standing areas and seating types different than tables and chairs, such as those in space '00 1' — Waiting Area — on sheet 'A-2', have specific occupant loads factors. Other 'occupiable' areas, such as space '005' — Corridor — and the restrooms — space '006' — Men — and space '007' — Women — also need to be accounted for. The indicated 'Dining' area also appears to be considerably smaller than that determined during a review of the plans — see attachment 'occupant load'. Change on the plans the noted occupant loads in response to the above information. (Plan has been updated to have lowei� tliaii 100 ocetipants, Pleasc see tipdated occupant load ealculatiori.) 5. General Notes — Note 7 — Change on the plans the provided information for the 'Health Department'j urisdiction from 'King County' to 'Snohomish Health District'. (revi sed, see updated drawim,) I __ On sheet A-2 — Proposed Floor Plan, Schedules & Partition Type Details: 6. Proposed Floor Plan a. Clarify on the plans the note: "Existing 2 hour fire rated wall to remain — Provided by shell permit.". A record of permitted work requiring or allowing the construction of such work could not be found. A proposal to construct a fire barrier to reduce the fire area to below that requiring an automatic fire sprinkler system per IBC 903.2.1.2 could be included in the scope of work under this pen -nit and must include a listed fire -resistance rated wall assembly determined in accordance with test procedures set forth in ASTM E 119 or UL 263 or in accordance with IBC section 703.3. The proposed fire barrier per IBC 707.3. 1 O/Table 707.3. 10 must include the specified components of the fire -resistance rated assembly (type and thickness of the gypsum wallboard - type, size, shank diameter, and length of fasteners) and their installation criteria (wallboard installed vertically or horizontally and the panel edge offset — fastener spacing) to guide proper construction and inspection. The construction of an 6 existing' wall proposed as that meeting the requirements of IBC 707.3. 1 O/Table 707.3. 10 will be verified by the Building Inspector. Page 2 of 4 (It is confirmed that the 2 hour fire rated walls we.re pLrmitted under BLD 2015- 1265) b. Clarify on the plans the note: "Existing 45 min fire rated door to remain — Provided by shell permit.". A record of permitted work requiring or allowing the construction of such work could not be found. A proposal to protect the opening in a fire barrier to reduce the fire area to below that requiring an automatic fire sprinkler system per IBC 903.2.1.2 could be included in the scope of work under this permit and must include a listed fire -resistance rated assembly determined in accordance with test procedures set forth in NFPA 252 or UL I OC per IBC 716.5. The proposed fire door assembly, required to have a I- I /2-hour fire -resistance rating per IBC Table 716.5, must also provide smoke and draft control per IBC 716.5.3. The installation of an 'existing' fire door assembly proposed as meeting that required per IBC 716.5 will be verified by the Building Inspector — see also plan review comment '7a'. (It is con hirmed that the 45 mins fire rated door was pertnitted u.nder 131A) 2015- 12165) c. Clarify on the plans the indicated width of space '005' —'Corridor'. It does not appear to provide the required maneuvering clearance per ICC Al 17.1-2009 Section 404.2.3 at the door 'marked' ' 102' when both a door closer and latch is installed as required per IBC 716.5.9 — see also plan review comment'7b'. ((.."orridor was revised to 4� to ineet the required clearance,, see updated drawing) d. Clarify on the plans the indicated 'swing' of the door 'marked' ' 105'. It appears to reduce the required means of egress width by more than one-half as prohibited by IBC 1005.7.1. (Door 105 was removed, see updated drawinp) e. Indicate on the plans the required posting of the occupant load per IBC 1004.3.(revised see updated dravvin,, f. Indicate on the plans the required minimum ventilation rates for each of the various uses of space (occupancy classification) per IMC Table 403.3. 1. 1. The information is required for the design of the mechanical system to be installed under a separate permit. (revised,, see updated drawing) 7. Door Schedule Clarify on the plans the remark '1' for door 'marked' ' 102'. The 'existing' 45 minute fire -resistance rated door does not meet the requirements for protecting an opening in a 2-hour fire -resistance rated fire barrier used to reduce the fire area to below that requiring an automatic fire sprinkler system per IBC 903.2.1.2. (It is eonFj fined that the 45 mins fire rated door was pert-nitted under BLD 2015-1265) a. Indicate on the plans if a 'door closer' is to be installed for the doors 'marked' 103' and '104'. The indicated width of the 'corridor' does not appear to provide the required maneuvering clearance per ICC A 117.1-2009 Section 404.2.3 at the doors to space '007' — Women — and space '006' — Men - when door closers are installed. (N o el osers were provided for the door 103 ) and 104, see updated door schedule,) 8. Equipment List — The review of this proposal is only for compliance with that required by the applicable codes for the use of the space and does not include the mechanical and plumbing systems. a. Clarify on the plans the difference in the indicated quantity of items 'marked' '9'— 1 shelf work table — to be installed and of that represented on the 'Proposed Floor Plan'. (revised, see updated equipment list) b. Clarify on the plans the difference in the specified length of the item 'marked'' 1 OA' Page 3 of 4 — (3) Door Sandwich Prep Table — to be installed and of that represented on the 'Proposed Floor Plan'. (revised,, . see updated equipni eut list.) c. Verify with the manufacturer that the installation of the proposed dishwasher 'marked' ' 17' does not require a Type 11 hood per International Mechanical Code (IMC) 507.3. (Verified., the dishwasher is undereouuter dishvvasher that does iiot produce heat at)d steani. Per IMC section 5073. the type 2 hood is ortly required for dishwasher that produces heat and steani. See attached. specifIcad.on lor di,��hwasher , 9. Detail '2/A2'— Typ. Type PI Partition —Clarify on the plans the note: "Extend to bottom of structure & provide top & bottom plates to allow for vertical adjustment". The design of the walls must provide an allowance for the movement of the roof construction while still retaining the top of the wall in place. (revi sect.. see updated drawing) 10. On sheet A-3 — Proposed Reflected Ceiling Plan: 11. Provide as part of a complete permit application submittal 2015 Washington State Energy Code (WSEQ 'Compliance Forms for Commercial Buildings including R2, R3, R4 over 3 stories and all Rl' as required for the selections noted on the 'Interior and Exterior Lighting Alterations' section of the WSEC Lighting Summary — LTG -SUM — supporting the compliance of the represented installation. The completed forms must include 'LTG -SUM', 'LTG-INT-SPACE' or'LTG-INT-BLD' as applicable, and'LTG-CHK', at a minimum. Verify that the methods utilized in meeting the applicable provisions have been identified on the plans. (see provided ciiergy code) Page 4 of 4