Loading...
20170525162552.pdfMETRIA E N G I N E E R 5 PLAN REVIEW COMMENTS — R VIEW 02 Project: Madrona School Permit #: BLD20170041 Location: 9300 236th St. SW, Edmonds, WA 98020 1. There is ample time to provide the current 2015 WSEC forms and they are required for this permit submittal. As noted in the first review, specifications are not reviewed; items listed as being required to be indicated on the plans need to be included in the plan set. Metrix: See attached 2015 WSEC NREC form. Please note a new sheet M-008 has been added to provide supplemental information in regards to new NREC form. Load calcs have been provided in previous response. 2. Specifications are not reviewed as part of plan review; provide the required information on sheet M-001. Metrix: See updated M-001 with added language that design meets all latest codes. 3. Increase font size of drainage fixture units (DFU's) so they are clearly legible; some DFU callouts are not readable as the waste line blots out the text. Revise plans as required. Metrix: See updated sheets with DFU count font size increased so that plans are more legible. 4. Increase font size of water service fixture units (WSFU's) so they are clearly legible. Revise plans as required. Metrix: See updated sheets with WSFU count font size increased so that plans are more legible. 5. Specifications are not reviewed as part of plan review; provide the required information on sheet M-003. Metrix: See updated M-003 with requested information provided in plumbing fixture schedule. 6. Provide ice maker with dedicated reduced pressure backflow zone assembly. Metrix: See updated M-222 with revised flag note 3 indicating additional CW RPBA for icemaker. 7. Sheet M-122 still missing the flag notes on the plan. 1131 SW 7th Street, Suite 110 Renton, WA 98057 Office: 425 336 2822 Fax: 425 336 2802 Madrona School BLD20170041 — Mechanical Permit Review 02 05-22-2017 Page 2 Metrix: Per further review, there are 2 flag notes on M-122 and each is called out once. No additional revisions necessary. 8. Specifications are not reviewed as part of plan review; provide the required information on sheet M-221. Metrix: See updated M-221 with flag note 2 indicating requested language. 9. EF-09 is not shown on sheet M-322. What is the vent pipe material? Indicate both on plan. Metrix: EF-09 has now been added to M-322. Flag Note 20 has been added to call out venting material. 10. Who is providing the hoods is not an issue; the kitchen hoods need to be included in a mechanical permit review. That can either be part of this review or be submitted under a separate permit submittal. Metrix: Per phone conversation with both Leif Bjorback and Steven Rainbow, it has been agreed upon that the kitchen hood portion of the mechanical permit shall be provided as a deferred submittal. During construction, Metrix shall provide the City of Edmonds the approved submittal with review for final AHJ approval. This will be a Type 11 hood as approved by Leif Bjorback through email on 8/4/2016 to Andy Drissell (attached email for reference). 11. Following review of the fume hood Spec sheet, please verify exhaust air flow rate for the exhaust fan matches the specified hood. Metrix: See updated M-005 with exhaust fan airflow that matches max airflow through specified fume hood. METRIX ENGINEERS From: Biorback, Lei To: "Andy Drissell" Cc: "Wilton. Taine E. (ESC)"; Nelson, Michael S. (ESC); Laura Bourland flaura(G)haidesign.com ; Brady Bell; Erik 01non; Corric Rosen; T�nner Kircho ; Biorback, Leif Subject: RE: Madrona Replacement School (ESD) - Type II Hood Inquiry Date: Thursday, August 04, 2016 5:19:12 PM Attachments: image001.prig imacieO02,onq imaQe003.onQ image004.pno Andy, it seems reason a b I e that a Type 11 hood shou I d be sufficient for the needs of the kitchen as you describe. Please include this same rationale on the permit drawings. Thanks, .Leif Byorback Building Official City of Edmonds (425) 771-0220 x 1380 Development Services Permit Center Hours: Monday, Tuesday, Thursday & Friday 8:00 AM — 4:30 PM Wednesdays 8:30 to noon From: Andy Drissell [mailto:ADrissell@MAHLUM.com] Sent: Tuesday, August 02, 2016 3:23 PM To: Bjorback, Leif Cc: 'Wilton, Taine E. (ESC)'; Nelson, Michael S. (ESC); Laura Bourland (laura@haidesign.com); Brady Bell; 'Erik Olnon'; Corrie Rosen; Tanner Kirchoff Subject: Madrona Replacement School (ESD) - Type II Hood Inquiry Hello Leif, We would like to confirm that a Type II hood is acceptable for the Madrona Replacement School kitchen. We assume that you require an explanation of what type of food will be prepared in the oven and the general kitchen practices with the double stack convection ovens. Per the Nutrition Services department for Edmonds School District, Nutrition Services staff heat breakfast sausage pizza, cheese omelets, and egg and cheese wraps. The kitchens require the ability to reheat food if it doesn't come to the kitchen at the proper temperature. Please note that the food is precooked and therefore produces minimal, if any, grease or smoke when reheated in the convection ovens. Please let us know if you require additional information to confirm that a Type II is acceptable in our application. Many thanks, Andy Drissell AIA LEED AP BD+C Mahlum I Architects Inc. (206) 816-1058 d (206) 441-4151 p (206) 441-0478 f