2017-0570 Bucatini TI-remodel - Peter Schroeder Arch.pdfOV EQ_4 City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: May 23, 2017 TO: Hots Sands LLC, D.B.A 'Bucatini' Peter Lamb peterlamb 1147 @ gmail. com FROM: Chuck Miller, Plans Examiner RE: Plan Check: BLD2017-0570 Project Address: 9818 Edmonds Way Project: Bucatini tenant improvement -remodel Scope: Tenant improvement -addition for restaurant — A-2 occupancy group — 123 occupants — VB construction - NFPA- 13 sprinkler system required — mechanical, plumbing, fire sprinkler, fire alann, etc. under separate permits Please be advised that the building plans for the above referenced project have been disapproved for the purposes of obtaining a building permit. During a review of the plans by the Building Division for compliance with the applicable building codes, it was found that the following information, clarifications, or changes are needed. Reviews by other divisions, such as Planning, Engineering, or Fire, may result in additional comments that require attention beyond the scope of this letter. A complete review cannot be performed until the revised plans/documents, including a written response in itemized letter format indicating where the 'clouded' or otherwise hi2hli2hted chan2es can be found on the revised plans, have been submitted to a Permit Coordinator. Resubmittals must be made at the Development Services Department on the 2 d Floor of City Hall. Permit Center hours are M, T, Th, & F from 8am-4:30pm and from 8:30am-12pm on Wednesdays. General plan review note: 1. Provide as part of a complete permit application submittal a copy of the required review approval letter from the Environmental Health Division of the Snohomish Health District for the proposed project per the City of Edmonds 'Tenant Improvement Permit Submittal Requirements'. On sheet Al — Project Data — Site Plan — Vicinity Plan: 2. Project Data a. Indicate on the plans the required automatic fire sprinkler system for fire areas with an occupant load of 100 or more per International Building Code (IBC) 903.2.1.2, Item 2 — see also plan review comment '2.c' b. Occupancy Group — Change on the plans the indicated occupancy classification to that of the use of a space for assembly purposes intended for food and/or drink consumption. c. Occupancy Load - Clarify on the plans the accounting of the functions of use of the proposed tenant space per IBC Table 1004.1.2. Approximately 25% of the 'occupiable' space has not been accounted for. Standing areas and seating types different than tables and chairs, such as the area just inside the entrance (typically used as 4waiting areas'), barstools at the 'lunch counter' and the 'bar', and the 'booths' indicated on sheet 'A2', have specific occupant loads factors. Other 'occupiable' areas, such as the 'kitchen' and the restrooms and the walkways leading to them, also need to be accounted for — see attachment 'occupant load'. Change on the plans the noted occupant loads in response to the above information. Detail B — 2-Hour Area Separation Wall — Clarify on the plans the proposed construction criteria of the 2-hour fire -resistance rated wall. It does not appear to reflect that found in IBC Table 721.1(2), the Gypsum Association 'Fire Resistance Design Manual, the Underwriters Laboratories 'Certifications Directory', or other referenced resources. A listed fire -resistance rated wall assembly determined in accordance with test procedures set forth in ASTM E 119 or UL 263 or in accordance with IBC section 703.3 must include the specified components of the fire -resistance rated assembly (type and thickness of the gypsum wallboard - type, size, shank diameter, and length of fasteners) and their installation criteria (wallboard installed vertically or horizontally and the panel edge offset — fastener spacing) to guide proper construction and inspection. Columns supporting the 'existing wood beam' must be noted on the plans and be fully enclosed by the fire -resistance rated wall construction or be protected with a fire -resistance rated assembly intended for columns. On sheet A2 — Floor Plan — Plumbing Plan: 4. Lighting Plan - Provide as part of a complete permit application submittal 2015 Washington State Energy Code (WSEQ 'Compliance Forms for Commercial Buildings including R2, R3, R4 over 3 stories and all Rl' as required for the selections noted on the 'Building Additions' section of the WSEC Lighting Summary — LTG -SUM — supporting the compliance of the represented installation. The completed forms must include 'LTG -SUM', 'LTG-INT-SPACE' or 'LTG-INT-BLD' as applicable, and 'LTG-CHK', at a minimum. The 'Light Fixture Schedule' must include the lighting fixture wattage and a lighting control narrative must be provided to verify that the methods utilized in meeting the applicable provisions have been identified on the plans. 5. Plumbing Plan — The review of this proposal is only for compliance with that required by the applicable codes for the use of the space and does not include the mechanical and plumbing systems. The purpose of the following notes is to highlight items represented on these plans that require specific information to be noted on the plans prepared for the separate permit application submittal(s). a. Provide information from the manufacturer of the 'glass washer' that the installation does not require a Type Il hood per International Mechanical Code (IMC) 507.3. An HVAC system design that incorporates the heat and moisture loads from the appliances or a separate removal system are acceptable alternatives that must be noted on the plans. Page 2 of 3 b. Note on the plans if the installation of a beverage dispenser utilizing a carbonator and the installation of backflow prevention device to protect the potable water supply to a carbonator is proposed as part of the project. All fixtures/equipment/appliances requiring a connection to the potable water supply system must be indicated on the plans. 6. Main Floor Plan a. Indicate on the plans the required posting of the occupant load per IBC 1004.3. b. Indicate on the plans the required minimum ventilation rates for each of the various uses of space (occupancy classification) per IMC Table 403.3. 1. 1. The information is required for the design of the mechanical system to be installed under a separate permit. c. Indicate on the plans the accessible seating and standing spaces distributed throughout the various areas of the facility. At least 5 percent, but not less than one, in each area must be accessible per IBC 1108.2.9. 1. The use of fixed tables and seating requires a clear floor space per ICC Al 17.1-2009 section 305, with exceptions for knee and toe clearance below drink surfaces 12 inches or less in depth. Movable tables and seating can be positioned/removed to accommodate as needed. The tops of accessible dining surfaces must be a minimum of 28 inches and a maximum of 34 inches above the floor. d. Indicate on the plans the required accessible toilet facility installations and placement of grab bars, dispensers, and other features in the 'existing restrooms' to meet the requirements IBC Table 2902.1/1109.2 and ICC Al 17.1-2009 section 603. 1. The costs of providing the accessible route per International Existing Building Code (IEBC) 410.7 are not required to exceed 20 percent of the costs of the alterations affecting the area of primary function. e. Clarify on the plans the placement of the required exits per IBC 1006.2. 1. The indicated distance does not appear to meet that required per IBC 1007. 1. 1 unless an automatic sprinkler system is installed as noted in plan review comment '2.a'. f. Indicate on the plans the following information regarding the 'seasonal patio': • If there is not a surrounding enclosure and the specifics of construction if there is. • The type of provided seating. • The means of egress. g. Wall Legend - Clarify on the plans the note: "Area Separation Wall — existing". A record of permitted work requiring or allowing the construction of such work could not be found. A proposal to construct a fire barrier to reduce the fire area to below that requiring an automatic fire sprinkler system per IBC 903.2.1.2 could be included in the scope of work under this permit and must include a listed fire -resistance rated wall assembly determined in accordance with test procedures set forth in ASTM E 119 or UL 263 or in accordance with IBC section 703.3. The proposed fire barrier per IBC 707.3. 1 O/Table 707.3. 10 must include the specified components of the fire - resistance rated assembly (type and thickness of the gypsum wallboard - type, size, shank diameter, and length of fasteners) and their installation criteria (wallboard installed vertically or horizontally and the panel edge offset — fastener spacing) to guide proper construction and inspection. The construction of an 'existing' wall proposed as that meeting the requirements of IBC 707.3. 1 O/Table 707.3. 10 will be verified by the Building Inspector. Page 3 of 3