2017-0586 Thai By Day TI-remodel 2- Peter Schroeder Arch.pdfCity of Edmonds. PLAN R.EVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: July 7, 2017 TO: Jeff Oaklief joakliefg J-arch.com FROM: Chuck Miller, Plans Examiner RE: Plan Check: BLD2017-0586 - 2nd review Project Address: 182 Sunset Avenue S Project: Thai By Day tenant improvement Scope: Add non -bearing interior walls and reconfigure space for restaurant — A-2 occupancy group — 102 occupants — VB construction - NFPA- 13 sprinkler system required — mechanical, plumbing, fire sprinkler, fire alarm, etc. under separate permits Please be advised that the building plans for the above referenced project have been disapproved for the purposes of obtaining a building permit. During a review of the plans by the Building Division for compliance with the applicable building codes, it was found that the following information, clarifications, or changes are needed. Reviews by other divisions, such as Planning, Engineering, or Fire, may result in additional comments that require attention beyond the scope of this letter. Items that recur on this list appear in italics. A complete review cannot be performed until the revised plans/documents, including a written response in itemized letter format indicating where the 'clouded' or otherwise highli2hted changes can be found on the revised plans, have been submitted to a Permit Coordinator. Resubmittals must be made at the Development Services Department on the 2nd Floor of City Hall. Permit Center hours are M, T, Th, & F from 8am-4:30pm and from 8:30am-12pm on Wednesdays. General plan review note: 1. Resolved - A copy of the required review approval letter from the Environmental Health Division of the Snohomish Health District for the proposed project has been received. On sheet A- 1. 0 — Project Info: 2. Project Information —Building Code Notes a. Occupancy Load Calculations — Resolved - The accounting of the functions of use of the proposed tenant space per International Building Code (IBC) Table 1004.1.2 and IBC 1004.4 and the noted occupant loads have been changed on the plans. b. Occupancy Separation — Resolved - The note: "Occupancy A/B No Separation Required" has been changed on the plans. 3. Occupancy and Exit Diagram a. Resolved - The length factor used to determine the occupant load along each side of the dining area has been changed to coincide with that to be used for fixed seating without dividing arms per IBC 1004.4 on the plans. b. Resolved — Walls have been added such that the means of egress shall not pass through kitchens, storage rooms, or spaces used for similar purposes per IBC 10 16.2, Item 5 on the plans. c. Resolved - The indicated 'swing' of the door 'marked' 'D04' has been changed to a sliding door on the plans that does not reduce the required means of egress width by more than one-half as prohibited by IBC 1005.7. 1. On sheet A-2.0 — Plans/Schedules/Details: 4. Floor Plan a. Resolved - The required posting of the occupant load per IBC 1004.3 has been indicated on the plans. b. Resolved - The accessible seating and standing spaces distributed throughout the various areas of the facility per IBC 1108.2.9.1 have been indicated on the plans. c. Resolved - The indicated width of the hallway leading to the restrooms has been changed to provide the required maneuvering clearance at the door 'marked' 'D02' per ICC A 117.1-2009 Section 404.2.3 on the plans. d. Resolved - The indicated width of the hallway leading to the restrooms has been changed on the plans to provide the required maneuvering clearance at the door 'marked' 'D03' per ICC Al 17.1-2009 Section 404.2.3 when a door closer is installed. The proposed installation of 'door closers' has been eliminated from the 'Door Schedule'. e. Resolved - The indicated 'swing' of the door 'marked' 'D04'has been changed to a sliding door on the plans that does not reduce the required means of egress width by more than one-half as prohibited by IBC 1005.7. 1. f. Resolved - The callout for the equipment 'marked' '2' in the space 'Cook Line' has been changed on the plans. g. Resolved - The represented width between the equipment 'marked' ' I V and the equipment 'marked' 16' and '9' has been increased on the plans to provide the required minimum clear width per IBC 1103.2.3 and ICC A 117.1-2009 section 403.5. h. Resolved - The section callout '08' in the space 'Host' has been changed on the plans to indicate the 'detail' and the 'sheet' where it can be found. i. Resolved - The section callout '09' in the 'bar' has been changed on the plans to indicate the 'detail' and the 'sheet' where it can be found. Page 2 of 3 Equipment Schedule a. Resolved - The difference in the indicated quantity of items 'marked' ' 6' — Hand Sink, Wall Mount — to be installed and of that represented on the 'Floor Plan' has been addressed on the plans. b. Resolved - The difference in the indicated quantity of items 'marked' ' 9' — Shelving, Wall Mounted 72"W x 12"D — to be installed and of that represented on the 'Floor Plan' has been addressed on the plans. c. Resolved - The difference in the indicated quantity of items 'marked' ' 12' — Over shelf 72"L x 12"W x 30"H — to be installed and of that represented on the 'Floor Plan' has been addressed on the plans. d. Resolved - The difference in the indicated quantity of items 'marked' ' 14' — Work Table 18"W x 30"D x 35"H — to be installed and of that represented on the 'Floor Plan' has been addressed on the plans. 6. Wall Types —Wall types 'W-2' and 'W-3'— Resolved -The proposed attachment at the base and top of the full -height walls and at the base of the 'half -walls' at the 'bar' and 'entry' has been addressed on the plans. On sheet A-4.0 — Reflected Ceiling Plan: 7. Reflected Ceiling Plan — Partially resolved - I TG XT S-A4 CE' or I TG INT BLD' as applieable; and I TG GHKI, at a minimum. The provided information must include a lightingfixture schedule with wattage and control narrativeper WSEC C103.2 to verify that the methods utilized in meeting the applicable provisions have been identified on the plans. The response to the earlier plan review comment states: "See updated Reflected Ceiling Plan and WSEC forms.". A 'lighting fixture schedule' indicating the type and wattage of each of the proposed lighting fixtures to be installed could not be found on the plans. Additional plan review comments regarding resubmitted construction documents: On sheet A-2.0 — Plans/Schedules/Details: Floor Plan — Specify on the plans each of the applicable 'wall types' to be constructed at the various locations represented on the plans. The 'callouts' to the wall types appear to have been eliminated/removed from the resubmitted plans. Page 3 of 3