Reviewer:
BLD20170615 � Laughtland Residence
Brad Shipley
Associate Planner
City of Edmonds Planning Division
121 5th Ave N Edmonds WA 98020
(425) 771-0220 ext. 1367
Brad.Shipley@)edmondswa.go
926 Walnut Street
1. Lot Area: The lot area shown includes both lots. Please only show area for lot being
developed. Re -calculate lot coverage as necessary.
Response: See updated Lot Coverage Calculations Sheet AO.
2. Lot Line Dimensions: Lot line dimensions shown along southern border are incorrect.
Please correct.
Response: See updated Site Plan Sheet AO.
Reviewer:
Eric Carter
Plans Examiner
City of Edmonds Planning Division
121 5th Ave N Edmonds WA 98020
425-771-0220 x 1389
eric.carterC@edi-nondswa.ciov
1. The energy notes indicate the home will comply with the prescriptive requirements of table
R402.1.1. The home must also comply with section R406 of the Washington State energy
code. Section R406 requires additional energy credits to be utilized to further benefit the
energy efficiency of the home. Please select an additional 3.5 credits from table 406.2 of the
2015 Washington State energy code and add those additional credits as well as indicate the
ratings of the individual appliances to the plans.
I
1 S 16 N.
0 B A 1. A N V �
BLD20170615 � Laughtland Residence
7/13/17 1 926 Walnut Street
Response. See updated Energy Notes, Sheet A2.
2. General notes referencing smoke and CO detectors to direct wired are referenced on sheet
AO. These smoke and CO detectors have specific requirements. Please indicate the location of
each Smoke and CO detector in compliance with R314 and R315 of the 2015 IRC, including
any state amendments on the plans.
Response. See Smoke Detector Requirement Notes Sheet A2, Updated plans showing
locations, Sheet A2 & A3.
3. It appears that each door has been labeled with a number for identification. A door schedule
has not been provided on the plans. Please provide a door schedule on the plans that
identifies size and safety features if applicable.
Response: See Door Schedule, Sheet AO.1
4. The windows on the plans do not include any indicating factors. Please include on the plans
individual window sizes, egress compliance, and any applicable safety features in accordance
with section R308 of the 2015 IRC.
Response: See Window Schedule, Sheet A0.1.
S. Local exhaust fans are required in accordance with R1507.4 Please indicate on the plans the
location and CFM rating of each individual exhaust fan in accordance with R1507.4.
Response. See I st floor & 2 nd Floor HRV plans, sheet A0.1. Local exhaust in
bathrooms to have "boost" feature.
6. Whole house ventilation is required per R1507.3. Please indicate on the plans the location and
CFM rating of the selected method of ventilation in accordance with R1507.3 and any
applicable state amendments.
Response: See Ist floor & 2 nd Floor HRV plans, sheet A0.1. Local exhaust in
bathrooms to have "boost" feature.
7. Appliance impact protection is required per M1307.3.1. Please indicate on the plans the
means of impact protection for the hot water tank and furnace.
2
0 [S 16 hl I BLD20170615
Laughtland Residence
6 IJ I L 0 17/13/17 � 926 Walnut Street
BALANCE
Response. See bollard location in front of HIN tank, Sheet A2.
End of Revision 01 addressing Building & Planning Comments.