Loading...
2017-1134 Cox deck replacement.pdfOV EDAI 0 DATE: TO: FROM: City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 August 28, 2017 Quan Ho Eric Carter, Plans Examiner RE: Plan Check: BLD2017-1134 Project Address: 7409 242 nd PL SW Scope: Replacement of existing deck. Please be advised that the building plans for the above referenced project have been disapproved for the purposes of obtaining a building permit. During a review of the plans by the Building Division for compliance with the applicable building codes, it was found that the following information, clarifications, or changes are needed. Reviews by other divisions, such as Planning, Engineering, or Fire, may result in additional comments that require attention beyond the scope of this letter. Items that recur on this list appear in italics. A complete review cannot be performed until the revised plans/documents, including a written response in itemized letter format indicating where the 'clouded' or otherwise hi2hli2hted chan2es can be found on the revised plans, have been submitted to a Permit Coordinator. Resubmittals must be made at the Development Services Department on the 2 d Floor of City Hall. Permit Center hours are M, T, Th, & F from 8am-4:30pm and from 8:30am-12pm on Wednesdays. During the cursory review of the submitted building plans, several items were found to be insufficient or more clarification is needed prior to plan approval. 1. The 2x6 beams, noted on the plans are severely overstressed for the anticipated loads. This beam will need to be of a larger size, please take into account of a minimum of l0PSF of "dead load" and 60PSF of "live load" when sizing your framing members. Mybuildingpermit.com was provided. Please indicate on the provided tip sheet which options and or methods are intended as a path to compliance. 2. The 4x4 joists, noted on the plans are severely overstressed for the anticipated loads. This beam will need to be of a larger size, please take into account of a minimum of I OPSF of "dead load" and 60PSF of "live load" when sizing your framing members. Mybuildingpermit.com was provided. Please indicate on the provided tip sheet which options and or methods are intended as a path to compliance. 3. Construction details of how the lower deck will be supporting the upper deck are not shown. Please provide framing member size, spacing and connection details of how the lower deck will support the upper deck on the plans. 4. The proposed 10" x I 0"x8"concrete pier supported by a 12" cement footing does not indicate footing depth or reinforcement. A minimum of 2 #4 Rebar reinforcement each way will be required for any new footings the bottom of the footing must be located a minimum of 18" below finished grade. Furthermore; footing placed 4' on center must be a minimum of 14" x 14". Please indicate on the plans. 5. Deck ledger attachment details were not provided. Joist hangers attached directly to the house are prohibited. Please add the applicable attachment and flashing details per IRC 507.2.1 the 2015 deck tip sheet from Mybuildingpermit.com was provided. Please indicate on the provided tip which options and or methods are intended as a path to compliance. 6. Lateral load connections are required per IRC 507.2.4. Please indicate the type and locations of connections to be used on the plans. Mybuildingpermit.corn was provided. Please indicate on the provided tip sheet which options and or methods are intended as a path to compliance. Please let me know if I can be of any further assistance. Sincerely, Eric Carter Page 2 of 3 Page 3 of 3