PLAN REVIEW COMMENTS
. ..... BUILDING DIVISION
(425) 771-0220
DATE: September 11, 2017
TO: Minoo Anklesaria
buckmeher(&hottnai1.co
FROM: Eric Carter, Plans Examiner
RE: Plan Check: BLD2017-1144
Project Address: 8302 218th ST SW
Scope: Addition/ Carport
Please be advised that the building plans for the above referenced project have been disapproved
for the purposes of obtaining a building permit. During a review of the plans by the Building
Division for compliance with the applicable building codes, it was found that the following
information, clarifications, or changes are needed. Reviews by other divisions, such as Planning,
Engineering, or Fire, may result in additional comments that require attention beyond the scope of
this letter. Items that recur on this list appear in italics.
A complete review cannot be performed until the revised plans/documents, including a
written response in itemized letter format indicatin2 where the (clouded' or otherwise
hi2hli2hted chani!es can be found on the revised plans, have been submitted to a Permit
Coordinator.
Resubmittals must be made at the Development Services Department on the 2 d Floor of City Hall.
Permit Center hours are M, T, Th, & F from 8am-4:30pm and from 8:30am-12pm on Wednesdays.
During the cursory review of the submitted building plans, several items were found to be insufficient
or more clarification is needed prior to plan approval.
General:
1. The minimum depth of the proposed continuous footing is required to 18" below grade. Please
indicate on the plans.
2. The lumber species and grade are not shown for the roof framing and support beam. This is
required to determine the adequacy of the proposed framing. Please add to the plans.
3. A ledger is required to attach the rafters to the existing structure and appears to be indicated on
the plans. Please indicate the size and species of the ledger as well as attachment type and
spacing.
4. 15# felt is indicated as the roofing underlayment. When the roof pitch is less than a 4:12, double
layers of underlayment are required. Please indicate on the plans.
This plan review has not been completed, additional comments may be generated upon review of the
resubmitted documents. Please let me know if I can be of any additional assistance.
Eric Carter