2017-1435 Edmonds 2020 LLC MP Review02.pdfRainBOW conSULTing MECHanicaL EnginEERINg December 13, 2017 Mr. Leif Bjorback Building Official City of Edmonds 121 Fifth Avenue North Edmonds, Washington 98020-3145 Subject: Edmonds 2020 LLC BLD2017-1435 Plumbing Permit Review 02 I have received and reviewed the above referenced project for conformance with the following codes, as adopted and amended by the State of Washington and the City of Edmonds: 2015 Uniform Plumbing Code (UPC) 2015 Washington State Energy Code, WAC 51 -11 (WSEC) The comments listed below only apply to the documents submitted with the building permit application for the plumbing review: 1. General: Increase text size to 1/8" so that plans are clearly legible. Applicant response: Text has been increased. Resolved. 2. General: Provide water heater installation detail. Applicant response: Located on P12.00. Per UPC 507.5 indicate how the drainage pans located beneath the water heaters are drained to an approved location; either a floor drain, hub drain or to the outside — draining to the garage floor is not acceptable. Please indicate this on the plumbing plans. 3. General: Provide building backflow preventer installation detail. Applicant response: Located on P1 2. 00 Resolved. 4. General: Provide firestop detail for water closet installation. Applicant response: Firestop detail located on P1 2. 00 water closet flanges will be installed in fire rated PT cans i.e. Hilti or Hold Rite. Resolved. Rainbow Consulting Mechanical Engineering 336 NW 50"' Street, Seattle, WA 98107 www.rainbowconsulting-me.com Steven Rainbow, PE Phone 206.235.6002 steven@rainbowconsulting-me.com Edmonds 2020 LLC BLD2017-1435 Plumbing Review 02 December 13, 2017 Page 2 of 3 5. Sheet PO.00, Gas Piping: Indicate longest length used as the basis for gas pipe sizing-, indicate gas piping material. Provide gas piping riser diagram. Applicant response: Located on pgs. P9.00 and P13.00. Resolved. 6. Sheet P1.00: Provide a schedule including pump data, for the groundwater/storm vault. If this is scheduled elsewhere in the plan set, provide a sheet reference. Applicant response: Pump data will be provided once pumps have been chosen by building owner. Pump selections for the basis of design is required to be included with permit documents; coordinate with building owner as required. 7. Sheet P2.00: Vents have been omitted from the garage drains connected to oil/water waste line connected to the sand & oil/water interceptor. In accordance with UPC 902.1, vents are permitted to be omitted from the drains connected to the oil/water interceptor where the drains are provided with a settling tank. Provide a schedule for the garage drains indicating a catch basin or other form of settling tank. Applicant response: Schedule located on PO.01, vent has been added to the catch basin per code. Vent can be viewed on P2.00. The garage drains are required to include a settling tank (perhaps more commonly known as a catch basin). Page 275 of the UPC Illustrated Manual is attached to illustrate what is required. A schedule for the garage drains is required to include make and model number so that the inclusion of the settling tank/catch basin can be verified. 8. Sheet P2.00, The sand & oil/water interceptor has not been provided with vents as required by UPC 1017.1. The separation or vapor compartment shall be independently vented to the outer air. Where two (2) or more separation or vapor compartments are used, each shall be vented to the outer air. Additionally, the interceptor shall be vented on the sewer side and shall not connect to a flammable vapor vent. All provisions of UPC 1017.0 shall be strictly adhered to. Provide sand & oil water inceptor installation detail. Applicant response: Vent has been added and installed see P2. 00 and P3. 00 for overhead installation. Typical installation detail has been added on P12.01. The sand & oil/water separator detailed in the plans do not meet the City of Edmonds Engineering Division standards for separators. While the sizing of the separator capacity is the responsibility of the Engineer, the minimum separator size required for this project is 100 gallons. Please note that these standards are new and are different that they would have been for Phase 1 of the project. A copy of the standards is attached for review. Please include the sizing calculation on the plans along with the correct oil/water separator installation detail. 9. Sheet P2.00: The plans indicate that the sand & oil/water separator has a 2" pump line to overhead plumbing. On sheet P3.0, there appears to be another pump line connected to the sand & oil/water separator (20 GPM). Please clarify the installation. Applicant response: The 2" pump lines have been separated and drawn to the appropriate sewer or storm lines. These were installed per 710.3 (1) 20 GPM minimum. Both interceptors have been determined to receive less than 5-10 GPM. See related comments above. Rainbow Consulting Mechanical Engineering 336 NW 50"' Street, Seattle, WA 98107 www.rainbowconsulting-me.com Steven Rainbow, PE Phone 206.235.6002 steven@rainbowconsulting-me.com Edmonds 2020 LLC BLD2017-1435 Plumbing Review 02 December 13, 2017 Page 3 of 3 10. Sheets P10.00 and P11.00: Domestic water plans are incomplete. Complete plumbing design and resubmit. Applicant response: Riser diagram and typical manifold installation have been included on P14.00. Resolved. If you have any questions or require additional clarification on any of the items contained in this letter, please email me at steven@rainbowconsulting-me.com or contact me directly at 206-235-6002. Sincerely, Rainbow Consulting LLC Steven Rainbow, PE cc: Douglas Beck, Beck & Associates, PLLC, beckpllc@msn.com Enc. Rainbow Consulting Mechanical Engineering 336 NW 50"' Street, Seattle, WA 98107 www.rainbowconsulting-me.com Steven Rainbow, PE Phone 206.235.6002 steven@rainbowconsulting-me.com VENTS @Vents Not Required. 903.0 Materials. 3 kderceptor. Vent piping shall be permitted to be 903.1 Applicable Standards. Vent pipe and fittings bd on an interceptor where such interceptor acts as a shall comply with the applicable standards referenced in my settling tank and discharges through a horizontal Table 701.2, except that: =waste pipe into a secondary interceptor. The second (1) No galvanized steel or 304 stainless steel pipe shall be o*wr shall be properly trapped and vented. installed underground and shall be not less than 6 inches IM See Figure 902.1 for an illustration of this instal- (152 nim) aboveground. L Section 1009.0, Interceptors (Clarifiers) and Separa- (2) ABS and PVC DWV piping installations shall be in accor- md Section 1016.0, Sand Interceptors, are the areas dance with the applicable standards referenced in Table sed by this exception. 170 1. 1, and Chapter 14 "Firestop Protection." Except for indi- 2 Bars, Soda Fountains, and Counter. Traps vidual single-family dwelling units, materials exposed within ig sinks that are part of the equipment of bars, soda ducts or plenums shall have a flame -spread index of not more bins. and counters need not be vented where the loca- than 25 and a smoke -developed index of not more than 50 =ad construction of such bars, soda fountains, and where tested in accordance with ASTM E84 or UL 723. aws is such as to make it impossible to do so. Where 903.2 Use of Copper or Copper Alloy Tubing. conditions exist, said sinks shall discharge by means Copper or copper alloy tube for underground drainage and piroved indirect waste pipes into a floor sink or other vent piping shall have a weight of not less than that of Nwd type of r e al g e WV. IMThis s ction allows indirect waste for special ' 903.2.1 Aboveground. Copper or cop alloy tube for J where ven g is impossible. An example would be aboveground drainage and vent piping shal have a weight bar with eating around it where an adjacent wall is of not less than that of copper or copper all drainage tube le for[a vent. Traps serving soda fountains and type DWV. sinks th are part of the bar equipment may be y waste into an approved receptor. Therefore, lie 903.2.2 Prohibited Use. Copper or c per alloy tube t 8, Indire t Wastes will apply. See Figure 902.2 for shall not be used for chemical or indu ial wastes as of thi installation. defined in Section 811.0. Opeq Grill C.O� C.O. 7 _�! n n Settilling Tank Interceptor FIGURE 902.1 VENT NOT REQUIRED ON SECONDARY INTERCEPTOR Bar Sink Indirect Waste Pipe lf� , - ILI� i -; � T, -.�_ -� *,& ­0 ir�. —.' 7�f -.*:,Ip � ". U 40"'3111- Floor Sink Vented Trap Un� ented "ap FIGU NOT REQUIRED UNIFORM PLUMBING CODE ILLUSTRATED TRAINING MANUAL 275 62.5" A A 04 7-1-77' 7-/-77 Z7 7n-,7�/7 7-1--7' r// � � z � � � T PROVIDE GASKET SEALED CAP FOR INLET TEE, FOR INTERIOR INSTALLATION ONLY 2.75" NOTES: GALVANIZED DIAMOND-y COVER PLAN PLATE COVERS WITH BOLT -DOWN LOCKS PROVIDE GASKET SEALED CAP FOR OUTLET TEE, FOR INTERIOR INSTALLATION ONLY 1.5"-5- 3.5 . ADJUSTMENT SLOTS ADJUSTABLE INLET /-SAMPLING TEE BAFFLES - ���W�ATER LEVEL INLET A I I GRIT/SLUDGE 4 RETAINER WEIR A 10 �J' '-A 17.5" 8" 22.5" 14.5" SECTION AA INSPECTION/SAMPLING TEE - SEE NOTE 3 OUTLET A * (o 1. USE UTILITY VAULT COMPANY INC. MODEL #25-SA OR EQUAL. PRECAST VAULT SHALL HAVE KNOCKOUTS AT ALL PIPE OPENINGS. IF KNOCKOUTS ARE NOT PRESENT, THEN PIPE OPENINGS SHALL BE CORE -DRILLED. PIPE OPENINGS SHALL BE 2" LARGER THAN THE PIPE DIAMETER. 2. LOCATE VAULT WITHIN 20' OF DRIVE FOR ACCESS BY MAINTENANCE VEHICLES. 3. PVC INSPECTION AND SAMPLING TEE SHALL BE THE SAME SIZE AS THE OUTLET PIPE FOR 6" OUTLET OR GREATER. USE 6" BY OUTLET -SIZE TEE WHERE OUTLET PIPE SIZE IS LESS THAN 6". INSTALL GASKETED CAP ON TOP OF THE SAMPLING TEE, FOR INTERIOR INSTALLATION ONLY. 4. FILL WITH CLEAN WATER PRIOR TO START-UP OF THE SYSTEM. 5. GRAY AND BLACK WATER SHALL BE CARRIED BY SEPARATE SIDE SEWER. 6. PIPE CONNECTION TO VAULT: KOR-N-SEAL OR EQUAL FOR CORE -DRILLED OPENINGS, OR SAND COLLAR FOR KNOCKOUT OPENING. SEAL ALL PIPE CONNECTIONS WITH NONSHRINK GROUT. 7. INTERIOR OIL/WATER SEPARATORS SHALL HAVE VENTING PER 2009 UNIFORM PLUMBING CODE REQUIREMENTS. 8. PRIOR TO STARTUP, OIL/WATER SEPARATOR SHALL PASS 1% PER DAY LEAK TEST WHERE ONLY A MAXIMUM OF 1% OF DEAD STORAGE REDUCTION IS ALLOWED WITHIN A 24 HOUR PERIOD PER THE 2009 UNIFORM PLUMBING CODE 712.2. 9. ACCESS LID SHALL HAVE SLIP RESISTANT TREATMENT. CITY OF EDMONDS PUBLIC WORKS DEPARTMENT "�st. IB9- 100 GALLON BAFFLE TYPE OIL/WATER SEPARATOR APPROVED BY: R. ENGLISH REVISION DATE OCTOBER 2015 STANDARD D ETAI L E6.1 4 [—1 2" - I - 24" i 24" 1 12--1 PROVIDE GASKET SEALED CAP FOR INLET TEE, FOR INTERIOR INSTALLATION ONLY. 7- NOTES: 1 . 2. 3. 4. 5. 6. 7. 8. 4 04 r- 72" COVER PLAN �--INLET SAMPLING TEE 6 F= 6" 1 L.— I I � I I OUTLET LlMIN GRIT/SLUDGE RETAINER 39" WEIR MIN A 4 A* u u __T 9" L 4. `7 5.5" �_l 6"----l-1 2" 1 21" 1 23 SECTION A -A uk 00 It NO. 3030P GALVANIZED DIAMOND PLATE ACCESS COVER, OR EQUAL NO. 1012P GALVANIZED DIAMOND PLATE INSPECTION COVER, OR EQUAL - 2 PLACES PROVIDE GASKET SEALED CAP FOR OUTLET TEE, FOR INTERIOR INSTALLATION ONLY INSPECTION/SAMPLING TEE - SEE NOTE 3 VAULT CHART CAPACITY GALLONS 450 750-900 MODEL # 660-SA 577-SA LENGTH 6'-0" 7'-0' WIDTH 4'-0" 4'-8" HEIGHT 6'-0" 7'-0' MANUFACTURER LIV LIV USE UTILITY VAULT COMPANY INC. MODELS (SEE CHART) OR EQUAL. PRECAST VAULT SHALL HAVE KNOCKOUTS AT ALL PIPE OPENINGS. IF KNOCKOUTS ARE NOT PRESENT, THEN PIPE OPENINGS SHALL BE CORE -DRILLED. PIPE OPENINGS SHALL BE 2" LARGER THAN THE PIPE DIAMETER. LOCATE VAULT WITHIN 20' OF DRIVE FOR ACCESS BY MAINTENANCE VEHICLES. P.V.C. INSPECTION AND SAMPLING TEE SHALL BE THE SAME SIZE AS THE OUTLET PIPE FOR 6" OUTLET OR GREATER. USE 6" P.V.C. TEE WHERE OUTLET PIPE SIZE IS LESS THAN 6". INSTALL GASKETED CAP ON TOP OF THE SAMPLING TEE, FOR INTERIOR INSTALLATIONS ONLY. FILL WITH CLEAN WATER PRIOR TO START-UP OF THE SYSTEM. GRAY AND BLACK WATER SHALL BE CARRIED BY SEPARATE SIDE SEWER. PIPE CONNECTION TO VAULT: KOR-N-SEAL OR EQUAL FOR CORE -DRILLED OPENINGS, OR SAND COLLAR FOR KNOCKOUT OPENING. SEAL ALL PIPE CONNECTIONS WITH NONSHRINK GROUT. INTERIOR OIL/WATER SEPARATORS SHALL HAVE VENTING PER 2009 UNIFORM PLUMBING CODE REQUIREMENTS. PRIOR TO STARTUP, OIL/WATER SEPARATOR SHALL PASS 1% PER DAY LEAK TEST WHERE ONLY A MAXIMUM OF 1% OF DEAD STORAGE REDUCTION IS ALLOWED WITHIN A 24 HOUR PERIOD PER THE 2009 UNIFORM PLUMBING CODE 712.2 ACCESS LIDS SHALL HAVE SLIP RESISTANT TREATMENT PER SECTION S4-19 OF THE ENGINEERING STANDARDS. '�'st. JB9- REVISION DATE CITY OF EDMONDS 450-900 GALLON BAFFLE OCTOBER 2015 PUBLIC WORKS TYPE OIL/WATER STANDARD DEPARTMENT I SEPARATOR D ETAI L I APPROVED BY: R. ENGLISH I E6.1 4.1