City of Edmonds
PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
March 19, 2018
Pacific Garages
Ed-olson@pacificgarages.com
Eric Carter, Plans Examiner
Plan Check: BLD2018-0289
Project Address: 615 6t" AVE N
Scope: New accessory structure
Please be advised that the building plans for the above referenced project have been disapproved
for the purposes of obtaining a building permit. During a review of the plans by the Building
Division for compliance with the applicable building codes, it was found that the following
information, clarifications, or changes are needed. Reviews by other divisions, such as Planning,
Engineering, or Fire, may result in additional comments that require attention beyond the scope of
this letter. Items that recur on this list appear in italics.
A complete review cannot be performed until the revised plans/documents, including a
written response in itemized letter format indicatinz where the 'clouded' or otherwise
highlij!hted chani!es can be found on the revised plans, have been submitted to a Permit
Coordinator.
Resubmittals must be made at the Development Services Department on the 2 nd Floor of City Hall.
Permit Center hours are M, T, Th, & F from 8am-4:30pm and from 8:30am-12pm on Wednesdays.
This building plan review cannot be completed until we receive the following items:
Page 2:
It is not clear how the lateral design for the structure was achieved. Is this building
designed prescriptively with section 602. 10 of the 2015 International Residential Code
or has this been designed by a Washington state licensed Engineer? If this structure has
been designed by and engineer please submit plans that have been stamped by the EOR
and include calculations. If this structure has been designed prescriptively, please
reference what methods were used in the design on the plans.
Page 3:
2. The plans note 2012 code references, this plan will need to comply with the 2015 code
cycle. Please update the references to reflect the correct code cycle.
3. The plans identify 2x6 DF#2 studs spaced 16" OC for the walls but the foundation walls
do not appear to be identified. Please label the stud size, spacing and type of material of
the foundation walls on the plans.
4. Underfloor ventilation is required per IRC R408.1. Please add the required number of
vents to the plans.
5. R404.2.4 requires the foundation walls not to be backfilled until the first floor has been
constructed. Please add this information to the plans.
6. Figure R403.1 (3) indicates a minimum of 8" of clearance between the top plate of the
foundation wall and the surrounding dirt grade. The Finish grade slope must also be at a
minimum of 1/2" per foot for the first six feet surrounding the structure. Please add these
notes to the plans.
7. R 403.1 (3) requires flashing to be installed at the top of the foundation wall plywood to
prevent water intrusion. Please add this detail to the plans.
Please let me know if I can be of any additional assistance.
Eric Carter