RE: BLD2018-0465
10032 Edmonds Way
Project: Westgate Village plumbing
Dear Chuck Miller,
May 18, 2018
Attached are plumbing clouded revised prints and comments in bold to your revision requests stated below
If you have any other questions please contact me
Thankyou
Dave Van Duine
RE: BLD2018-0465 — 10032 Edmonds Way
On sheet P1.0 —General Notes, Schedules & Legends Plumbing:
Plumbing Fixture Connection Schedule — Designation P8 — Mop Sink — Change on the
plans the minimum required trap size (in inches) serving the mop sink in from '1-1/2' to
'2' per Uniform Plumbing Code (UPC) Table 702.1.
COMMENT: Schedule has been revised
On sheet P 3.0 — Level Pi — Plumbing (Above Ground):
2. Level P1 — Plumbing (Above Ground) plan
a. Provide as part of a complete permit application submittal manufacturers
specifications for the proposed water heaters to guide proper review, installation,
and inspection. Of particular concern is the proposed length and termination of the
exhaust.
b. Clarify on the plans the represented, but unidentified, drain/waste/vent in the
northwest corner of space 'P344' — Water — gridlines 'CD-C4.9. A corresponding
connection could not be found on sheet 'P4.0' — Retail & Parking Level —Plumbing.
COMMENT: Sheet P4.0 has been revised and water heater install guide is attached
RESUB
MAY 18 20%
Page I of 3
MM%%VW
6505 233rd PI SE, Woodinville, WA 98072 - (425) 643-3830 9 FAX (425) 747-3041
On sheet P5.0 — Residential Level 1 Plumbing:
3. Residential Level I —Plumbing
a. Clarify on the plans the note, "INSTALL STUDOR VENT AT KITCHEN SINK", in the
following spaces:
0 205
0 206
0 226
0 229
it does not appear to comply with that required per UPC 909-1.
b. Provide on the plans the proposed waste piping installation below the
following fixtures:
• Kitchen sink — space 303
• Kitchen sink —space 305
• Kitchen sink —space 306
• Kitchen sink —space 309
• Kitchen sink —space 310
• Kitchen sink — space 325
• Kitchen sink — space 326
• Kitchen sink — space 329
• Kitchen sink — space 330
• Kitchen sink —space 331
• Kitchen sink — space 334
COMMENT: Studor vents have been eliminated and island sink venting has been added
please see attached sheet on island sink venting the city of Bellevue allows. Is this
acceptable?
On sheet P6.0 — Residential Level 2 Plumbing:
4, Residential Level 2 — Plumbing
a. Clarify on the plans the note, "INSTALL STU DOR VENT AT KITCHEN SINK", in the
following spaces:
0 305
0 306
0 309
0 326
0 329
It does not appear to comply with that required per UPC 909-1.
b. Provide on the plans the proposed waste piping installation below the
following fixtures:
Kitchen sink —space 403
Kitchen sink —space 405
Kitchen sink — space 407
Page 2 of 3
Kitchen sink — space 422
Kitchen sink —space 425
Kitchen sink — space 428
COMMENT: Studor vents have been eliminated and island sink venting has been
added please see attached sheet on island sink venting the city of Bellevue allows. Is
this acceptable?
On sheet P7.0 — Residential Level 3
Plumbing:
5. Residential Level 3 —Plumbing —Clarify on the plans the note, "INSTALL STU DOR
VENT AT KITCHEN SINK", in the following spaces:
405
422
424
It does not appear to comply with that required per UPC 909.1.
COMMENT: Studor vents have been eliminated and island sink venting has been
added please see attached sheet on island sink venting the city of Bellevue allows. Is
this acceptable?
On sheet P10.0 — Risers Plumbing:
6. General Notes
a. Note 3 — Change on the plans the code table reference regarding the
maximum length of vent piping from '7-5'to'703.2.
b. Note 4 — Change on the plans the code table reference regarding the minimum
size of waste and vent fixtures from '7-5' to that found in the 2015 UPC.
c. Note 5 — Change on the plans the code table reference regarding the
maximum length of vent piping from '6-4'to'610.3/610.4'.
COMMENT: Notes have been revised