City of Edmonds Building Division
Attn: Chuck Miller, Plans Examiner
121 5th Avenue North
Edmonds, WA 98020
RE: Correction Notice #1
Address: 9529 244th Street SW
Reference #: BLD2018-0442
Project Name: Dr. Haberman Office Alteration
Thank you for sending review comments of the project referred above. Below are our responses (in italics)
to your letter from May 10, 2018. 1 have included the approximate wording from your correction letters for
your reference. All corrections are indicated by Revision symbol #1 on the drawing sheets.
1 Van accessible parking space to meet dimensional requirements...
AO.1 Existing Van Accessible Parking space in the existing concrete parking lot, which is outside
the scope of work of this project, has been dimensioned to show compliance with ICC A117.1-2009
Section 502.2.
2a Specify the minimum required structural member to replace the existing 6x6 wood beam to be
removed...
A1.1 Please see A2.1 Foundation plan callout which specifies 6x10 beam to replace 6x6.
2b Clarify on plan set 6"CMU shown on architectural and 8" CMU shown on structural.
S2.0 Existing CMU callout has been changed to show 6"CMU to match existing condition.
3. Clarify on plan header callouts, which don't seem to correlate with demo plan...
A1.2 Sorry for the confusion, header notes were not supposed to be visible on the demo plan.
They are shown properly in relation to the proposed work shown on A1.4 Framing Plan.
4a. Floor plan legend interferes with key notes.
A1.2 Note/legend conflict has been resolved.
4b. Clarify use of term selectively. Specifically identify wall.
A1.2 Walls to be demolished are clearly shown as dashed lines on the demolition plan. Use of
the term "selectively" is an architectural phrase which places the responsibility of the exact
location, and a clean cut and patch coordinated with the newly proposed work onto the contractor.
We could dimension walls or openings to be demolished with +/- notations, but it is simpler and
more accurate to have the contractor layout the work as proposed, and cleanly cut back existing
work as required to accommodate the new construction and patching, based on their materials and
RESUB
55 S. Atlantic Street - Suite 301 - Seattle, WA 98134 - 206.682.7525 / Fax. 206.682.7529 MAY 18 2018
WIN, 21115M�
methods of construction.
5. Wall Legend says see demo plan.
A1.2 The demo Plan is the same sheet on which the wall legend is located. We have removed the
note on the legend to avoid any further confusion.
6, Differentiate door types A and B on the plans.
AU The floor plans incorporate discrete door callouts for every new door that must be
coordinated with Door Schedule for specific door information. A door types diagram has been
added to this sheet to help clarify the difference between type A, B and C door panels.
7a. Egress plan notes — change reference to current IBC section.
AU Egress plan notes have been modified to reflect current code references. Apologies — this
design began in early 2010, and has seen many iterations over the years. We have removed the
specific code references.
7b. Egress plan notes — change reference to current IBC section.
See response to 7a.
7c. Egress plan notes — change reference to current IBC section.
See response to 7a.
7d. Egress plan notes — change reference to current IBC section.
See response to 7a.
7e. Egress plan notes — change reference to current IBC section.
See response to 7a.
8a. Main Floor Plan with exiting. Indicate location of medical gas storage and vacuum system,
A1.1 A label showing the location of the existing legally permitted medical gas storage and
vacuum systems has been added to the foundation plan.
8b. Main Floor Plan with exiting. Indicated type of furnishing in the waiting room, as it relates to
accessibility and occupant load.
AU Furnishing by owner has been shown on the plan. Waiting area occupancy rate is
calculated at 15 sf / person.
8c. Main Floor Plan with exiting. Clarify on the plans the width of the ADA counter.
A1.5 Enlarged Floor plan has been modified to show a 36" wide counter. A clear floor area for
parallel approach has been shown dashed on the plan for clarity of design compliance. Countertop
height is 30".
8d. Main Floor Plan with exiting. Show width compliance at framed opening into office
A1.5 Enlarged Floor plan has been modified to show width compliance at entry to off ice. Wall
layout has changed somewhat to create 42" clearance for side approach at both this entry, and the
Bath and Chair 5 doors as well.
55 S. Atlantic Street - Suite 301 - Seattle, WA 98134 - 206.682.7525 / Fox. 206.682.7529
8e. Main Floor Plan with exiting. Door 101 to Chair 5 clearances.
AU Door 101 push side front approach is compliant per 404.2.3.2. Hallway layout modified
somewhat to allow Door 101 latch side approach to be compliant.
8f. Main Floor Plan with exiting. Solid backing per vendor spec,
A1.1 Note has been added clarifying the requirement for backing.
8g. Main Floor Plan with exiting. Door clearances at ADA bath.
A1.1 Hallway layout has been changed somewhat to allow door clearances to meet current
standards.
8h. Main Floor Plan with exiting. Door clearances at lab.
Lab and Panograph x-ray changes have been abandoned. Both will remain as is.
8i. Main Floor Plan with exiting. Accessible access in lab.
See answer to 8h above.
8j, Main Floor Plan with exiting. Clear floor space at lab
See answer to 8h above.
8k. Main Floor Plan with exiting. Solid backing at Panograph X-ray.
A1.1 A note has been added showing the requirement for 2x8 blocking between studs at this
location.
9a. Main Floor Plan Keynotes. Reference to 2003 rather than 2009 ANSI All 17.1
A1.1 Reference has been changed to 2009.
9b. Main Floor Plan Keynotes. Door closer note conflict.
A1.1 Door schedule has been modified to eliminate closer.
9c. Main Floor Plan Keynotes. Occupancy load rate at waiting area.
A1.1 Thank you for pointing this out — there is much misinformation out in the building code
forums regarding this topic of waiting areas. After consulting ICC code officials, we agree with you
that the waiting area occupant load should be calculated at 15sf per person. We have modified the
egress notes to show compliance. The waiting area is smaller now than in the existing condition.
9d. Main Floor Plan Keynotes. Keynote 21 conflict.
A1.1 All reference to keynote 21 have been eliminated.
1 Oa. Framing Plans, elements to be demolished shown in red.
A1.4 Title has been modified. Apologies for any references to color, contactors are eager to
adopt the use of color in pdf's which adds great to legibility. City of Edmonds, like a few other
jurisdictions is still using paper, where color cannot be relied upon. We have modified any
reference to be line type specific, rather than color specific.
1 Ob. Framing Plans, callout to A2. 1.
A1.4 Mistakenly, an interior elevation callout marker was left on the framing plan. It has been
55 S. Atlantic Street - Suite 301 - Seattle, WA 98134 - 206.682.7525 / Fax. 206.682.7529
removed for clarity.
1 Oc. Framing Plans, existing roof framing member sizes, species and grade
A1.4 Please see revised sheet A1.4 for existing roof joist size/spacing and bearing wall
designation. See also attached calculations for maximum span of the roof joists with assumed
species and grade common for the age and type of building.
11. Enlarged floor plans, drawing numbers
A1.5 Drawing numbers have been changed.
12a. Enlarged Bath Plan, reference to code versions
A1.5 Code version references have been changed to reflect current code.
12b. Enlarged Bath Plan, fixture mounting heights
A1.5 A fixture mounting height diagram was inadvertently left off the sheet, it has been added.
13 Enlarged Operatory Plan, fastener requirement for blocking.
A1.5 Fastener requirement has been added with callout. Standard attachment of (6) 8d toenails
per stud end should provide required resistance to the maximum 8501b moment reaction.
14a. Enlarged Reception Plan, clear width at file cabinets
A1.5 The clear width requirement of 36" called out in section 403.5 has been indicated on the
enlarged plan.
14b. Enlarged Reception Plan, ADA counter width
A1.5 The ADA counter width has been increased to 36" to comply with service counter for parallel
approach per ANSI Al 17.1-2009 section 904.3.1
14c. Enlarged Reception Plan, door mark at storage
A1.5 Enlarged plan door mark changed to 100.
15a. Reflected Ceiling Plan, existing light fixtures to be retained
AM RCP has been updated to show existing lighting fixtures
15b. Reflected Ceiling Plan, occupancy sensor controls
A4.1 RCP has been updated to show sensor controls
15c. Reflected Ceiling Plan, time switch controls
A4.1 RCP has been updated to show required time switch controls.
16. Energy Lighting Schedule, lighting control narrative per WSEC C 103.2
AM Lighting control narrative has been added to the plan set.
17. General Structural Notes, floor live load at waiting area
55 S. Atlantic Street - Suite 301 - Seattle, WA 98134 - 206.682.7525 / Fax. 206.682.7529
S1.0 Please see revised sheet A1.4 for clarification in the waiting room. This area of the floor is not
changing use and the waiting area actually getting smaller. We verified that the floor has a capacity of
70 psf Live Load. Please see attached calculations.
18. Framing Details, column cap callout
S2.0 Column cap notation has been modified.
19. D1 Equipment Plan
Equipment plans were provided as reference only. Plumbing, electrical or mechanical work associated
with this project are all under separate permit.
20. D2 Equipment Plan
Equipment plans were provided as reference only. Plumbing, electrical or mechanical work associated
with this project are all under separate permit.
21 a. Lighting Summary LTG -SUM, building area method
LTG -SUM The form has been updated to clarify interior lighting power method.
21b. Lighting Summary LTG -SUM, Luminaire level lighting controls
LTG -SUM The form has been updated to compliance path.
21c, Lighting Summary LTG -SUM, interior and exterior lighting alterations served by the new panel
LTG -SUM The form has been updated.
22 Interior Lighting, maximum allowed lighting wattage total area used for calculation
LTG -SUM The form has been updated.
All requested corrections are clouded on the drawing sheets. Please call me if you have any questions or
comments. Thank You.